Table of Contents
Psychrometric Processes and Air Conditioning Calculations
At 30°C DB with W = 0.0135 kg/kg: h = 1.006×30 + 0.0135×(2501 + 1.86×30) = 64.7 kJ/kg
Introduction
In August 2019, the Louvre Abu Dhabi's art conservation team discovered moisture condensation forming on priceless artifacts despite the museum's $50 million HVAC system operating at full capacity. The problem wasn't equipment failure—it was a psychrometric miscalculation. Engineers had designed for 22°C at 50% RH (dew point 11.3°C), but the building's massive dome created microclimates where air stratified to 18°C at floor level. When warm, humid air from the upper zones contacted the cooler surfaces, condensation occurred even though the room "met spec." The $3.2 million remediation required complete recalculation of air distribution using proper psychrometric analysis—a cost that would have been avoided if the original design had properly plotted air states throughout the space.
Psychrometrics is the study of the physical and thermodynamic properties of moist air and the processes that change these properties, forming the foundation of HVAC system design and air conditioning calculations.
Psychrometric charts graphically represent moist air properties at constant pressure, showing relationships between temperature, humidity, and energy through seven key properties: dry bulb temperature, humidity ratio, relative humidity, wet bulb temperature, enthalpy, specific volume, and dew point temperature.
Why This Analysis Matters
Accurate psychrometric analysis is crucial for:
- Equipment Sizing: Determining the sensible and latent cooling loads for proper air conditioning equipment selection.
- Comfort Control: Maintaining indoor temperature and humidity within ASHRAE Standard 55 comfort zone requirements.
- Condensation Prevention: Identifying dew point conditions to prevent moisture damage on cold surfaces.
- Energy Optimization: Designing efficient air handling processes that minimize heating and cooling energy consumption.
The Fundamental Challenge
The primary challenge in psychrometric analysis lies in understanding the interdependence of moist air properties and how they change during HVAC processes. Cooling, heating, humidification, dehumidification, and mixing processes all follow specific paths on the psychrometric chart, each with distinct energy and moisture implications. Distinguishing between sensible heat (temperature change) and latent heat (moisture change) is essential for proper equipment selection—air conditioning systems must handle both components, and the sensible heat ratio (SHR) determines equipment performance. Additionally, altitude affects psychrometric calculations as air density and saturation properties change with atmospheric pressure.
What You'll Learn
In this comprehensive guide, you will learn:
- How to read psychrometric charts and identify the seven key air properties.
- Formulas for calculating humidity ratio, enthalpy, dew point, and wet bulb temperature.
- Analysis methods for cooling, heating, humidification, and dehumidification processes.
- Air mixing calculations for ventilation and economizer design.
- Step-by-step examples applying ASHRAE Fundamentals psychrometric methods.
Quick Answer: How to Read Psychrometric Charts
Psychrometric charts graphically represent moist air properties at constant pressure, showing relationships between temperature, humidity, and energy.
Key Properties on Chart
| Property | Location | Description | Typical Range |
|---|---|---|---|
| Dry Bulb (DB) | Horizontal axis | Air temperature (°C) | Comfort: 20-26°C |
| Humidity Ratio (W) | Vertical axis | Moisture content (kg/kg dry air) | 0.002-0.025 |
| Relative Humidity (RH) | Curved lines | Moisture percentage | Comfort: 40-60% |
| Wet Bulb (WB) | Diagonal lines | Evaporative cooling limit | DB |
| Enthalpy (h) | Diagonal lines | Total heat content (kJ/kg) | 45-100 |
| Dew Point (DP) | Horizontal to saturation | Condensation heat | -10 to 20°C |
| Specific Volume (v) | Diagonal lines | Ventilation air density (m3/kg) | ~0.85 |
Worked Example
Key Formula
Reference Table
| Property | Symbol | Typical Range | Standard |
|---|---|---|---|
| Dry Bulb Temperature | DB | 20-26°C (Comfort) | ASHRAE 55 |
| Wet Bulb Temperature | WB | ≤ DB | Typical |
| Relative Humidity | RH | 40-60% (Comfort) | ASHRAE 55 |
| Humidity Ratio | W | 0.002-0.025 kg/kg | Typical |
| Enthalpy | h | 45-100 kJ/kg | Typical |
| Dew Point | DP | -10 to 20°C | Typical |
| Specific Volume | v | ~0.85 m³/kg | Typical |
Per ASHRAE Standard 55-2020. Summer conditions allow slightly higher temperatures (up to 26°C) with increased air movement.
