Table of Contents
kVA to Amps Conversion Guide
100 kVA at 400V three-phase = $(100 \times 1000) / (1.732 \times 400) = 144.3 amps
Introduction
The kVA to amps calculator helps engineers convert apparent power to current for electrical system design. Our free kVA to amps conversion tool supports both single-phase and three-phase systems. Transformers, generators, and UPS systems display their capacity in kVA, but cables, breakers, and busbars must be sized for current in amperes.
Why This Conversion Matters
When a project specifies a 500 kVA transformer, the immediate engineering question is: what cable size feeds it, and what breaker protects it? The answer requires converting that kVA rating to amperes—specifically, 722A at 400V three-phase. Miss this conversion, and you risk undersized cables that overheat, undersized breakers that trip nuisance faults, or oversized infrastructure that wastes capital. Every major electrical component selection—from the main distribution panel to branch circuit conductors—depends on accurate kVA-to-amp conversion.
The Fundamental Challenge
The relationship between kVA and amperes depends entirely on voltage, and three-phase systems add the factor that catches many engineers off guard. A 100 kVA load draws 144A at 400V but 277A at 208V—nearly double the current at the lower voltage. Single-phase calculations differ from three-phase calculations. This guide systematically addresses voltage levels, phase configurations, and the critical safety factors required by IEC 60364-5-52 for proper cable sizing.
What You'll Learn
This guide provides the complete methodology for kVA-to-amp conversions across all electrical configurations. You'll master the formulas for single-phase and three-phase systems with proper voltage selection per IEC 60038 standards. Practical examples demonstrate cable sizing with temperature correction, grouping factors, and voltage drop verification. Reference tables provide quick multipliers for common voltage levels and standard transformer current ratings.
Quick Answer: How to Convert kVA to Amps
Convert apparent power (kVA) to current (amps) by dividing kVA by voltage. For three-phase systems, also divide by .
Conversion Formulas
| System Type | Formula | Notes |
|---|---|---|
| Single-Phase | Simple division | |
| Three-Phase | Line-to-line voltage, |
Where:
- = Current (A)
- kVA = Apparent power (kilovolt-amperes)
- = Potential (V)
Quick Reference
| Electrical potential | System | Multiplier | Example |
|---|---|---|---|
| 230V | Single-Phase | ||
| 120V | Single-Phase | ||
| 400V | Three-Phase | ||
| 480V | Three-Phase |
Worked Example
Reference Table
| Parameter | Typical Range | Standard |
|---|---|---|
| Three-Phase Factor () | 1.732 | Mathematical constant |
| Continuous Load Factor | 125% | IEC 60364-5-52, NEC 215.2 |
| Temperature Correction (35°C) | 0.94 | IEC Table B.52-14 |
| Grouping Factor (4-6 cables) | 0.80 | IEC Table B.52-17 |
| Voltage Drop Limit (Feeders) | ≤3% | IEC 60364-5-52 |
Key Standards
IEC 60364-5-52: Requires 125% safety margin for continuous loads when sizing conductors. NEC 215.2: Specifies feeder conductor sizing at 125% of continuous load. Always verify voltage type (line-to-line vs line-to-neutral) on equipment nameplates.
- 480V 3-phase:
- 208V 3-phase:
- 230V single-phase:
Common transformer currents at 400V 3-phase:
- 100 kVA → 144A → 70mm2 cable
- 250 kVA → 361A → 185mm2 cable
- 500 kVA → 722A → cable
- 1000 kVA → 1443A → conductor or busbar
- 1600 kVA → 2310A → Busbar mechanism
Electrical line sizing safety factors (IEC 60364-5-52):
- Continuous load (h): Multiply by 1.25
- Temperature (35°C): Divide by 0.94
- Grouping (4 cables): Divide by 0.80
- Combined: Amp Electric current 1.66
Example: 500 kVA transformer wiring sizing:
- Full load: 722 A
- With safety factors: A required
- Lead: per phase ( after derating = 720A actual)
- Volt level drop limit: 3% = 12V at 400V
Critical rules:
- Always use (1.732) for 3-phase calculations
- Use line-to-line potential (phase-to-phase), not line-to-neutral
- Apply 125% factor for continuous loads
- Verify electrical potential drop 3% for feeders
Standards Reference
IEC 60364-5-52 - Wire Sizing:
- V value drop limits: 3% for feeders, 5% total installation
- Continuous load factor: 125% for loads operating 3 hours
- Temperature correction factors apply for ambient temperatures above reference
NEC Article 215 - Feeders:
- Feeder conductors sized at 125% of continuous load
- Overcurrent protection coordination required
IEEE 141 - Industrial Wattage Systems:
- Three-phase calculations use factor
- Line-to-line electric tension standard for equipment ratings
Understanding Current Calculation from kVA
Amperage (I) measured in amperes (A) represents the flow of electric charge through a conductor. Converting from kVA to amps is essential for lead sizing, protection device selection, and electrical load analysis.
