Cable Sizing Calculator

Calculate minimum cable cross-section based on current rating, voltage drop, and installation conditions

IEC 60364-5-52IEC 60287IEC 60228
Calculator Input
Enter your electrical load and installation parameters to calculate the required cable size.
Load Parameters
A

Current that the cable must carry (0.1 - 2000 A)

V

Operating voltage of the circuit (12 - 1000 V)

Single-phase or three-phase electrical system

m

One-way cable run length (1 - 1000 m)

Power factor of the load (0.5 - 1.0, default: 0.8)

Cable Characteristics

Cable conductor material

Cable insulation material (affects temperature rating)

Installation Conditions

How the cable will be installed (affects heat dissipation)

°C

Operating environment temperature (-10 to 60°C, default: 30°C)

Number of cables grouped together (1 - 20, default: 1)

%

Maximum acceptable voltage drop (1 - 5%, default: 3%)

Engineering Theory & Fundamentals
Understanding the engineering principles and standards behind this calculator

Cable sizing ensures electrical conductors can safely carry design loads while maintaining acceptable voltage levels throughout distribution systems, balancing current-carrying capacity (ampacity), voltage drop limitations, short-circuit withstand capability, and economic considerations. Proper cable sizing prevents conductor overheating, minimizes energy losses, ensures protective device coordination, and maintains system reliability. Electrical codes worldwide (NEC, IEC 60364, BS 7671) mandate cables must carry design current without exceeding rated temperature limits—every 10°C10°\text{C} increase above rating potentially halves insulation lifespan through accelerated thermal degradation.

Ampacity and Derating Factors: Current-carrying capacity depends on conductor material (copper offers superior conductivity 58MS/m58\,\text{MS/m} at 20°C20°\text{C}, aluminum provides cost/weight savings requiring larger sizes), insulation type (PVC 70°C70°\text{C}, XLPE 90°C90°\text{C}, EPR 90°C90°\text{C}), and installation method (open air provides best cooling, enclosed conduits require significant derating). Derating factors account for installation conditions: ambient temperature corrections adjust for deviation from 30°C30°\text{C} reference, grouping factors (0.7-0.9) address thermal interaction between adjacent cables sharing conduits/trays, and soil thermal resistivity affects buried cables. Modern installations increasingly specify XLPE for superior thermal performance, moisture resistance, and aging characteristics.

Voltage Drop Constraints: While ampacity ensures safe operation, voltage drop affects equipment performance and power quality. Excessive drop causes motor overheating, lamp flickering, control system malfunction, and elevated I2RI^2R losses. Electrical codes typically limit voltage drop to 3% for branch circuits, 5% total from source to load—representing compromise between conductor cost and system performance. Voltage drop = 2×I×L×R/10002 \times I \times L \times R / 1000 for single-phase (where LL is one-way length), 3×I×L×R/1000\sqrt{3} \times I \times L \times R / 1000 for three-phase. Inductive reactance becomes significant in large cables (>95mm2>95\,\text{mm}^2) and long feeders, particularly at low power factors, requiring inclusion of both resistance and reactance components.

Short-Circuit Protection: Cables must withstand fault currents without insulation damage during protective device operating time. The adiabatic equation relates minimum conductor size to fault current magnitude and duration, assuming all thermal energy remains in conductor during brief fault conditions. This calculation typically governs equipment grounding conductors and bonding jumpers where fault current may greatly exceed normal load current. Modern installations coordinate short-circuit analysis with protective device settings to ensure cables survive worst-case fault scenarios.

Economic and Harmonic Considerations: Life-cycle cost analysis balances initial conductor cost against lifetime I2RI^2R losses—larger cables reduce operating costs through decreased electricity consumption. High-utilization feeders justify upsizing beyond minimum code requirements. Harmonic currents from modern electronic loads (VFDs, switching power supplies, LED lighting) increase conductor heating through skin effect. Neutral conductors in three-phase systems may carry triplen harmonics (3rd, 9th, 15th) that add arithmetically rather than canceling, potentially exceeding phase conductor currents and requiring neutral upsizing.

Standards Reference: NEC Article 310 specifies conductor ampacity and sizing requirements. IEC 60364-5-52 provides international cable selection standards. IEEE 141 (Red Book) addresses industrial power system cable sizing including voltage drop and short-circuit analysis.

Learn More

Dive deeper with our comprehensive guide

Mathematical Formulas
Engineering equations with detailed explanations and unit references
15 formulas

Usage Examples

Real-world scenarios showing how to use this calculator effectively