Guides
ElectricalBeginner8 min
ReviewedStandards-Based

Amp to KW Calculator - Convert Current to Power

Learn how to convert current in amperes (A) to power in kilowatts (kW). Supports DC, AC single-phase, and AC three-phase systems with power factor correction.

Enginist Engineering Team
Professional electrical engineers with expertise in power systems, circuit design, and electrical code compliance.
Reviewed by PE-Licensed Electrical Engineers
Published: October 19, 2025
Updated: November 9, 2025

Amp to KW Calculator - Convert Current to Power

Quick AnswerHow do you convert amps to kW?
Convert amps to kW using the formula for single-phase or three-phase AC systems. For DC circuits, simply use P=V×IP = V \times I (no power factor needed).
P=V×I×PF1000P = \frac{V \times I \times PF}{1000} (single-phase) or P=3×V×I×PF1000P = \frac{\sqrt{3} \times V \times I \times PF}{1000} (three-phase)
Example

20A at 400V three-phase with PF=0.88 gives (1.732×400×20×0.88)/1000=12.19(1.732 \times 400 \times 20 \times 0.88) / 1000 = 12.19 kW

Introduction

Converting current (amperes) to power (kilowatts) is essential for electrical system design, equipment sizing, and energy analysis. However, current alone cannot determine power—you need voltage and, for AC systems, power factor to calculate real power consumption.

Why This Conversion Matters

Understanding the relationship between current, voltage, and power enables engineers to:

  • Size electrical equipment properly — Select circuit breakers, conductors, transformers, and protective devices
  • Analyze energy consumption — Calculate power usage for billing, efficiency analysis, and load management
  • Verify motor performance — Confirm motors operate within rated current and power specifications
  • Comply with electrical codes — Meet NEC, IEC, and local code requirements for conductor sizing and protection

The Fundamental Challenge

The relationship between current and power differs by circuit type:

DC Circuits: P=I×VP = I \times V

Single-Phase AC: P=I×V×PFP = I \times V \times PF

Three-Phase AC: P=3×I×VLL×PFP = \sqrt{3} \times I \times V_{LL} \times PF

What You'll Learn

This guide is designed for electrical engineers, technicians, and students who need to calculate power from current and voltage for DC and AC systems. You will learn:

  • Fundamental power formulas for DC, single-phase AC, and three-phase AC systems
  • Power factor considerations — How to account for power factor in AC circuits
  • Three-phase power calculations — Line-to-line vs. line-to-neutral voltage applications
  • Motor current analysis — Converting nameplate current ratings to power
  • Circuit protection sizing — Selecting breakers and conductors based on power calculations
  • Practical applications — Equipment sizing, energy management, and code compliance

Quick Answer: How to Convert Amps to kW

Convert current (amps) to power (kilowatts) by multiplying current by voltage and dividing by 1000. For AC systems, include power factor. For three-phase systems, include the 3\sqrt{3} factor.

Conversion Formulas

System TypeFormulaNotes
DCP=I×V1000P = \frac{I \times V}{1000}Simple voltage ×\times amperage
AC Single-PhaseP=I×V×PF1000P = \frac{I \times V \times PF}{1000}Include power factor
AC Three-Phase (Line-to-Line)P=3×I×VLL×PF1000P = \frac{\sqrt{3} \times I \times V_{\text{LL}} \times PF}{1000}Include 3\sqrt{3} factor (1.732)
AC Three-Phase (Line-to-Neutral)P=3×I×VLN×PF1000P = \frac{3 \times I \times V_{\text{LN}} \times PF}{1000}Three times single-phase

Parameters:

  • II = Electrical flow (A)
  • VV = Potential (V)
  • PFPF = Electrical power factor (0 to 1.0)
  • 3\sqrt{3} = 1.732 (three-phase factor)

What Are Some Worked Examples of?

