Guides
ElectricalIntermediate20 min
ReviewedStandards-Based

How to Design a Panel Schedule: Complete NEC 2023 Guide

Learn how to create NEC-compliant electrical panel schedules. Understand load calculations, breaker sizing, wire selection, phase balancing, and demand factors with practical examples.

James Rodriguez, PE
James Rodriguez is a licensed Professional Engineer with 18 years of experience in electrical design for residential and commercial projects. He is a certified NFPA and IEEE member who has designed electrical systems for over 500 projects. James specializes in NEC code compliance and teaches continuing education courses for electricians.
Reviewed by Licensed Electrical Engineers and Master Electricians
Published: December 14, 2025
Quick AnswerHow do you design a panel schedule?
Design a panel schedule in 5 steps: (1) List all circuits with their VA loads, (2) Apply NEC demand factors to reduce calculated load, (3) Size branch circuit breakers at 125% of continuous loads, (4) Select wire sizes from NEC 310.16 based on ampacity, (5) Balance loads across phases within 10%. A typical 2,000 sq ft home needs a 200A panel with 30-42 circuits.

Key Takeaways

  • 1**NEC 220.12 lighting loads**: 3 VA/sq ft for dwellings, 3.5 VA/sq ft for offices—a 2,000 sq ft home has 6,000 VA base lighting load before demand factors
  • 2**Demand factors reduce panel size**: First 3,000 VA at 100%, remainder at 35% for dwellings (NEC 220.42)—a 10,000 VA connected load becomes 5,450 VA demand load
  • 3**Continuous loads need 125%**: Any load running 3+ hours (HVAC, EV chargers, commercial lighting) requires breaker sized at 125% of load current per NEC 210.20(A)
  • 4**Phase balance within 10%**: In 3-phase systems, keep phase loads balanced to prevent neutral overloading and transformer issues—spread large loads across phases
  • 5**Standard breaker sizes (NEC 240.6)**: 15, 20, 25, 30, 35, 40, 50, 60, 70, 100A—always round UP to the next standard size
  • 6**Wire sizing from NEC 310.16**: 14 AWG for 15A, 12 AWG for 20A, 10 AWG for 30A, 8 AWG for 40A, 6 AWG for 55A at 60C copper

What is a Panel Schedule?

A panel schedule is a detailed document that maps every circuit in an electrical panel. It's required by NEC 408.4 for proper panel identification. Panels must comply with UL 67 for panelboard standards and IEEE C2 (National Electrical Safety Code) for safe installations. The schedule serves as a roadmap for:

  • Electrical contractors during installation
  • Inspectors during code compliance review
  • Maintenance personnel for troubleshooting
  • Homeowners for understanding their electrical system
ColumnDescriptionExample
Circuit #Position in panel1, 2, 3...
DescriptionLoad name"Kitchen Receptacles"
Breaker (A)Overcurrent protection20A
PolesSingle, double, or triple1P, 2P, 3P
VoltageOperating voltage120V, 240V
Wire SizeConductor gauge12 AWG
VA/WattsLoad magnitude1,800 VA
Typical Residential Load Distribution
How electrical loads are typically distributed in a home panel

20.0 kW

Total connected load

HVAC
35%(7,000W)
Water Heater
20%(4,000W)
Kitchen/Cooking
18%(3,600W)
Lighting
12%(2,400W)
Laundry
8%(1,600W)
Receptacles
7%(1,400W)

Largest load

HVAC (35%)

Service size for 20kW

200A typical

After demand factors

~12-15 kW

Step 1: Calculate General Lighting Load

NEC 220.12 specifies minimum lighting loads by occupancy type:

Occupancy TypeVA per sq ftExample (2,000 sq ft)
Dwelling unit36,000 VA
Office3.57,000 VA
Bank3.57,000 VA
School36,000 VA
Store36,000 VA
Warehouse0.51,000 VA
Hospital24,000 VA
Restaurant24,000 VA
LightingLoad(VA)=FloorArea(sqft)×VApersqftLighting Load (VA)=Floor Area (sq ft)×VA per sq ftLightingLoad(VA)=FloorArea(sqft)×VApersqftLighting Load (VA)=Floor Area (sq ft)\times VA per sq ft\text{Lighting Load (VA)} = \text{Floor Area (sq ft)} \times \text{VA per sq ft}Lighting Load (VA)=Floor Area (sq ft)\times VA per sq ft
2,000 sq ft Home

Lighting load = 2,000 sq ft × 3 VA/sq ft = 6,000 VA

This represents the general lighting and receptacle load before adding specific appliances.

