Table of Contents
Cooling Load Calculation: Complete Engineering Guide
100m² office with 10 people and 15 W/m² lighting needs approximately 8-10 kW cooling capacity.
Introduction
Cooling load calculation is the process of determining the total amount of heat that must be removed from a building space to maintain desired indoor temperature and humidity conditions, forming the foundation of HVAC system design. Cooling load consists of two main components: sensible heat (temperature change) and latent heat (moisture), with total cooling load equaling the sum of all heat gains from people, lighting, equipment, solar radiation, transmission through building envelope, ventilation, and infiltration.
Why This Calculation Matters
Accurate cooling load calculation is crucial for:
- Equipment Sizing: Selecting air conditioning equipment with correct capacity to meet peak cooling demands.
- Energy Efficiency: Avoiding oversized equipment that wastes energy through short cycling and poor humidity control.
- Occupant Comfort: Ensuring adequate cooling capacity to maintain design temperatures and humidity levels.
- Cost Optimization: Balancing initial equipment costs with long-term operating expenses and maintenance.
The Fundamental Challenge
The primary challenge in cooling load calculation lies in accurately accounting for all heat gain sources—both external (solar radiation, transmission, ventilation) and internal (people, lighting, equipment)—while considering their time-varying nature. Peak cooling loads often occur at specific times depending on building orientation and occupancy patterns, requiring analysis of multiple conditions to determine the design load. Additionally, distinguishing between sensible and latent loads is essential for proper equipment selection and humidity control. Oversizing equipment (using excessive safety factors) causes energy waste and poor dehumidification, while undersizing leads to comfort failures during peak conditions.
What You'll Learn
In this comprehensive guide, you will learn:
- The core formula and all contributing heat gain components.
- How to calculate sensible heat gains from people, lighting, equipment, solar, and transmission.
- Methods for determining latent heat gains from occupants and ventilation air.
- Equipment sizing from cooling load including tons of refrigeration conversion.
- Step-by-step examples to confidently apply ASHRAE Fundamentals methods in your projects per Chapter 18 and Standard 90.1 requirements.
This guide is designed for HVAC engineers, building designers, and facility managers who need to calculate cooling loads for residential, commercial, and industrial buildings. You will learn the fundamental calculation methods, how to determine sensible and latent heat gains, methods for sizing equipment and airflow requirements, performance metrics, and standards compliance per ASHRAE Fundamentals Handbook and Standard 90.1.
Quick Answer: How to Calculate Cooling Load for Buildings
Cooling load is the sum of sensible heat (temperature-related) and latent heat (humidity-related) that must be removed from a space.
Core Formula
Where:
- = Total cooling load (kW or BTU/h)
- = Sensible heat gain (temperature-related)
- = Latent heat gain (humidity-related)
Component Formulas
| Component | Formula | Description |
|---|---|---|
| Sensible Heat | Heat-related heat | |
| Latent Heat | Humidity-related heat | |
| Design Load | Safety factor (1.1-1.2) | |
| Equipment Sizing | Convert to tons of refrigeration |
Worked Example
Reference Table
| Parameter | Typical Range | Standard |
|---|---|---|
| Sensible Heat (People) | 70 W/person | ASHRAE |
| Latent Heat (People) | 45 W/person | ASHRAE |
| Lighting (Office) | 8-25 W/m² | Typical |
| Equipment (Office) | 15-100 W/m² | Typical |
| Ventilation (Office) | 10 L/s per person | ASHRAE 62.1 |
| Cooling Load (Office) | 50-150 W/m² | Typical |
| Cooling Load (Retail) | 80-120 W/m² | Typical |
| Cooling Load (Restaurant) | 100-150 W/m² | Typical |
| Safety Factor | 1.1-1.2 | Typical |
| Tons of Refrigeration | 1 ton = 3.517 kW | Standard |
Key Standards
ASHRAE Fundamentals Handbook: Chapter 18: Cooling and Heating Load Calculation Principles. Provides comprehensive guidance on cooling load calculation methods, heat gain components, and calculation procedures. Chapter 19 covers nonresidential cooling and heating load calculations.
ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality. Specifies minimum ventilation rates (10 L/s per person for offices) that affect cooling load calculations through ventilation heat gain.
ASHRAE Standard 90.1: Energy Standard for Buildings. Establishes minimum energy efficiency requirements including maximum U-values for building envelope and minimum equipment efficiency ratings that impact cooling load calculations.