DC System: 10A at 230V
P=10×2301000=2.3 kWP = \frac{10 \times 230}{1000} = \textbf{2.3 kW}
AC Single-Phase: 15A at 230V, PF=0.85
P=15×230×0.851000=2.93 kWP = \frac{15 \times 230 \times 0.85}{1000} = \textbf{2.93 kW}
AC Three-Phase: 20A at 400V, PF=0.88
P=3×20×400×0.881000=12.19 kWP = \frac{\sqrt{3} \times 20 \times 400 \times 0.88}{1000} = \textbf{12.19 kW}

What Does the Reference Table Show for?

ParameterTypical RangeStandard
Power Factor (Resistive Loads)1.0Unity
Power Factor (Motors, Full Load)0.85-0.90Typical
Power Factor (Motors, Half Load)0.70-0.80Typical
Power Factor (Fluorescent Lights)0.50-0.90Varies by ballast
Three-Phase Factor (√3)1.732Mathematical constant

What Are the Key Standards for?

What Is Current, Voltage, and Power?

Current (A)

Amp is the flow of electric charge, measured in amperes (A). It represents how much electricity is flowing through a conductor.

Key Points:

  • Measured in amperes (A)
  • Represents charge flow rate
  • Depends on load and V value
  • Determines conductor sizing

Voltage (V)

Electric tension is the electrical potential difference, measured in volts (V). It represents the force pushing electric current through a circuit.

Key Points:

  • Measured in volts (V)
  • Represents electrical pressure
  • Determines I value flow
  • Affects electrical power consumption

Power (kW)

Wattage is the rate of energy consumption or generation, measured in kilowatts (kW). It represents how much work is being done.

Key Points:

  • Measured in kilowatts (kW)
  • Represents energy rate
  • Product of amperage and volt level
  • Determines equipment sizing

Power Coefficient (PF)

Load factor is the ratio of real capacity to apparent energy in AC systems, representing the efficiency of electrical power usage.

Key Points:

  • Ranges from 0 to 1
  • Affects AC wattage calculations
  • Indicates load efficiency
  • Important for equipment design

The Formulas

DC Power Formula

For direct electrical flow (DC) systems, the formula is straightforward:

P=I×V1000P = \frac{I \times V}{1000}

Where:

  • P(kW) = Load in kilowatts
  • I(A) = Amp in amperes
  • V(V) = Potential in volts
  • 1000 = Conversion factor (W to kW)

AC Single-Phase Formula

For alternating electric current single-phase systems, capacity factor must be considered:

P=PF×I×V1000P = \frac{PF \times I \times V}{1000}

Where:

  • PF = Energy factor (0 to 1)
  • Other variables same as DC

AC Three-Phase Formula (Line-to-Line)

For three-phase systems with line-to-line electrical potential:

P=3×PF×I×VLL1000P = \frac{\sqrt{3} \times PF \times I \times V_{\text{LL}}}{1000}

Where:

  • VLLV_{\text{LL}} = Line-to-line V value
  • 31.732\sqrt{3} \approx 1.732 (three-phase factor)

AC Three-Phase Formula (Line-to-Neutral)

For three-phase systems with line-to-neutral electric tension:

P=3×PF×I×VLN1000P = \frac{3 \times PF \times I \times V_{\text{LN}}}{1000}

Where:

  • VLNV_{\text{LN}} = Line-to-neutral volt level
  • 33 = Number of phases

Step-by-Step Calculations

Example 1: DC Power

Problem: A DC machine draws 10 A at 230 V. Compute the electrical power consumption.

Solution:

  1. Identify infrastructure type: DC

  2. Given values:

    • I value (I) = 10 A
    • Potential (V) = 230 V
  3. Apply DC formula:

    P=I×V1000P=10×2301000=23001000=2.3kWP = \frac{I \times V}{1000} P = \frac{10 \times 230}{1000} = \frac{2300}{1000} = 2.3\,\text{kW}
  4. Result: The drive unit consumes 2.3 kW of wattage.

Example 2: AC Single-Phase

Problem: An AC single-phase load draws 15 A at 230 V with 0.85 load factor. Find the real capacity.