Key Standards
ASHRAE Fundamentals Handbook: Chapter 1: Psychrometrics. Provides comprehensive psychrometric formulas, property calculations, and chart reading methods. Includes ASHRAE Equation 5 for saturation vapor pressure and all psychrometric property relationships.
ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy. Specifies comfort conditions (24°C/50% RH summer, 20-22°C/30-50% RH winter) that guide psychrometric design targets.
ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality. Specifies minimum ventilation rates (10 L/s per person for offices) that affect psychrometric calculations through ventilation heat gain.
Air Properties
Dry Bulb Temperature (DB)
The dry bulb temp is the thermal reading of airflow measured with a standard thermometer. It's the most common heat measurement in HVAC.
Typical Design Values:
- Summer Design: 35-40°C (outdoor), 24-26°C (indoor)
- Winter Design: -5 to 5°C (outdoor), 20-22°C (indoor)
Wet Bulb Temperature (WB)
The wet bulb thermal value is measured using a thermometer with a wet wick around the bulb. As atmosphere passes over the wick, water evaporates, AC the bulb.
Key Points:
- Wet bulb is always dry bulb degree
- When RH = 100%, wet bulb = dry bulb
- Lower wet bulb indicates drier ventilation air
- Used to determine humidity ratio and enthalpy
Relative Humidity (RH)
Relative humidity is the ratio of actual water vapor power to saturation vapor force at the same heat level.
Formula:
Where:
- RH = Relative humidity (%)
- = Actual vapor stress (kPa)
- = Saturation vapor load at dry bulb temp (kPa)
Typical Values:
- Comfort Zone: 40-60%
- Summer Indoor: 50-60%
- Winter Indoor: 30-50%
Humidity Ratio (W)
The humidity ratio is the mass of water vapor per unit mass of dry fresh air.
Formula:
Where:
- W = Humidity ratio (kg/kg dry air supply)
- = Vapor pressure value (kPa)
- P = Total system pressure (kPa)
- 0.622 = Ratio of molecular weights (water/dry airflow)
Dew Point Temperature
The dew point is the thermal reading at which water vapor begins to condense when atmosphere is cooled at constant power and humidity ratio.
Key Points:
- Dew point dry bulb heat
- When dew point = dry bulb, RH = 100%
- Condensation occurs when surface thermal value < dew point
- Critical for preventing moisture problems
Enthalpy (h)
Enthalpy represents the total heat content of moist ventilation air, including sensible and latent heat.
Formula:
Where:
- h = Enthalpy (kJ/kg dry fresh air)
- = Specific heat of dry air supply (1.006 kJ/kg·K)
- T = Dry bulb degree (°C)
- W = Humidity ratio (kg/kg dry airflow)
- = Latent heat of vaporization at 0°C (2501 kJ/kg)
- = Specific heat of water vapor (1.86 kJ/kg·K)
Typical Values:
- Outdoor Summer: 85-100 kJ/kg
- Indoor Comfort: 45-60 kJ/kg
- Outdoor Winter: 5-20 kJ/kg
Specific Volume (v)
Specific volume is the volume occupied by 1 kg of dry atmosphere plus associated water vapor.
Formula:
Where:
-
v = Specific volume (m3/kg dry ventilation air)- = Gas constant for dry fresh air (0.287 kJ/kg·K)
-
T = Absolute heat level (K)
-
P = Total force (kPa)
-
= Vapor stress (kPa)
Psychrometric Chart
Chart Layout
The psychrometric chart is a graphical representation of psychrometric properties. Key features:
- Dry Bulb Temp: Horizontal axis (bottom)
- Humidity Ratio: Vertical axis (right)
- Relative Humidity: Curved lines from bottom-left to top-right
- Wet Bulb Thermal reading: Diagonal lines
- Enthalpy: Diagonal lines (often parallel to wet bulb)
- Specific Volume: Diagonal lines
- Dew Point: Horizontal line from humidity ratio to saturation curve
Using the Chart
To find properties from DB and WB:
- Locate dry bulb heat on horizontal axis
- Follow vertical line up to wet bulb thermal value diagonal
- Read humidity ratio from vertical axis
- Read relative humidity from curved lines
- Read enthalpy from diagonal lines
- Follow horizontal line to saturation curve for dew point
To find properties from DB and RH:
- Locate dry bulb degree on horizontal axis
- Follow vertical line up to relative humidity curve
- Read humidity ratio from vertical axis
- Follow diagonal line to find wet bulb heat level
- Read enthalpy from diagonal lines
Core Formulas
Saturation Vapor Pressure
ASHRAE Equation 5 (Chapter 1, Fundamentals 2021):
Where:
- = Saturation vapor load (Pa)
- T = Absolute temp (K)
- = Constants from ASHRAE
For temperatures 0-100°C:
- = -5.8002206E+03
- = 1.3914993E+00
- = -4.8640239E-02
- = 4.1764768E-05
- = -1.4452093E-08
- = 6.5459673E+00
Vapor Pressure from Relative Humidity
Humidity Ratio from Vapor Pressure
Wet Bulb Temperature (Iterative)
Wet bulb thermal reading is found by solving:
This requires iteration as depends on .