Step 2: Add Required Circuits

NEC mandates minimum circuits for dwelling units:

Required CircuitQuantityBreakerVA EachTotal VANEC Reference
Small appliance (kitchen)2 minimum20A1,5003,000210.11(C)(1)
Laundry1 minimum20A1,5001,500210.11(C)(2)
Bathroom1 minimum20A210.11(C)(3)

Step 3: Apply Demand Factors

Not all loads operate simultaneously. NEC 220.42 provides demand factors to calculate realistic panel loading:

NEC Demand Factors
Load reduction factors for residential service calculations (NEC 220)
100% = Full load
Lower % = More reduction

20 kW connected load

→ ~12-14 kW demand

HVAC + Electric Heat

Count larger only

Savings from factors

25-40% reduction

Dwelling Unit Demand Factors

Portion of LoadDemand Factor
First 3,000 VA100%
Remainder35%
DemandLoad=3000+(Total3000)×0.35Demand Load=3000+(Total3000)×0.35DemandLoad=3000+(Total3000)×0.35Demand Load=3000+(Total−3000)\times0.35\text{Demand Load} = 3000 + (\text{Total} - 3000) \times 0.35Demand Load=3000+(Total−3000)\times0.35
10,500 VA Connected Load

Connected load = 6,000 VA (lighting) + 3,000 VA (small appliance) + 1,500 VA (laundry) = 10,500 VA

Demand load = 3,000 + (10,500 - 3,000) × 0.35 = 3,000 + 2,625 = 5,625 VA

This 46% reduction shows why demand calculations matter for panel sizing.

Step 4: Add Major Appliances

After the demand-factored general load, add specific equipment:

Electric Range (NEC 220.55)

Number of RangesDemand Load
18,000 VA
211,000 VA
314,000 VA
417,000 VA
520,000 VA

For ranges over 12 kW, add 5% for each kW over 12 kW

Electric Dryer (NEC 220.54)

Number of DryersDemand Factor
1-4100%
580%
670%
765%
860%

Minimum demand: 5,000 VA per dryer

HVAC (NEC 220.60)

For noncoincident loads (heating OR cooling):

  • Use only the LARGER of heating or cooling load
  • Do NOT add both—they don't run simultaneously
  • Consider power factor for motor loads

Step 5: Size the Main Breaker

ServiceCurrent(A)=TotalDemandLoad(VA)VoltageService Current (A)=Total Demand Load (VA)VoltageServiceCurrent(A)=VoltageTotalDemandLoad(VA)Service Current (A)=Total Demand Load (VA)Voltage\text{Service Current (A)} = \frac{\text{Total Demand Load (VA)}}{\text{Voltage}}Service Current (A)=VoltageTotal Demand Load (VA)

For 240V single-phase residential service:

Total DemandCalculated CurrentMain Breaker
Under 12,000 VAUnder 50A60A or 100A
12,000-20,000 VA50-83A100A
20,000-30,000 VA83-125A125A or 150A
30,000-48,000 VA125-200A200A
Over 48,000 VAOver 200A225A or 400A
Complete Residential Load Calculation
Load CategoryVA
General lighting (2,000 sq ft × 3)6,000
Small appliance (2 × 1,500)3,000
Laundry1,500
Subtotal before demand10,500
After demand factors5,625
Range (NEC 220.55)8,000
Dryer (5,000 × 100%)5,000
Air conditioner6,000
Water heater4,500
Total Demand29,125 VA
Service current29,125 ÷ 240 = 121A
Main breaker150A or 200A

Step 6: Size Branch Circuit Breakers

Wire Ampacity by Gauge (NEC 310.16)
Current-carrying capacity for copper conductors at different temperatures
60°C insulation (TW)
75°C insulation (THWN)
Standard breaker size

Most common residential

#12 AWG (20A breaker)

200A service requires

#4/0 AWG minimum

THWN advantage

+15-20% ampacity

The 125% Rule for Continuous Loads

Per NEC 210.20(A), breakers serving continuous loads (3+ hours operation) must be sized at 125%. Breakers must meet UL 489 standards for molded-case circuit breakers. The load calculation formula:

BreakerSizeLoadCurrent×1.25Breaker SizeLoad Current×1.25BreakerSizeLoadCurrent×1.25Breaker Size\geq Load Current\times1.25\text{Breaker Size} \geq \text{Load Current} \times 1.25Breaker Size\geq Load Current\times1.25
Continuous LoadLoad Current× 1.25Breaker Size
Commercial lighting16A20A20A
EV charger (32A)32A40A40A
EV charger (40A)40A50A50A
Pool pump12A15A15A
Water heater18.75A23.4A25A or 30A

Standard Breaker Sizes (NEC 240.6)

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200A...

Always round UP to the next standard size.

Step 7: Select Wire Sizes

NEC Table 310.16 provides conductor ampacities. For detailed wire selection methods, see our cable sizing guide. Wire selection must also account for voltage drop on longer runs:

Copper Wire Ampacity at Different Temperature Ratings

Wire Size (AWG)60°C75°C90°CTypical Use
1415A20A25A15A circuits (lighting)
1220A25A30A20A circuits (receptacles)
1030A35A40A30A circuits (dryer)
840A50A55A40-50A circuits (range)
655A65A75A60A circuits (HVAC)
470A85A95A70-80A circuits
385A100A115A100A circuits
295A115A130ASub-panels
1110A130A145ALarge sub-panels
1/0125A150A170A150A service
2/0145A175A195A175A service
3/0165A200A225A200A service
4/0195A230A260A200A+ service

Step 8: Balance Phases (3-Phase Systems)

Phase Balancing Impact
How load distribution affects neutral current and system efficiency
Phase A
Phase B
Phase C

Goal: Keep imbalance

<10% of largest phase

Neutral overload risk

Above 30% imbalance

NEC 220.61

70% demand on neutral

For 3-phase panels, distribute loads to keep phases within 10% of each other:

Phase Assignment Rules

Load TypePhase Assignment
Single-pole 120VAlternates A-B-C-A-B-C
Double-pole 240VSpans two phases (A-B, B-C, or C-A)
Triple-pole 3-phaseAll three phases

Balancing Strategy

  1. List all loads by phase assignment
  2. Sum each phase separately
  3. Calculate imbalance: (Max - Min) / Average
  4. Target: Under 10% imbalance
  5. Adjust: Move single-phase loads between phases
3-Phase Panel Balancing

Before balancing:

  • Phase A: 25,000 VA
  • Phase B: 18,000 VA
  • Phase C: 20,000 VA
  • Imbalance: (25,000 - 18,000) / 21,000 = 33% (too high!)

After moving 3,500 VA from A to B:

  • Phase A: 21,500 VA
  • Phase B: 21,500 VA
  • Phase C: 20,000 VA
  • Imbalance: (21,500 - 20,000) / 21,000 = 7% (acceptable)

Safety and Code Compliance

Panel design must follow NFPA 70 (National Electrical Code) and NFPA 70E for workplace electrical safety. Key compliance points:

Safety RequirementNEC ReferenceDescription
Working clearance110.26Min 3 ft depth, 30 in width in front of panel
Panel height408.37Overcurrent devices max 6 ft 7 in above floor
Circuit directory408.4Each circuit must be legibly identified
Arc-fault protection210.12AFCI required for bedrooms, living areas
Ground-fault protection210.8GFCI required for bathrooms, kitchens, outdoors

Common Panel Configurations

Residential Panels

Home SizeTypical PanelMain BreakerCircuits
Under 1,500 sq ft100A, 20-space100A16-20
1,500-2,500 sq ft200A, 30-space200A24-30
2,500-4,000 sq ft200A, 42-space200A32-42
Over 4,000 sq ft200A+, 42+ space200A+40+

Commercial Panels

ApplicationTypical PanelVoltagePhases
Small office100-225A120/208V3-phase
Retail store225-400A120/208V3-phase
Restaurant400-600A120/208V3-phase
Industrial600-1200A277/480V3-phase

Try the Calculator

Our interactive Panel Schedule Calculator handles all NEC calculations automatically:

Panel Schedule Calculator

NEC 2023 compliant panel schedule builder with automatic load calculations

Open Calculator

Frequently Asked Questions

Frequently Asked Questions

How to Design a Panel Schedule | Enginist