Cable Sizing Calculator
Calculate minimum cable cross-section based on current rating, voltage drop, and installation conditions
Cable sizing ensures electrical conductors can safely carry design loads while maintaining acceptable voltage levels throughout distribution systems, balancing current-carrying capacity (ampacity), voltage drop limitations, short-circuit withstand capability, and economic considerations. Proper cable sizing prevents conductor overheating, minimizes energy losses, ensures protective device coordination, and maintains system reliability. Electrical codes worldwide (NEC, IEC 60364, BS 7671) mandate cables must carry design current without exceeding rated temperature limits—every increase above rating potentially halves insulation lifespan through accelerated thermal degradation.
Ampacity and Derating Factors: Current-carrying capacity depends on conductor material (copper offers superior conductivity at , aluminum provides cost/weight savings requiring larger sizes), insulation type (PVC , XLPE , EPR ), and installation method (open air provides best cooling, enclosed conduits require significant derating). Derating factors account for installation conditions: ambient temperature corrections adjust for deviation from reference, grouping factors (0.7-0.9) address thermal interaction between adjacent cables sharing conduits/trays, and soil thermal resistivity affects buried cables. Modern installations increasingly specify XLPE for superior thermal performance, moisture resistance, and aging characteristics.
Voltage Drop Constraints: While ampacity ensures safe operation, voltage drop affects equipment performance and power quality. Excessive drop causes motor overheating, lamp flickering, control system malfunction, and elevated losses. Electrical codes typically limit voltage drop to 3% for branch circuits, 5% total from source to load—representing compromise between conductor cost and system performance. Voltage drop = for single-phase (where is one-way length), for three-phase. Inductive reactance becomes significant in large cables () and long feeders, particularly at low power factors, requiring inclusion of both resistance and reactance components.
Short-Circuit Protection: Cables must withstand fault currents without insulation damage during protective device operating time. The adiabatic equation relates minimum conductor size to fault current magnitude and duration, assuming all thermal energy remains in conductor during brief fault conditions. This calculation typically governs equipment grounding conductors and bonding jumpers where fault current may greatly exceed normal load current. Modern installations coordinate short-circuit analysis with protective device settings to ensure cables survive worst-case fault scenarios.
Economic and Harmonic Considerations: Life-cycle cost analysis balances initial conductor cost against lifetime losses—larger cables reduce operating costs through decreased electricity consumption. High-utilization feeders justify upsizing beyond minimum code requirements. Harmonic currents from modern electronic loads (VFDs, switching power supplies, LED lighting) increase conductor heating through skin effect. Neutral conductors in three-phase systems may carry triplen harmonics (3rd, 9th, 15th) that add arithmetically rather than canceling, potentially exceeding phase conductor currents and requiring neutral upsizing.
Standards Reference: NEC Article 310 specifies conductor ampacity and sizing requirements. IEC 60364-5-52 provides international cable selection standards. IEEE 141 (Red Book) addresses industrial power system cable sizing including voltage drop and short-circuit analysis.
Related Calculators
You might also need these calculators
Referenced Standards & Guidelines
Calculations comply with the following authoritative sources
IEC 60364 - Low-voltage Electrical Installations
IEC 60364 (2017)
International standard for electrical installation design, protection against electric shock, and overcurrent protection.
NEC (National Electrical Code) - NFPA 70
NFPA 70 (2023)
US electrical installation code covering wiring, protection, and equipment standards for safe electrical systems.
BS 7671 - Requirements for Electrical Installations (IET Wiring Regulations)
BS 7671:2018+A2:2022 (2022)
UK electrical installation standard covering design, erection, and verification of electrical installations.
All formulas and calculations are based on peer-reviewed standards and official engineering guidelines
Usage Examples
Real-world scenarios showing how to use this calculator effectively