Dew Point Temperature
Dew point is found by solving for the heat at which :
Psychrometric Processes
| Process | Chart Direction | DB Temp | Humidity (W) |
|---|---|---|---|
Sensible Cooling Cooling coil (dry) | Horizontal Left → | Decreases | Constant |
Cooling + Dehumid. Cooling coil (wet) | Down-Left to Saturation ↙ | Decreases | Decreases |
Heating Heating coil | Horizontal Right → | Increases | Constant |
Humidification Steam injection | Vertical Up ↑ | ~Constant | Increases |
Evap. Cooling Evaporative cooler | Up-Left (const. WB) ↖ | Decreases | Increases |
Key Insight: Sensible processes move horizontally (constant W), latent processes move vertically (constant DB), and combined processes move diagonally. The cooling coil ADP determines the end state.
1. Sensible Cooling
Process: Refrigeration without dehumidification (constant humidity ratio)
Conditions:
- Surface thermal value > dew point
- No condensation occurs
- Humidity ratio remains constant
Energy Calculation:
Where:
- = Sensible heat transfer (kW)
- = Mass flow rate of dry air supply (kg/s)
- = Initial and final temperatures (°C)
Application: Chilling coils in dry climates
2. Sensible Heating
Process: Heating without humidification (constant humidity ratio)
Conditions:
- Heat added without moisture addition
- Humidity ratio remains constant
- Relative humidity decreases
Energy Calculation:
Application: Space heaters, electric heaters
3. Humidification
Process: Adding moisture to airflow (constant dry bulb or adiabatic)
Adiabatic Humidification:
- Constant enthalpy process
- Water evaporates using sensible heat
- Dry bulb degree decreases
- Humidity ratio increases
Isothermal Humidification:
- Constant dry bulb heat level
- Heat added to maintain temp
- Humidity ratio increases
Energy Computation:
Application: Humidifiers, spray systems
4. Dehumidification
Process: Removing moisture from atmosphere
Conditions:
- Temperature control surface thermal reading < dew point
- Condensation occurs
- Both sensible and latent heat removed
Energy Analysis:
Application: Air conditioning coils, desiccant systems
5. Air Mixing
Process: Mixing two ventilation air streams
Mass Balance:
Energy Balance:
Humidity Ratio:
Dry Bulb Heat:
Application: Return fresh air mixing, economizer systems
Mixing Formula
Tmix = (m₁·T₁ + m₂·T₂) / (m₁ + m₂)
Tmix = (0.30 × 35 + 0.70 × 24) / 1.0 = 27.3°C
Key Insight: On a psychrometric chart, the mixed state lies on a straight line between the two inlet states, positioned closer to the larger airflow stream.
Worked Examples
Example 1: Find Air Properties from DB and WB
Given:
- Dry bulb thermal value: 30°C
- Wet bulb degree: 22°C
- Atmospheric pressure value: 101.325 kPa
Find: Relative humidity, humidity ratio, enthalpy, dew point
Solution:
Step 1: Determine saturation vapor arrangement pressure at wet bulb (22°C = 295.15 K)
Step 2: Compute humidity ratio at wet bulb
Step 3: Find humidity ratio at dry bulb
Step 4: Evaluate saturation vapor power at dry bulb (30°C)
Step 5: Measure actual vapor force
Step 6: Assess relative humidity
Step 7: Determine enthalpy
Answer:
- Humidity ratio: 0.0135 kg/kg
- Relative humidity: 50.6%
- Enthalpy: 64.7 kJ/kg
- Dew point: ~18.5°C
Example 2: Cooling and Dehumidification
Given:
- Inlet air supply: 30°C DB, 22°C WB
- Outlet airflow: 15°C DB, 14°C WB
- Atmosphere flow rate: 2.5 m3/s- Atmospheric stress: 101.325 kPa
Find: Total AC capacity, sensible refrigeration, latent chilling
Solution:
Step 1: Find inlet ventilation air properties (from Example 1)
- Enthalpy = 64.7 kJ/kg
- Humidity ratio = 0.0135 kg/kg
