Table of Contents
Key Takeaways
- 1**NEC 220.12 lighting loads**: 3 VA/sq ft for dwellings, 3.5 VA/sq ft for offices—a 2,000 sq ft home has 6,000 VA base lighting load before demand factors
- 2**Demand factors reduce panel size**: First 3,000 VA at 100%, remainder at 35% for dwellings (NEC 220.42)—a 10,000 VA connected load becomes 5,450 VA demand load
- 3**Continuous loads need 125%**: Any load running 3+ hours (HVAC, EV chargers, commercial lighting) requires breaker sized at 125% of load current per NEC 210.20(A)
- 4**Phase balance within 10%**: In 3-phase systems, keep phase loads balanced to prevent neutral overloading and transformer issues—spread large loads across phases
- 5**Standard breaker sizes (NEC 240.6)**: 15, 20, 25, 30, 35, 40, 50, 60, 70, 100A—always round UP to the next standard size
- 6**Wire sizing from NEC 310.16**: 14 AWG for 15A, 12 AWG for 20A, 10 AWG for 30A, 8 AWG for 40A, 6 AWG for 55A at 60C copper
What is a Panel Schedule?
A panel schedule is a detailed document that maps every circuit in an electrical panel. It's required by NEC 408.4 for proper panel identification. Panels must comply with UL 67 for panelboard standards and IEEE C2 (National Electrical Safety Code) for safe installations. The schedule serves as a roadmap for:
- Electrical contractors during installation
- Inspectors during code compliance review
- Maintenance personnel for troubleshooting
- Homeowners for understanding their electrical system
| Column | Description | Example |
|---|---|---|
| Circuit # | Position in panel | 1, 2, 3... |
| Description | Load name | "Kitchen Receptacles" |
| Breaker (A) | Overcurrent protection | 20A |
| Poles | Single, double, or triple | 1P, 2P, 3P |
| Voltage | Operating voltage | 120V, 240V |
| Wire Size | Conductor gauge | 12 AWG |
| VA/Watts | Load magnitude | 1,800 VA |
20.0 kW
Total connected load
Largest load
HVAC (35%)
Service size for 20kW
200A typical
After demand factors
~12-15 kW
Step 1: Calculate General Lighting Load
NEC 220.12 specifies minimum lighting loads by occupancy type:
| Occupancy Type | VA per sq ft | Example (2,000 sq ft) |
|---|---|---|
| Dwelling unit | 3 | 6,000 VA |
| Office | 3.5 | 7,000 VA |
| Bank | 3.5 | 7,000 VA |
| School | 3 | 6,000 VA |
| Store | 3 | 6,000 VA |
| Warehouse | 0.5 | 1,000 VA |
| Hospital | 2 | 4,000 VA |
| Restaurant | 2 | 4,000 VA |
Step 2: Add Required Circuits
NEC mandates minimum circuits for dwelling units:
| Required Circuit | Quantity | Breaker | VA Each | Total VA | NEC Reference |
|---|---|---|---|---|---|
| Small appliance (kitchen) | 2 minimum | 20A | 1,500 | 3,000 | 210.11(C)(1) |
| Laundry | 1 minimum | 20A | 1,500 | 1,500 | 210.11(C)(2) |
| Bathroom | 1 minimum | 20A | — | — | 210.11(C)(3) |
The two 20A small appliance circuits must serve ONLY kitchen, dining, and pantry areas. They cannot serve other rooms or fixed appliances like dishwashers.
Step 3: Apply Demand Factors
Not all loads operate simultaneously. NEC 220.42 provides demand factors to calculate realistic panel loading:
20 kW connected load
→ ~12-14 kW demand
HVAC + Electric Heat
Count larger only
Savings from factors
25-40% reduction
Dwelling Unit Demand Factors
| Portion of Load | Demand Factor |
|---|---|
| First 3,000 VA | 100% |
| Remainder | 35% |
Step 4: Add Major Appliances
After the demand-factored general load, add specific equipment:
Electric Range (NEC 220.55)
| Number of Ranges | Demand Load |
|---|---|
| 1 | 8,000 VA |
| 2 | 11,000 VA |
| 3 | 14,000 VA |
| 4 | 17,000 VA |
| 5 | 20,000 VA |
For ranges over 12 kW, add 5% for each kW over 12 kW
Electric Dryer (NEC 220.54)
| Number of Dryers | Demand Factor |
|---|---|
| 1-4 | 100% |
| 5 | 80% |
| 6 | 70% |
| 7 | 65% |
| 8 | 60% |
Minimum demand: 5,000 VA per dryer
HVAC (NEC 220.60)
For noncoincident loads (heating OR cooling):
- Use only the LARGER of heating or cooling load
- Do NOT add both—they don't run simultaneously
- Consider power factor for motor loads
Heat pumps with backup electric heat require both the compressor load AND backup heater load if they can operate simultaneously.