Why Convert kVA to Amps?
Electrical Equipment Ratings:
- Transformers are rated in kVA
- Generators are rated in kVA or kW
- Cables are rated by electrical flow-carrying capacity (amps)
- Circuit breakers are rated by amp (amps)
Design Requirements:
- Wire sizing requires knowing electric current flow
- Overcurrent protection must be based on I value
- Volt level drop calculations need amperage values
- Thermal analysis of conductors uses electrical flow
Key Concept: A 500 kVA transformer at 400V 3-phase produces approximately 722 amps. This amp rating determines the minimum conductor size, breaker rating, and busbar capacity required.
Relationship to Power and Voltage:
The fundamental relationship is based on the definition of apparent energy:
Single-Phase Conversion
For single-phase systems, electric current is calculated by dividing apparent electrical power by potential.
Formula Derivation:
Starting from the wattage equation:
Solving for I value:
Converting kVA to VA:
Important: This formula assumes balanced loads and sinusoidal waveforms. For non-linear loads with harmonics, additional derating may be required per IEC 61000-3-2.
Example Calculation:
Given:
- Apparent load: S = 10 kVA
- Electrical potential: V = 230V (single-phase)
Solution:
Application: For this 10 kVA load at 230V, you would need:
- Minimum electrical line size: 10 mm2 copper (IEC 60364-5-52, Table B.52-3, 50A rating)
- Circuit breaker: 50A Type C (allowing for inrush currents)
- V value drop budget: Max 3% = 6.9V over wiring length
Three-Phase Conversion
For three-phase systems, there are two methods depending on electric tension measurement type.
Method 1: Line-to-Line Voltage (Most Common)
Formula:
Where:
- = Phase amperage in amperes
- = Apparent capacity in kilovolt-amperes
- = Line-to-line volt level (between any two phases)
- 1.732
Example:
- = 100 kVA
- = 400V
Pro Tip: For quick estimates, use the "2A per kVA" rule at 400V: . This works for 380-415V systems.
Method 2: Line-to-Neutral Voltage
Formula:
Example:
- = 100 kVA
(Small difference due to rounding of )
Standard Three-Phase Voltages:
| Installation | Region | ||
|---|---|---|---|
| LV | 400V | 230V | Europe, Asia, Africa |
| LV | 380V | 220V | Parts of Asia |
| LV | 415V | 240V | Australia, NZ |
| LV | 208V | 120V | North America (commercial) |
| LV | 480V | 277V | North America (industrial) |
| MV | 11kV | 6.35kV | Distribution |
| MV | 33kV | 19.05kV | Sub-transmission |
Line-to-Line vs Line-to-Neutral
Line-to-Line (L-L) - MOST COMMON
When to Use:
- Balanced three-phase loads (motors, transformers)
- Delta-connected equipment
- Standard equipment nameplates (e.g., "400V 3-phase")
Measurement:
- Potential between any two phase conductors
- Use with formula
Line-to-Neutral (L-N)
When to Use:
- Wye (star) connected loads with neutral
- Single-phase loads on three-phase equipment
- Lighting circuits on commercial systems
Measurement:
- Electrical potential between one phase and neutral
- Use with factor of 3 formula
Voltage Relationship:
For a balanced wye infrastructure:
Example: If = 230 400V
Critical: Always verify V value type on equipment nameplates. A motor rated "230V 3-phase" expects 230V line-to-line, NOT line-to-neutral!
Worked Example: cable sizing
Scenario: Size cables for a 500 kVA, 400V three-phase transformer secondary.
Step 1: Calculate Full Load Current
Using L-L formula:
Step 2: Apply Continuous Load Factor (125%)
Per IEC 60364-5-52, for continuous loads ( 3 hours):
Step 3: Apply Temperature Correction
Ambient degree 35°C, correction factor = 0.94:
Step 4: Apply Grouping Factor
4 cables in conduit, grouping factor = 0.80:
Step 5: Select Cable Size
From IEC 60364-5-52, Table B.52-3 (copper, XLPE, 70°C):
- 240 mm2: 340A (too small)
- per phase: 680A (too small)
- per phase: per phase ✘
- per phase: ✘
- per phase: ✘
- per phase: ✘
Solution: Use per phase (nearest standard size above requirement)
Actual capacity: A > 721.69A ✔
Step 6: Verify voltage drop
For 30m run, using electric tension drop formula:
Where R = 0.0469 Ω/km for 400 mm2 copper at 70°C:
Percentage drop: 0.44% ✔ (well below 3% limit)
Worked Example: Generator Feeder
Scenario: Size feeder for 750 kVA, 480V three-phase generator.
