Fresh Air Flow Calculation Guide
Office with 20 people, 100m², Rp=2.5, Ra=0.3 gives Q = 2.5×20 + 0.3×100 = 80 L/s (170 CFM) minimum outdoor air.
Introduction
Calculating required fresh air flow is essential for maintaining acceptable indoor air quality, ensuring occupant health and comfort, and complying with building codes. Fresh air flow (outdoor air ventilation) dilutes indoor contaminants including CO₂, VOCs, odors, and particulates to maintain acceptable indoor air quality. ASHRAE 62.1 requires minimum ventilation rates based on both occupancy and floor area using the combined method: , where is the ventilation rate per person, is the number of occupants, is the ventilation rate per area, and is the floor area.
Why This Calculation Matters
Accurate fresh air flow calculation is crucial for:
- Occupant Health: Maintaining CO₂ levels below 1000 ppm to prevent sick building syndrome and ensure cognitive performance.
- Indoor Air Quality: Diluting indoor contaminants (VOCs, odors, particulates) to acceptable levels per ASHRAE 62.1.
- Energy Efficiency: Balancing ventilation requirements with HVAC energy consumption to avoid oversized systems.
- Code Compliance: Meeting building code requirements that typically adopt ASHRAE 62.1 by reference.
The Fundamental Challenge
The primary challenge in fresh air calculation lies in correctly applying the ASHRAE 62.1 combined ventilation method, which requires both per-person () and per-area () components. Using only one component—a common mistake—can undersize outdoor air by 30-50%. Additionally, engineers must verify that calculated ventilation meets minimum air changes per hour (ACH) requirements for the space type, apply appropriate diversity factors for variable occupancy, and consider energy recovery for systems with high outdoor air requirements. Balancing air quality with energy consumption requires careful analysis, particularly in extreme climates where conditioning outdoor air is expensive.
What You'll Learn
In this comprehensive guide, you will learn:
- The ASHRAE 62.1 combined ventilation method () and lookup tables for different space types.
- How to calculate and verify air changes per hour (ACH) requirements.
- Demand control ventilation (DCV) strategies for variable occupancy spaces.
- Energy recovery requirements and payback analysis.
- Step-by-step examples to confidently calculate fresh air requirements per ASHRAE 62.1-2019.
Interactive Fresh Air Flow Visualization
Explore the ASHRAE 62.1 ventilation rate procedure with this interactive tool. Adjust space type, occupancy, and floor area to see real-time calculations of required fresh air flow, CO₂ levels, and air changes per hour:
Quick Answer: How to Calculate Fresh Air Flow
Fresh air requirements are calculated using the ASHRAE 62.1 combined method, which accounts for both occupancy and floor area. The formula is:
Where both the per-person component () and the per-area component () must be added together.
Core Formula
Where:
- = Required fresh air flow (L/s)
- = Ventilation rate per person (L/s per person)
- = Number of occupants
- = Ventilation rate per area (L/s per m²)
- = Floor area (m²)
Additional Formulas
| Formula | Purpose |
|---|---|
| Air Changes per Hour | |
| Energy Recovery |
Reference Table
| Parameter | Typical Range | Standard |
|---|---|---|
| Office () | 5 L/s per person | ASHRAE 62.1 |
| Office () | 0.6 L/s per m² | ASHRAE 62.1 |
| Restaurant () | 7.5-10 L/s per person | ASHRAE 62.1 |
| Minimum ACH (Office) | 4-6 ACH | ASHRAE 62.1 |
| Minimum ACH (Kitchen) | 10-15 ACH | ASHRAE 62.1 |
| DCV Threshold | ≥25 people per 1000 ft² | ASHRAE 62.1 |
Key Standards
ASHRAE 62.1: Ventilation and acceptable indoor air quality in commercial buildings. Specifies minimum ventilation rates using the Ventilation Rate Procedure (VRP) with per-person and per-area components for over 70 space types. Provides lookup tables with and values for different applications.
ASHRAE 90.1: Energy Standard for Buildings. Sets energy efficiency requirements, mandating ERV/HRV systems for high outdoor air applications (≥70% OA or ≥5000 CFM in climate zones 3-8).
Worked Example
Design Standards
ASHRAE 62.1-2019 Requirements:
- Combined method () is required for all commercial buildings
- Typical offices: 5 L/s/person + 0.6 L/s/m² with 4-6 ACH minimum
- Restaurants: 7.5 L/s/person + 0.9 L/s/m² with 8-12 ACH
- Educational: 3.5 L/s/person + 0.5 L/s/m² with 4-6 ACH
Always use the higher of calculated current or minimum ACH requirement.