Step 5: Size the Main Breaker
For 240V single-phase residential service:
| Total Demand | Calculated Current | Main Breaker |
|---|---|---|
| Under 12,000 VA | Under 50A | 60A or 100A |
| 12,000-20,000 VA | 50-83A | 100A |
| 20,000-30,000 VA | 83-125A | 125A or 150A |
| 30,000-48,000 VA | 125-200A | 200A |
| Over 48,000 VA | Over 200A | 225A or 400A |
Step 6: Size Branch Circuit Breakers
Most common residential
#12 AWG (20A breaker)
200A service requires
#4/0 AWG minimum
THWN advantage
+15-20% ampacity
The 125% Rule for Continuous Loads
Per NEC 210.20(A), breakers serving continuous loads (3+ hours operation) must be sized at 125%. Breakers must meet UL 489 standards for molded-case circuit breakers. The load calculation formula:
| Continuous Load | Load Current | × 1.25 | Breaker Size |
|---|---|---|---|
| Commercial lighting | 16A | 20A | 20A |
| EV charger (32A) | 32A | 40A | 40A |
| EV charger (40A) | 40A | 50A | 50A |
| Pool pump | 12A | 15A | 15A |
| Water heater | 18.75A | 23.4A | 25A or 30A |
Standard Breaker Sizes (NEC 240.6)
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200A...
Always round UP to the next standard size.
Step 7: Select Wire Sizes
NEC Table 310.16 provides conductor ampacities. For detailed wire selection methods, see our cable sizing guide. Wire selection must also account for voltage drop on longer runs:
Copper Wire Ampacity at Different Temperature Ratings
| Wire Size (AWG) | 60°C | 75°C | 90°C | Typical Use |
|---|---|---|---|---|
| 14 | 15A | 20A | 25A | 15A circuits (lighting) |
| 12 | 20A | 25A | 30A | 20A circuits (receptacles) |
| 10 | 30A | 35A | 40A | 30A circuits (dryer) |
| 8 | 40A | 50A | 55A | 40-50A circuits (range) |
| 6 | 55A | 65A | 75A | 60A circuits (HVAC) |
| 4 | 70A | 85A | 95A | 70-80A circuits |
| 3 | 85A | 100A | 115A | 100A circuits |
| 2 | 95A | 115A | 130A | Sub-panels |
| 1 | 110A | 130A | 145A | Large sub-panels |
| 1/0 | 125A | 150A | 170A | 150A service |
| 2/0 | 145A | 175A | 195A | 175A service |
| 3/0 | 165A | 200A | 225A | 200A service |
| 4/0 | 195A | 230A | 260A | 200A+ service |
- 60°C column: Most residential devices with standard terminals
- 75°C column: When both conductor AND terminations are rated 75°C
- 90°C column: Used for derating calculations only (not termination ampacity)
Step 8: Balance Phases (3-Phase Systems)
Goal: Keep imbalance
<10% of largest phase
Neutral overload risk
Above 30% imbalance
NEC 220.61
70% demand on neutral
For 3-phase panels, distribute loads to keep phases within 10% of each other:
Phase Assignment Rules
| Load Type | Phase Assignment |
|---|---|
| Single-pole 120V | Alternates A-B-C-A-B-C |
| Double-pole 240V | Spans two phases (A-B, B-C, or C-A) |
| Triple-pole 3-phase | All three phases |
Balancing Strategy
- List all loads by phase assignment
- Sum each phase separately
- Calculate imbalance: (Max - Min) / Average
- Target: Under 10% imbalance
- Adjust: Move single-phase loads between phases
Safety and Code Compliance
Panel design must follow NFPA 70 (National Electrical Code) and NFPA 70E for workplace electrical safety. Key compliance points:
| Safety Requirement | NEC Reference | Description |
|---|---|---|
| Working clearance | 110.26 | Min 3 ft depth, 30 in width in front of panel |
| Panel height | 408.37 | Overcurrent devices max 6 ft 7 in above floor |
| Circuit directory | 408.4 | Each circuit must be legibly identified |
| Arc-fault protection | 210.12 | AFCI required for bedrooms, living areas |
| Ground-fault protection | 210.8 | GFCI required for bathrooms, kitchens, outdoors |
Common Panel Configurations
Residential Panels
| Home Size | Typical Panel | Main Breaker | Circuits |
|---|---|---|---|
| Under 1,500 sq ft | 100A, 20-space | 100A | 16-20 |
| 1,500-2,500 sq ft | 200A, 30-space | 200A | 24-30 |
| 2,500-4,000 sq ft | 200A, 42-space | 200A | 32-42 |
| Over 4,000 sq ft | 200A+, 42+ space | 200A+ | 40+ |
Commercial Panels
| Application | Typical Panel | Voltage | Phases |
|---|---|---|---|
| Small office | 100-225A | 120/208V | 3-phase |
| Retail store | 225-400A | 120/208V | 3-phase |
| Restaurant | 400-600A | 120/208V | 3-phase |
| Industrial | 600-1200A | 277/480V | 3-phase |
Try the Calculator
Our interactive Panel Schedule Calculator handles all NEC calculations automatically:
NEC 2023 compliant panel schedule builder with automatic load calculations
Open Calculator