- Specific volume = 0.887 m³/kg
Step 2: Find outlet fresh air properties
- Enthalpy = 39.5 kJ/kg
- Humidity ratio = 0.0098 kg/kg
- Specific volume = 0.827 m³/kg
Step 3: Compute mass current rate
Step 4: Find total temperature control capacity
Step 5: Evaluate sensible air conditioning
Step 6: Measure latent AC
Step 7: Verify
Answer:
- Total refrigeration: 71.0 kW
- Sensible chilling: 42.6 kW (60%)
- Latent temperature control: 26.2 kW (40%)
Example 3: Air Mixing
Given:
- Stream 1: 30°C DB, 50% RH, 1.5 kg/s
- Stream 2: 15°C DB, 90% RH, 1.0 kg/s
- Atmospheric load: 101.325 kPa
Find: Mixed air supply properties
Solution:
Step 1: Find properties of Stream 1
- = 63.8 kJ/kg
- = 0.0133 kg/kg
Step 2: Find properties of Stream 2
- = 38.9 kJ/kg
- = 0.0096 kg/kg
Step 3: Assess total mass movement
Step 4: Determine mixed airflow enthalpy
Step 5: Compute mixed atmosphere humidity ratio
Step 6: Find mixed ventilation air heat level
Answer:
- Mixed fresh air temp: 24°C
- Mixed air supply humidity ratio: 0.0119 kg/kg
- Mixed airflow enthalpy: 54.4 kJ/kg
Design Applications
Sensible (75%)
Dry bulb temperature change
Latent (25%)
Humidity ratio change
Key Insight: Higher SHR (0.9+) indicates dry climates; lower SHR (0.6) indicates humid climates requiring more dehumidification.
1. Cooling Load Calculation
Psychrometric analysis is essential for calculating air conditioning loads:
Sensible Load:
Latent Load:
Where:
- V = Atmosphere circulation rate (m³/s)
- = Outdoor and return ventilation air temperatures (°C)
- = Outdoor and return fresh air humidity ratios (kg/kg)
2. Air Conditioning System Sizing
Total AC Capacity:
Where:
- = Outdoor air supply enthalpy (kJ/kg)
- = Supply airflow enthalpy (kJ/kg)
3. Ventilation Requirements
Minimum Outdoor Atmosphere:
Typical Values (per person):
- Office: 10 L/s
- Classroom: 8 L/s
- Auditorium: 8 L/s
4. Energy Recovery Systems
Sensible Recovery Efficiency:
Total Recovery Efficiency:
Common Mistakes
1. Ignoring Latent Load
Mistake: Only calculating sensible refrigeration load
Impact: Undersized chilling equipment, high humidity
Solution: Always evaluate both sensible and latent loads
2. Wrong Wet Bulb Temperature
Mistake: Using outdoor dry bulb instead of wet bulb for temperature control load
Impact: Incorrect air conditioning capacity determination
Solution: Use design wet bulb thermal reading from climate data
3. Incorrect Air Mixing
Mistake: Averaging temperatures without considering mass flow rate rates
Impact: Wrong mixed fresh air properties
Solution: Use mass-weighted averages for all properties
4. Neglecting Dew Point
Mistake: Not checking for condensation on surfaces
Impact: Moisture damage, mold growth
Solution: Always verify surface heat > dew point
5. Wrong Enthalpy Reference
Mistake: Using different enthalpy references in calculations
Impact: Incorrect energy calculations
Solution: Use consistent reference state (0°C, dry air supply)
What Are the Best Practices for?
Professional Tip: Document all design assumptions, input parameters, and safety factors. This ensures code compliance, simplifies future modifications, and provides clear audit trails for inspections.
1. Use ASHRAE Formulas
Always use ASHRAE Fundamentals formulas for accurate calculations. These are based on extensive experimental data.
2. Verify with Psychrometric Chart
Use the psychrometric chart to verify calculations and visualize processes.
3. Consider Altitude
Atmospheric pressure value decreases with altitude, affecting all psychrometric properties. Adjust calculations for high-altitude locations.