Proper fresh air exchange is essential for maintaining good indoor air supply quality. This guide explains how to determine the required fresh airflow movement for different space types based on ASHRAE 62.1 standards.
Overview
Fresh air supply circulation requirements are determined by two main approaches:
- Airflow circulation Rate Procedure (VRP) - Based on occupancy and space type
- Indoor Atmosphere Quality Procedure (IAQP) - Based on contaminant control
This guide focuses on the Ventilation air exchange Rate Procedure, which is the most commonly used method.
ASHRAE 62.1 Ventilation Rates
Office Spaces
| Space Type | Airflow Rate (L/s per person) | Fresh air movement Rate (L/s per m²) |
|---|---|---|
| Office | 5 | 0.6 |
| Conference Room | 5 | 0.6 |
| Reception | 5 | 0.6 |
Educational Facilities
| Space Type | Air supply supply Rate (L/s per person) | Airflow circulation Rate (L/s per m²) |
|---|---|---|
| Classroom | 5 | 0.6 |
| Auditorium | 5 | 0.6 |
| Library | 5 | 0.6 |
Assembly Spaces
| Space Type | Atmosphere exchange Rate (L/s per person) | Airflow Rate (L/s per m²) |
|---|---|---|
| Restaurant | 7.5 | 0.9 |
| Bar | 10 | 1.2 |
| Theater | 5 | 0.6 |
Residential
| Space Type | Ventilation air movement Rate (L/s per person) | Fresh air supply Rate (L/s per m²) |
|---|---|---|
| Living Room | 2.5 | 0.3 |
| Bedroom | 2.5 | 0.3 |
| Kitchen | 7.5 | 0.9 |
| Bathroom | 20 | 2.4 |
How Do You Calculate?
Method 1: Per Person
Where:
- = air supply circulation rate per person (L/s)
- = number of occupants
- = airflow exchange rate per person (L/s per person)
Method 2: Per Area
Where:
- = airstream rate per area (L/s)
- = floor area (m²)
- = atmosphere movement rate per area (L/s per m²)
Method 3: Combined (ASHRAE 62.1)
Important: ASHRAE 62.1 requires the sum of both components, not the maximum:
This is different from older methods that used the maximum. Both the per-person component () and the per-area component () must be added together.
Air Changes per Hour
Ventilation air changes per hour (ACH) is another useful metric:
Where:
- ACH = fresh air changes per hour
- Q = air supply supply flow rate rate (m³/s)
- V = room volume (m³)
Typical ACH Values
| Space Type | Minimum ACH | Recommended ACH |
|---|---|---|
| Office | 4 - 6 | 6 - 10 |
| Classroom | 4 - 6 | 6 - 10 |
| Restaurant | 8 - 12 | 12 - 15 |
| Bathroom | 6 - 10 | 10 - 15 |
| Kitchen | 10 - 15 | 15 - 20 |
Worked Example
Evaluate the required fresh airflow discharge for an office with the following parameters:
- Floor area: 100 m²
- Ceiling height: 2.7 m
- Occupancy: 10 people
- Space type: Office
Step 1: Calculate Volume
Step 2: Calculate Ventilation Rate per Person
Step 3: Calculate Ventilation Rate per Area
Step 4: Select Maximum
Step 5: Calculate ACH
This is below the recommended 4-6 ACH for offices, so we should increase atmosphere circulation to at least 4 ACH.
Step 6: Adjust for Minimum ACH
What Are the Design Considerations for?
Occupancy Diversity
Actual occupancy is often less than design occupancy. Consider diversity factors:
| Space Type | Diversity Factor |
|---|---|
| Office | 0.7 - 0.8 |
| Classroom | 0.9 - 1.0 |
| Restaurant | 0.8 - 0.9 |
| Retail | 0.5 - 0.7 |
Multiple Spaces
For systems serving multiple spaces:
Where:
- = ventilation air exchange rate for space (L/s)
- = diversity factor for space (dimensionless)
- = number of spaces served by the system
Demand Control Ventilation (DCV)
DCV systems adjust airflow based on actual occupancy:
- CO₂ sensors monitor occupancy
- Fresh air movement rate adjusts automatically
- Energy savings of 20-40%
Energy Implications
Energy Cost
Where:
- = energy consumption (kWh/year)
- = air supply supply rate (m³/s)
- = airflow density (kg/m³)
- = specific heat (kJ/kg·K)
- = temperature difference (°C)
- = operating hours (hours/year)
Energy Recovery
Energy recovery ventilators (ERVs) and heat recovery ventilators (HRVs) can reduce energy consumption by 60-80%.