Solution:

  1. Identify setup type: AC Single-Phase

  2. Given values:

    • Amperage (I) = 15 A
    • Electrical potential (V) = 230 V
    • Energy Factor (PF) = 0.85
  3. Apply AC single-phase formula:

    P=PF×I×V1000P=0.85×15×2301000=2932.51000=2.93kWP = \frac{PF \times I \times V}{1000} P = \frac{0.85 \times 15 \times 230}{1000} = \frac{2932.5}{1000} = 2.93\,\text{kW}
  4. Result: The load consumes 2.93 kW of real electrical power.

Example 3: AC Three-Phase (Line-to-Line)

Problem: A three-phase wattage unit draws 20 A at 400 V line-to-line with 0.88 load factor. Evaluate the capacity.

Solution:

  1. Identify arrangement type: AC Three-Phase (Line-to-Line)

  2. Given values:

    • Electrical flow (I) = 20 A
    • V value (VLLV_{\text{LL}}) = 400 V
    • Energy Factor (PF) = 0.88
  3. Apply three-phase formula:

    P=3×PF×I×VLL1000P=1.732×0.88×20×4001000=12193.281000=12.19kWP = \frac{\sqrt{3} \times PF \times I \times V_{\text{LL}}}{1000} P = \frac{1.732 \times 0.88 \times 20 \times 400}{1000} = \frac{12193.28}{1000} = 12.19\,\text{kW}
  4. Result: The motor unit consumes 12.19 kW of electrical power.

What Are Some Practical Examples of?

Example 4: Industrial Motor

Scenario: An industrial three-phase electric motor draws 50 A at 380 V line-to-line with 0.85 wattage factor. Measure the load rating.

Given:

  • Amp = 50 A
  • Electric tension (LL) = 380 V
  • Capacity Factor = 0.85

Analysis:

P=3×0.85×50×3801000=1.732×0.85×50×3801000=27970.81000=27.97kWP = \frac{\sqrt{3} \times 0.85 \times 50 \times 380}{1000} = \frac{1.732 \times 0.85 \times 50 \times 380}{1000} = \frac{27970.8}{1000} = 27.97\,\text{kW}

Result: The machine has a energy rating of approximately 28 kW.

Example 5: Household Load

Scenario: A household appliance draws 8 A at 230 V single-phase with 0.95 electrical power factor. Assess the wattage consumption.

Given:

  • Electric current = 8 A
  • Volt level = 230 V
  • Load Factor = 0.95

Determination:

P=0.95×8×2301000=17481000=1.748kWP = \frac{0.95 \times 8 \times 230}{1000} = \frac{1748}{1000} = 1.748\,\text{kW}

Result: The appliance consumes 1.75 kW of capacity.

Example 6: Low reactive power ratio Load

Scenario: A fluorescent lighting mechanism draws 5 A at 230 V with 0.6 energy factor. Determine the real electrical power.

Given:

  • I value = 5 A
  • Potential = 230 V
  • Wattage Factor = 0.6

Evaluation:

P=0.6×5×2301000=6901000=0.69kWP = \frac{0.6 \times 5 \times 230}{1000} = \frac{690}{1000} = 0.69\,\text{kW}

Result: Despite drawing 5 A, the load only consumes 0.69 kW of real load due to low capacity factor.

System Types

DC Systems

Characteristics:

  • Constant electrical potential and amperage
  • No energy factor
  • Simple electrical power assessment
  • Used in batteries, solar panels, DC motors

Formula: P(kW) = I(A)×V(V)1000\frac{I(A) \times V(V)}{1000}

AC Single-Phase Systems

Characteristics:

  • Alternating electrical flow
  • Requires wattage factor
  • Common in residential applications
  • 230 V or 120 V standard voltages

Formula: P (kW)=PF×I (A)×V (V)1000P\ (\text{kW}) = \frac{PF \times I\ (\text{A}) \times V\ (\text{V})}{1000}

AC Three-Phase Systems

Characteristics:

  • Three alternating currents
  • Higher performance
  • Used in industrial applications
  • 380 V, 400 V, or 480 V standard voltages

Formulas:

  • Line-to-Line: P=3×PF×I×VLL1000P = \frac{\sqrt{3} \times PF \times I \times V_{\text{LL}}}{1000}
  • Line-to-Neutral: P=3×PF×I×VLN1000P = \frac{3 \times PF \times I \times V_{\text{LN}}}{1000}

Standards and References

International Standards

  • IEC 60050-131: International Electrotechnical Vocabulary
  • IEC 60034-1: Rotating electrical machines
  • IEEE 141: Electric load distribution for industrial plants

Typical Power Factors

Load TypeCapacity Factor
Incandescent Lights1.0
Resistance Heaters1.0
Motors (Full Load)0.85-0.90
Motors (Half Load)0.70-0.80
Fluorescent Lights0.50-0.90
Induction Furnaces0.60-0.70

Our calculations follow industry best practices and have been validated against real-world scenarios.

Conclusion

Converting current (amps) to power (kilowatts) is essential for electrical system design, equipment sizing and selection, load calculations, energy consumption analysis, and cost estimation. Understanding the differences between DC, AC single-phase, and AC three-phase power calculations enables accurate system design and efficient power usage. The formulas vary by system type: DC uses simple multiplication, AC single-phase requires power factor, and AC three-phase includes the √3 factor. Always use accurate voltage measurements and power factor values for reliable results.

Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.


What Are the Key Takeaways from?

  • Convert amps to kW using formulas: DC: P=I×V1000P = \frac{I \times V}{1000}; AC Single-Phase: P=I×V×PF1000P = \frac{I \times V \times PF}{1000}; AC Three-Phase: P=3×I×VLL×PF1000P = \frac{\sqrt{3} \times I \times V_{\text{LL}} \times PF}{1000}
  • Power factor is critical for AC systems—ignoring it leads to significant inaccuracies; typical values: resistive loads 1.0, motors 0.85-0.90, fluorescent lights 0.50-0.90
  • Three-phase systems use 3\sqrt{3} (1.732) factor for line-to-line voltage calculations; line-to-neutral uses factor of 3 instead of 3\sqrt{3}
  • Always verify voltage type (line-to-line vs line-to-neutral) for three-phase systems to avoid calculation errors
  • Use measured or nameplate values for current, voltage, and power factor rather than assumptions for accurate power calculations
  • This conversion is essential for motor sizing, circuit breaker selection, energy audits, generator sizing, and solar power system design

Where Can You Learn More About?

What Are the References for & Standards?

This guide follows established engineering principles and standards. For detailed requirements, always consult the current adopted edition in your jurisdiction.

Primary Standards

IEC 60050-131 International Electrotechnical Vocabulary - Part 131: Electric and magnetic circuits. Defines power calculation methods for DC and AC systems.

IEC 60034-1 Rotating electrical machines - Part 1: Rating and performance. Specifies motor ratings and power factor values.

IEC 61000-4-30 Electromagnetic compatibility (EMC) - Part 4-30: Testing and measurement techniques - Power quality measurement methods. Provides standards for power factor measurement.

Supporting Standards & Guidelines

National Electrical Code (NEC) Article 430 Motors, Motor Circuits, and Controllers - Specifies motor current calculations and protection requirements.

IEC 60364-5-52 Low-voltage electrical installations - Part 5-52: Selection and erection of electrical equipment - Wiring systems. Provides guidance on cable sizing based on current.

IEC 60050 - International Electrotechnical Vocabulary International standards for electrical terminology and definitions.

NEMA Publications National Electrical Manufacturers Association standards for electrical equipment.

Further Reading

Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.


Disclaimer: This guide provides general technical information based on international electrical standards. Always verify calculations with applicable local electrical codes (NEC, IEC, BS 7671, etc.) and consult licensed electrical engineers or electricians for actual installations. Electrical work should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.

Frequently Asked Questions

Amp to kW Calculator | Enginist