4. Account for Process Efficiency
Real processes are not ideal. Account for:
- Coil bypass factor (0.05-0.15)
- Fan heat gain (2-5%)
- Duct heat gain/loss
5. Use Design Conditions
Always use design conditions from local climate data:
- Summer design: 1% or 2.5% dry bulb and mean coincident wet bulb
- Winter design: 99.6% or 97.5% dry bulb
6. Validate Results
Check that calculated values are within reasonable ranges:
- Humidity ratio: 0.002-0.025 kg/kg (typical)
- Enthalpy: 5-100 kJ/kg (typical)
- Relative humidity: 30-70% (comfort zone)
Real-World Case Studies
Case Study 1: Hospital Operating Room Humidity Control
Case Study 2: Data Center Economizer Failure
Case Study 3: Indoor Pool Natatorium Disaster
Quick Reference Card
Psychrometric Process Summary
| Process | Chart Movement | W Changes? | h Changes? | Application |
|---|---|---|---|---|
| Sensible Cooling | Horizontal left | No | Decreases | Dry climate AC |
| Sensible Heating | Horizontal right | No | Increases | Winter heating |
| Cooling + Dehumid | Diagonal down-left | Decreases | Decreases | Typical summer AC |
| Adiabatic Humid | Along constant h | Increases | Constant | Evaporative coolers |
| Isothermal Humid | Vertical up | Increases | Increases | Steam humidifiers |
| Air Mixing | Straight line | Weighted avg | Weighted avg | Economizer systems |
Critical Dew Points to Remember
| Application | Target RH | Typical DP | Coldest Surface Limit |
|---|---|---|---|
| Office | 50% at 24°C | 13°C | Windows (>14°C) |
| Hospital OR | 50% at 20°C | 9°C | Surgical instruments |
| Data Center | 45% at 24°C | 11°C | CPU heat sinks (>12°C) |
| Museum | 50% at 21°C | 10°C | Exterior walls (>11°C) |
| Natatorium | 50% at 29°C | 17°C | Roof structure (>18°C) |
Design Checklist
Before Finalizing Any Psychrometric Design:
- Plotted all air states on chart (outdoor, return, supply, mixed)?
- Calculated both sensible AND latent loads separately?
- Verified supply air humidity ratio is BELOW room requirement?
- Checked dew point against ALL cold surfaces in space?
- Considered economizer operation with dew point limits?
- Accounted for altitude effects on saturation pressure?
- Verified equipment SHR matches required SHR?
- Documented all assumptions for commissioning?
Our cooling load calculations reflect real-world conditions and safety factors.
Our cooling load calculations reflect real-world conditions and safety factors.
Our engineering team developed this methodology based on internal testing and real-world validation.
Conclusion
Psychrometric calculations are fundamental to HVAC system design. By understanding the relationships between temperature, humidity, and energy, engineers can design efficient heating and cooling systems, optimize energy consumption, ensure occupant comfort, and prevent moisture problems.
Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.
Key Takeaways
- Calculate enthalpy using —enthalpy represents total heat content including sensible and latent heat
- Determine humidity ratio from vapor pressure using —humidity ratio is mass of water vapor per unit mass of dry air
- Use psychrometric chart to visualize HVAC processes—chart shows relationships between all air properties enabling process design
- Calculate total cooling load from enthalpy difference— where enthalpy difference includes both sensible and latent components
- Maintain comfort conditions per ASHRAE 55—24°C/50% RH summer, 20-22°C/30-50% RH winter for optimal occupant comfort
- Prevent condensation by keeping surface temperatures above dew point—dew point is temperature where condensation begins, critical for moisture control
Further Learning
- Cooling Load Guide - Cooling load calculations
- Duct Sizing Guide - Air distribution design
- Heat Loss Guide - Building heat loss calculations
- Psychrometric Calculator - Interactive calculator for psychrometric calculations
References & Standards
Primary Standards
ASHRAE Fundamentals Handbook Chapter 1: Psychrometrics. Provides comprehensive psychrometric formulas, property calculations, and chart reading methods. Includes ASHRAE Equation 5 for saturation vapor pressure and all psychrometric property relationships.
ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy. Specifies comfort conditions (24°C/50% RH summer, 20-22°C/30-50% RH winter) that guide psychrometric design targets.
ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality. Specifies minimum ventilation rates (10 L/s per person for offices) that affect psychrometric calculations through ventilation heat gain.
Supporting Standards & Guidelines
ASHRAE Handbook - HVAC Systems and Equipment Chapter 4: Air Handling and Distribution. Provides guidance on air handling system design and psychrometric processes.
Further Reading
- ASHRAE Technical Resources - American Society of Heating, Refrigerating and Air-Conditioning Engineers resources
- McQuiston, Parker, Spitler: Heating, Ventilating, and Air Conditioning Analysis and Design - Comprehensive HVAC textbook
- Stoecker, Jones: Refrigeration and Air Conditioning - Reference for refrigeration and air conditioning principles
Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.
Disclaimer: This guide provides general technical information based on international HVAC standards. Always verify calculations with applicable local codes and consult licensed professionals for actual installations. HVAC system design should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.