Step 1: Calculate Full Load Current
Step 2: Apply NEC 125% Continuous Load Factor
Per NEC 445.13:
Step 3: Select Conductor Size
From NEC Table 310.16, 75°C copper in conduit:
- 500 kcmil: 430A (too small)
- per phase: 860A (too small)
- per phase: (marginal)
- per phase: ✔
Solution: Use () per phase
Step 4: Select Overcurrent Protection
Per NEC 445.13, maximum OCPD = 115% of generator rating:
Select 1000A circuit breaker (next standard size below 1037A)
Step 5: Verify Short Circuit Rating
Generator subtransient reactance X"d = 15%:
Circuit breaker must have interrupting rating . Select 10kA or 14kA rated breaker ✔
Practical Applications
1. Transformer Secondary Cable Sizing
Common transformer sizes and currents at 400V:
| Transformer kVA | Electrical flow (A) | Typical Lead Size (Copper) |
|---|---|---|
| 100 kVA | 144A | 70 mm2 |
| 250 kVA | 361A | 185 mm2 |
| 500 kVA | 722A | |
| 800 kVA | 1155A | |
| 1000 kVA | 1443A | |
| 1600 kVA | 2310A | (busbar recommended) |
| 2000 kVA | 2887A | Busbar setup required |
Design Practice: For transformers 1000 kVA, consider busbar systems instead of cables for better thermal performance and easier maintenance.
2. Switchboard Main Bus Rating
Find busbar amp rating for a building with:
- Transformer: 1600 kVA, 400V
- Demand factor: 80% (NEC 220-87)
Select 2000A busbar (next standard size)
3. Motor Control Center Feeder
Evaluate feeder for MCC serving:
- Connected load: 450 kVA of motors
- Demand factor: 75% (NEC 430-26)
- Energy factor: 0.85 (typical for motors)
With 125% sizing: A
Select cables ( A) ✔
Common Mistakes
Mistake 1: Forgetting for Three-Phase
Wrong:
Correct:
Impact: Wire would be undersized by 73%, causing overheating and potential fire hazard!
Mistake 2: Using Line-to-Neutral Instead of Line-to-Line
A 100 kVA transformer rated 400V means 400V line-to-line, not line-to-neutral.
Wrong:
Correct:
Mistake 3: Ignoring Safety Factors
Using full load electric current without applying correction factors:
Unsafe: Selecting 150A conductor for 144A load ✘
Safe: ✔
Mistake 4: Not Accounting for Harmonic Currents
Modern electronic loads (VFDs, UPS, LED lighting) produce harmonic currents that increase RMS I value and neutral amperage.
Typical derating:
- < 15% THD: No derating
- 15-33% THD: Derate by 0.90
- 33-45% THD: Derate by 0.80
- > 45% THD: Detailed harmonic analysis required
For a data center with 45% THD:
Mistake 5: Confusing Transformer kVA with Load kVA
Scenario: 500 kVA transformer serving 350 kVA load.
Wrong approach: Size cables for 350 kVA load ✘
Correct approach: Size cables for 500 kVA transformer rating ✔
Reason: Cables must handle transformer short-circuit electrical flow and future load growth.
Industry Standards
IEC 60364-5-52 - Cable Selection
Key requirements:
- Conductor sizing based on continuous amp
- Heat level correction factors (Table B.52-14 to B.52-16)
- Grouping factors (Table B.52-17 to B.52-20)
- Volt level drop limits: 3% feeders, 5% total
Installation methods:
- Method A1: Insulated conductors in conduit in thermally insulated wall
- Method C: Single-layer cables on wall or unperforated tray
- Method E: Cables on perforated tray or ladder
NEC (NFPA 70) - Conductor Sizing
Relevant sections:
- 215.2(A)(1): Feeder conductor sizing at 125% continuous load
- 240.4(B): Overcurrent protection for conductors
- 310.15(B): Ampacity tables and correction factors
- 430.24: Machine feeder sizing at 125% of largest drive unit plus sum of others
Derating factors:
- More than 3 conductors: 80% (4-6), 70% (7-9), 50% (10-20)
- Ambient > 30°C: Apply correction per Table 310.15(B)(2)(a)
IEEE 519 - Harmonic Limits
Electric current distortion limits at PCC:
| ISC / IL | THD | Individual Harmonic |
|---|---|---|
| < 20 | 4.0% | 2.0% |
| 20-50 | 7.0% | 3.5% |
| 50-100 | 10.0% | 4.5% |
| 100-1000 | 12.0% | 5.5% |
| > 1000 | 15.0% | 7.0% |
Where:
- = Maximum short-circuit I value at PCC
- = Maximum demand load amperage (fundamental) at PCC
Critical for Modern Systems: With increasing use of VFDs and switch-mode electrical power supplies, always consider harmonic currents in electrical line sizing. Neutral conductors may need to be oversized for triplen harmonics.