Standards and References
- ASHRAE 62.1-2019: Atmosphere circulation for Acceptable Indoor Ventilation air Quality
- EN 16798-1: Energy performance of buildings - Fresh air exchange
- ISO 16814: Building environment design - Indoor air supply quality
Our airflow calculations follow industry standards for optimal system performance.
Our airflow calculations follow industry standards for optimal system performance.
Conclusion
Calculating required fresh air flow is essential for maintaining acceptable indoor air quality, ensuring occupant health and comfort, and complying with building codes. ASHRAE 62.1 requires minimum ventilation rates based on both occupancy and floor area using the combined method: , where is the ventilation rate per person (L/s per person), is the number of occupants, is the ventilation rate per area (L/s per m²), and is the floor area (m²). Both components are required—never use only per-person or only per-area rates.
Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.
Verify minimum air changes per hour (ACH) requirements—offices require 4-6 ACH, kitchens 10-15 ACH. The ACH is calculated as , where is in m³/s and is room volume in m³. Demand control ventilation (DCV) uses CO₂ sensors to modulate outdoor air intake based on actual occupancy, saving 20-40% HVAC energy while maintaining code compliance.
Outdoor air is the largest HVAC energy load in most climates, consuming 30-50% of total heating/cooling energy. Energy consumption is calculated as , where is airflow rate (m³/s), is air density (1.2 kg/m³), is specific heat (1.005 kJ/kg·K), is temperature difference (°C), and is operating hours per year. Energy recovery ventilators (ERVs) recover 60-80% of this energy through heat/moisture exchange, with typical payback periods of 2-5 years. Following ASHRAE 62.1 guidelines ensures proper ventilation while optimizing energy consumption.
Key Takeaways
-
Calculate fresh air flow using combined method: —both per-person () and per-area () components are required; never use only one component. This is the ASHRAE 62.1 standard method.
-
Use correct ventilation rates from ASHRAE 62.1: Offices require L/s per person and L/s per m²; rates vary by space type (70+ space types in standard). Always reference Table 6.2.2.1 for current values.
-
Verify minimum ACH requirements: Offices require 4-6 ACH, kitchens 10-15 ACH; calculate where is in m³/s and is room volume in m³. Use the higher of calculated flow or minimum ACH requirement.
-
Apply occupancy diversity factors: Offices 0.7-0.8, retail 0.5-0.7; accounts for actual vs design occupancy. System flow: where is diversity factor for space .
-
Consider demand control ventilation: DCV saves 20-40% energy for variable occupancy spaces; requires CO₂ sensors or occupancy counters. Must maintain minimum component at all times while modulating component.
-
Account for energy recovery: ERVs/HRVs recover 60-80% of ventilation energy; required by ASHRAE 90.1 for high outdoor air applications (≥70% OA or ≥5000 CFM in climate zones 3-8). Energy cost: .
-
Use current ASHRAE 62.1 edition: Rates increased 25-40% from 1989 version; always use latest edition (currently 62.1-2019) for compliance. Most building codes adopt ASHRAE 62.1 by reference.
Further Learning
- Duct Sizing Guide - Sizing ductwork for ventilation systems
- Duct Pressure Loss Guide - Calculating friction loss in ducts
- HRV Sizing Guide - Sizing heat recovery ventilators
- Fresh Air Flow Calculator - Interactive calculator for ventilation requirements
References & Standards
Primary Standards
ASHRAE 62.1 Ventilation and acceptable indoor air quality in commercial buildings. Specifies minimum ventilation rates using the Ventilation Rate Procedure (VRP) with per-person and per-area components for over 70 space types. Provides lookup tables with and values for different applications.
ASHRAE 90.1 Energy Standard for Buildings. Sets energy efficiency requirements, mandating ERV/HRV systems for high outdoor air applications (≥70% OA or ≥5000 CFM in climate zones 3-8).
Supporting Standards & Guidelines
EN 13779 Ventilation for non-residential buildings. European performance requirements for ventilation and air-conditioning systems.
International Mechanical Code (IMC) Comprehensive mechanical systems code including ventilation requirements.
Further Reading
- ASHRAE Ventilation Guide - Best practices for ventilation system design
- SMACNA HVAC Systems Duct Design Manual - Industry-standard duct design manual
Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.
Disclaimer: This guide provides general technical information based on international HVAC standards. Always verify calculations with applicable local building codes (ASHRAE 62.1, EN 13779, IMC, etc.) and consult licensed mechanical engineers or HVAC specialists for actual installations. Ventilation system design should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.