Refrigeration load is the total amount of heat that must be removed from a space to maintain the desired indoor thermal value and humidity. It represents the rate at which heat must be extracted, measured in Watts (W) or British Thermal Units per hour (BTU/h).
Why Cooling Load Matters
- Equipment Sizing: Proper load solution ensures correctly sized air supply conditioning equipment
- Energy Performance: Oversized equipment wastes energy; undersized equipment fails to maintain comfort
- Cost Optimization: Accurate sizing minimizes initial equipment costs and operating expenses
- Comfort: Proper load computation ensures consistent degree and humidity control
- Code Compliance: Building codes require load calculations for HVAC permits
ASHRAE Standards and Methods
ASHRAE Fundamentals Handbook
The primary reference for chilling load calculations provides:
- Chapter 18: Temperature control and Heating Load Analysis Principles
- Chapter 19: Nonresidential Air conditioning and Heating Load Calculations
- Chapter 30: Energy Estimating and Modeling Methods
ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
Specifies minimum airflow rates for different space types:
- Office Spaces: 10 L/s per person
- Classrooms: 7.5 L/s per person
- Retail: 7.5 L/s per person
- Restaurants: 10 L/s per person
ASHRAE Standard 90.1: Energy Standard for Buildings
Establishes minimum energy effectiveness requirements:
- Building Envelope: Maximum U-values for walls, roofs, windows
- Equipment Productivity: Minimum EER and COP ratings
- Load Determination: Requires detailed load calculations for compliance
Heat Gain Components
AC load consists of two main components: sensible heat and latent heat.
Sensible Heat Gain
Sensible heat causes a heat level change without phase change (no moisture involved). Components include:
- People Heat Gain
- Lighting Heat Gain
- Equipment Heat Gain
- Solar Heat Gain
- Transmission Heat Gain (through building envelope)
- Airflow movement Heat Gain
- Infiltration Heat Gain
Latent Heat Gain
Latent heat is associated with moisture (humidity) and phase changes. Components include:
- People Latent Heat (respiration, perspiration)
- Atmosphere supply Latent Heat
- Infiltration Latent Heat
Heat Gain Calculation Methods
1. People Heat Gain
Heat gain from occupants depends on activity level:
Sensible Heat:
Latent Heat:
Where:
- = Number of people
- = Sensible heat gain per person (W/person)
- = Latent heat gain per person (W/person)
ASHRAE Values (Office work, sedentary):
- Sensible: 70 W/person
- Latent: 45 W/person
- Total: 115 W/person
2. Lighting Heat Gain
Heat gain from lighting fixtures:
Where:
- = Lighting power density (W/m2)
- = Floor area (m2)
Typical Values:
- Fluorescent: 15 W/m2
- LED: 8 W/m2
- Incandescent: 25 W/m2
- High-bay: 30 W/m2
3. Equipment Heat Gain
Heat gain from electrical equipment:
Where:
- = Equipment power density (W/m2)
- = Floor area (m2)
Typical Values:
- Office: 20 W/m2
- Server room: 100 W/m2
- Kitchen: 50 W/m2
- Retail: 15 W/m2
4. Solar Heat Gain
Heat gain through windows from solar radiation:
Where:
- = Window area (m2)
- = Solar radiation intensity (W/m2)
- = Solar Heat Gain Coefficient (0-1)
- = Shading coefficient (0-1)
SHGC Values (ASHRAE):
- Single glass: 0.86
- Double glass: 0.76
- Low-E glass: 0.40
- Tinted glass: 0.50
- Reflective: 0.20
Shading Coefficients:
- No shading: 1.0
- Light blinds: 0.7
- Medium blinds: 0.5
- Heavy drapes: 0.3
- Exterior shading: 0.2
5. Transmission Heat Gain
Heat gain through building envelope (walls, roof, windows):
Where:
- = U-value (W/(m2·K))
- = Surface area (m2)
- = Temp difference (°C)
Typical U-Values (ASHRAE):
- Walls:
- Uninsulated: 2.5 W/(m2·K)
- Insulated: 0.5 W/(m2·K)
- Well insulated: 0.3 W/(m2·K)
- Roof:
- Uninsulated: 3.0 W/(m2·K)
- Insulated: 0.4 W/(m2·K)
- Well insulated: 0.25 W/(m2·K)
- Windows:
- Single: 5.7 W/(m2·K)
- Double: 2.8 W/(m2·K)
- Triple: 1.8 W/(m2·K)
- Low-E: 1.5 W/(m2·K)
6. Ventilation Heat Gain
Heat gain from outdoor ventilation air fresh air circulation:
Sensible Heat:
Latent Heat:
Where:
- = Volumetric airflow rate (m3/s)
- = Air supply density (1.204 kg/m3 at 20°C)
- = Specific heat of airflow (1005 J/(kg·K))
- = Latent heat of vaporization (2,450,000 J/kg)
- = Thermal reading difference (°C)
- = Humidity ratio difference (kg/kg)
Atmosphere exchange Rates (ASHRAE 62.1):
- Office: 10 L/s per person
- Classroom: 7.5 L/s per person
- Retail: 7.5 L/s per person
- Restaurant: 10 L/s per person
7. Infiltration Heat Gain
Heat gain from uncontrolled ventilation air leakage:
Where:
- = Fresh air changes per hour
- = Room volume (m3)
Typical Infiltration Rates:
- Tight construction: 0.1 ACH
- Average construction: 0.5 ACH
- Loose construction: 1.0 ACH
Total Cooling Load Calculation
Sensible Cooling Load
Where:
- = People sensible heat gain
- = Lighting heat gain
- = Equipment heat gain
- = Solar heat gain
- = Transmission heat gain (walls, roof, windows)
- = Airflow supply sensible heat gain
- = Infiltration sensible heat gain
Latent Cooling Load
Where:
- = People latent heat gain
- = Airflow latent heat gain
- = Infiltration latent heat gain
Total Cooling Load
Design Cooling Load (with Safety Factor)
Where = Safety factor (typically 1.1 to 1.3)
Equipment Sizing
Cooling Capacity
Refrigeration equipment is sized based on the design chilling load:
Tons of Refrigeration:
Where 1 ton = 3.517 kW (12,000 BTU/h)
Kilowatts:
Airflow Requirements
Required airflow for sensible temperature control:
Where = Supply fresh air heat difference (typically 8-12°C)
Conversion to CFM:
Where 1 m3/s = 2118.88 CFM
Worked Example: Real-World Office Cooling Load Calculation
Performance Metrics
Load per Area
Typical Values:
- Low: < 50 W/m2
- Moderate: 50-100 W/m2
- High: 100-150 W/m2
- Very High: 150-200 W/m2
- Critical: > 200 W/m2
Load per Volume
Typical range: 20-80 W/m3
Load per Person
Typical range: 100-300 W/person
Common Mistakes and Best Practices
Common Mistakes
- Oversizing Equipment: Using excessive safety factors (>1.3) wastes energy
- Ignoring Internal Gains: Underestimating people, lighting, and equipment heat
- Incorrect U-Values: Using outdated or incorrect thermal properties
- Solar Heat Gain: Underestimating solar heat gain through windows
- Airflow Load: Not accounting for air supply movement and infiltration properly
- Latent Load: Ignoring latent heat gain from humidity
Best Practices
Professional Tip: Document all design assumptions, input parameters, and safety factors. This ensures code compliance, simplifies future modifications, and provides clear audit trails for inspections.
- Use ASHRAE Standards: Follow ASHRAE Fundamentals Handbook methods
- Account for All Heat Sources: Include all internal and external heat gains
- Consider Peak Loads: Design for worst-case conditions
- Apply Reasonable Safety Factors: Use 1.1-1.2 for typical applications
- Verify with Multiple Methods: Cross-check calculations with different methods
- Consider Part-Load Operation: Design for variable loads with staging
- Document Assumptions: Clearly document all input parameters and assumptions
Advanced Considerations
Diversity Factors
For multiple spaces, apply diversity factors to account for non-simultaneous peak loads:
- Office Buildings: 0.7-0.8
- Residential: 0.5-0.7
- Retail: 0.6-0.8
Time-Dependent Loads
AC loads vary throughout the day:
- Solar Heat Gain: Peaks at midday
- Occupancy: Varies with building use
- Equipment: May have scheduled operation
- Airflow supply: May be reduced during unoccupied hours
Zoning Strategies
Divide buildings into thermal zones:
- Exterior Zones: High solar and transmission loads
- Interior Zones: Primarily internal heat gains
- North vs. South: Different solar exposure
- East vs. West: Different peak times
Conclusion
Accurate cooling load calculation is essential for proper HVAC system design. By understanding the principles, following ASHRAE standards, and applying the methods outlined in this guide, engineers can ensure energy-efficient, cost-effective, and comfortable building environments.
Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.
Key Takeaways
Core Formula
Total cooling load is the sum of sensible and latent heat components:
Where:
- Sensible heat () causes temperature change—typically 70-80% of total load
- Latent heat () affects humidity through moisture—typically 20-30% of total load
Essential Heat Sources
Account for ALL heat gain components in your calculations:
| Component | Sensible | Latent | ASHRAE Standard |
|---|---|---|---|
| People | 70 W/person | 45 W/person | Fundamentals Handbook |
| Lighting | 8-25 W/m2 | — | Technology dependent |
| Equipment | 15-100 W/m2 | — | Usage dependent |
| Solar | Variable | — | SHGC × SC × Area |
| Transmission | — | Envelope dependent | |
| Ventilation | ASHRAE 62.1 | ||
| Infiltration | ACH-based | ACH-based | Construction dependent |
Critical: Missing any component leads to undersized equipment and comfort failures.
ASHRAE Standard Values
Use ASHRAE Fundamentals Handbook values for reliable calculations:
- People heat gain: 115 W/person total (70 W sensible + 45 W latent) for office work
- Ventilation rates: 10 L/s per person for offices (ASHRAE 62.1)
- U-values: Modern insulated walls 0.3-0.5 W/(m2·K), roofs 0.25-0.4 W/(m2·K)
- Solar Heat Gain Coefficient (SHGC): 0.20 (reflective) to 0.86 (single glass)
Safety Factor Application
Apply safety factor of 1.1-1.2 to design load:
Guidelines:
- 1.1 (10%): Well-documented projects with low uncertainty
- 1.2 (20%): Standard practice for most applications
- >1.3: Avoid—causes oversizing, energy waste, and poor humidity control
Equipment Sizing
Size equipment based on design cooling load:
Where 1 ton = 3.517 kW (12,000 BTU/h)
Selection criteria:
- Select next standard size ≥ calculated capacity
- Verify airflow: 350-450 CFM per ton
- Match Sensible Heat Ratio (SHR) to application requirements
- Ensure compliance with ASHRAE 90.1 efficiency standards
Load Density Verification
Verify load density against typical ASHRAE values:
| Building Type | Typical Range | Notes |
|---|---|---|
| Residential | 40-80 W/m2 | Lower internal gains |
| Office | 50-150 W/m2 | Standard glazing, moderate gains |
| Retail | 80-120 W/m2 | High lighting, customer density |
| Restaurant | 100-150 W/m2 | Cooking equipment, high occupancy |
| Server Room | 200-400 W/m2 | High equipment density |
Red flag: If your calculated load density significantly exceeds these ranges, review:
- Solar heat gain assumptions (window area, SHGC, shading)
- Ventilation rates (may be too high)
- Internal gains (equipment/lighting power density)
- Building envelope U-values (may be outdated)
Further Learning
- Heat Loss Guide - Building heat loss calculations
- Duct Sizing Guide - Air distribution design
- Psychrometric Guide - Air properties and processes
- Cooling Load Calculator - Interactive calculator for cooling load calculations
References & Standards
Primary Standards
ASHRAE Fundamentals Handbook Chapter 18: Cooling and Heating Load Calculation Principles. Provides comprehensive guidance on cooling load calculation methods, heat gain components, and calculation procedures. Chapter 19 covers nonresidential cooling and heating load calculations.
ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality. Specifies minimum ventilation rates (10 L/s per person for offices) that affect cooling load calculations through ventilation heat gain.
ASHRAE Standard 90.1 Energy Standard for Buildings. Establishes minimum energy efficiency requirements including maximum U-values for building envelope and minimum equipment efficiency ratings that impact cooling load calculations.
Supporting Standards & Guidelines
AHRI Standards Air-Conditioning, Heating, and Refrigeration Institute certification programs. Provides performance rating standards for HVAC equipment.
EN 14511 Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers. European standard for AC equipment testing and rating.
Further Reading
- ASHRAE Technical Resources - American Society of Heating, Refrigerating and Air-Conditioning Engineers resources
Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.
Disclaimer: This guide provides general technical information based on international HVAC standards. Always verify calculations with applicable local codes and consult licensed professionals for actual installations. HVAC system design should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.