Using Our kVA-to-Amp Calculator
Features:
✅ Single-phase and three-phase calculations with automatic formula selection
✅ Line-to-line and line-to-neutral potential options
✅ Instant results with formulas shown
✅ Built-in warnings for high currents (IEC compliance)
✅ Mobile-friendly interface
How to Use:
-
Select phase configuration:
- Single phase
- Three-phase (Line-to-Line)
- Three-phase (Line-to-Neutral)
-
Enter apparent wattage: In kVA (e.g., 500)
-
Enter electrical potential: In volts
- Single phase: 230V, 120V
- Three-phase L-L: 400V, 480V, 11000V
- Three-phase L-N: 230V, 277V
-
Click Measure to get electrical flow in amperes
-
Review warnings if amp exceeds IEEE/IEC thresholds
Pro Tip: Use our calculator to quickly verify hand calculations and explore different V value options for optimal wiring sizing.
Our calculations follow industry best practices and have been validated against real-world scenarios.
Conclusion
Converting kVA to amps is fundamental to electrical engineering, essential for cable sizing and selection, overcurrent protection device rating, busbar and switchgear sizing, voltage drop calculations, and thermal analysis of conductors. Understanding the differences between single-phase and three-phase current calculations, applying appropriate safety factors, and considering harmonics for modern electronic loads enables engineers to properly size electrical components and ensure safe, code-compliant installations. Always verify voltage type (line-to-line vs line-to-neutral) on equipment nameplates and account for future expansion when sizing equipment.
Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.
Key Takeaways
- Convert kVA to amps using formulas: Single-Phase: ; Three-Phase: , where
- Always use factor for three-phase line-to-line voltage calculations—omitting it causes 73% underestimation of current, leading to dangerously undersized conductors
- Verify voltage type on equipment nameplates—"400V 3-phase" means 400V line-to-line, not line-to-neutral; using wrong voltage type causes significant calculation errors
- Apply safety factors: 125% for continuous loads (IEC 60364-5-52, NEC 215.2), temperature correction (0.94 at 35°C), grouping factors (0.80 for 4-6 cables), and harmonic derating for electronic loads
- Three-phase systems deliver same power with 33% less current per conductor compared to single-phase, making them more efficient for larger loads and requiring smaller conductors
- For transformers ≥1000 kVA, consider busbar systems instead of cables for better thermal performance and easier maintenance
Further Learning
- Amp to kVA Guide - Reverse conversion from current to apparent power
- Cable Sizing Guide - Comprehensive cable selection guide
- Transformer Sizing Guide - Understanding transformer ratings
- Voltage Drop Guide - Verify voltage drop meets code requirements
- Power Factor Guide - Understanding power factor and correction
- kVA to Amp Calculator - Interactive calculator for conversions
References & Standards
This guide follows established engineering principles and standards. For detailed requirements, always consult the current adopted edition in your jurisdiction.
Primary Standards
IEC 60364-5-52 Low-voltage electrical installations - Part 5-52: Selection and erection of electrical equipment - Wiring systems. Specifies conductor sizing based on current, temperature correction, and grouping factors.
NEC Article 215 Feeders - Requires conductors sized at 125% of continuous load for feeders.
NEC Article 310 Conductors for General Wiring - Provides ampacity tables and correction factors for conductor sizing.
Supporting Standards & Guidelines
IEEE Std 141 Recommended Practice for Electric Power Distribution for Industrial Plants. Provides guidance on load calculations and system design.
IEEE Std 519 Recommended Practice and Requirements for Harmonic Control in Electric Power Systems. Specifies harmonic current limits and derating factors for electronic loads.
IEC 60050 - International Electrotechnical Vocabulary International standards for electrical terminology and definitions.
NEMA Publications National Electrical Manufacturers Association standards for electrical equipment.
Further Reading
- Electrical Installation Guide - Schneider Electric - Comprehensive guide to electrical installation best practices
Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.
Disclaimer: This guide provides general technical information based on international electrical standards. Always verify calculations with applicable local electrical codes (NEC, IEC, BS 7671, etc.) and consult licensed electrical engineers or electricians for actual installations. Electrical work should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.