Psychrometric Calculator
Calculate air properties, psychrometric processes, and air mixing using ASHRAE standards
Psychrometrics is the science of moist air properties and their interactions, fundamental to all HVAC system design, analysis, and operation. Atmospheric air is a mixture of dry air and water vapor, with the water vapor content affecting thermal comfort, equipment performance, and energy consumption. The psychrometric chart graphically represents the thermodynamic properties of moist air, enabling engineers to visualize air conditioning processes such as heating, cooling, humidification, and dehumidification. Understanding psychrometric principles is essential for proper equipment selection, process control, and energy optimization.
Temperature Measurements: Dry-bulb temperature is measured by a standard thermometer, representing the sensible heat content of air. Wet-bulb temperature indicates the lowest temperature achievable through evaporative cooling, measured using a wetted wick exposed to moving air. The wet-bulb depression (difference between dry-bulb and wet-bulb) indicates the air's moisture-absorbing capacity. Dew point temperature is where water vapor begins to condense when air is cooled at constant pressure, directly indicating absolute moisture content. These temperature values define unique state points on the psychrometric chart.
Humidity Properties: Relative humidity expresses the ratio of actual water vapor pressure to saturation vapor pressure at the same temperature, typically 30-60% for human thermal comfort per ASHRAE Standard 55. Humidity ratio is the mass of water vapor per unit mass of dry air, remaining constant during sensible heating or cooling processes. Enthalpy represents total heat content per unit mass of dry air, including both sensible heat (temperature-related) and latent heat (moisture-related). These properties are critical for cooling load calculations and equipment sizing.
Psychrometric Processes: Sensible heating increases dry-bulb temperature while maintaining constant humidity ratio, moving horizontally right on the psychrometric chart. Sensible cooling reduces temperature at constant humidity ratio until reaching the dew point, where further cooling causes dehumidification. Humidification adds moisture, achievable through steam injection or evaporative cooling along constant wet-bulb lines. Dehumidification involves cooling air below its dew point temperature, condensing water vapor on cooling coil surfaces. The sensible heat ratio (SHR) defines the slope of the cooling process line, critical for matching equipment capacity to building load characteristics.
Air Mixing and Economizer Control: Mixing processes combine two air streams, such as outdoor ventilation air with recirculated return air in air handling units. The mixed air condition lies on a straight line between the two inlet states, with position determined by mass flow ratio. Psychrometric analysis of mixing is essential for economizer control strategies, where varying the outdoor air fraction optimizes free cooling. Enthalpy comparison determines whether outdoor air conditions justify increased ventilation for cooling rather than mechanical refrigeration, enabling significant energy savings in temperate climates.
Advanced Applications: Industrial processes demand precise psychrometric control for product quality. Data centers maintain 40-50% RH to minimize corrosion while avoiding static discharge. Clean rooms for semiconductor fabrication specify temperature ±0.1°C and humidity ±1% RH. Desiccant dehumidification systems can achieve dew points below 0°C for specialized applications. Modern building automation systems continuously monitor psychrometric conditions, optimizing HVAC operation through demand-controlled ventilation and predictive controls that leverage weather forecasts and building thermal mass for energy efficiency.
Standards Reference: ASHRAE Standard 55 defines thermal comfort zones (30-60% RH, 20-26°C). ASHRAE Standard 62.1 specifies ventilation rates and indoor air quality requirements. ASHRAE Fundamentals Handbook provides psychrometric charts for various elevations and detailed calculation procedures for all air properties.
Related Calculators
You might also need these calculators
Referenced Standards & Guidelines
Calculations comply with the following authoritative sources
ASHRAE 55 - Thermal Environmental Conditions for Human Occupancy
ASHRAE 55-2020 (2020)
Specifies thermal comfort conditions for building occupants, used in HVAC system design.
ASHRAE 62.1 - Ventilation for Acceptable Indoor Air Quality
ASHRAE 62.1-2022 (2022)
Standard for minimum ventilation rates and indoor air quality in commercial and institutional buildings.
All formulas and calculations are based on peer-reviewed standards and official engineering guidelines