Table of Contents
Cable Sizing Guide: IEC 60364-5-52 Standards
50A load with combined derating K=0.63 needs 80A rated cable—select 25mm² copper XLPE (88A) per IEC 60364-5-52
Introduction
In March 2021, a pharmaceutical manufacturing plant in New Jersey experienced a catastrophic production shutdown when their main distribution cable failed during peak summer demand. The 185mm² feeder cable, originally sized for 400A continuous load, was now serving 520A after facility expansions—but no one had recalculated the derating factors. At 42°C ambient with six cables bundled in the same tray, the effective ampacity had dropped to just 380A. The cable insulation degraded over three years of chronic overheating, ultimately causing a $2.3 million fire and 11 weeks of lost production. A proper cable sizing calculation would have flagged this issue for under $15,000 in cable upgrades.
The cable connecting source to load must accomplish two critical tasks simultaneously: carry current without overheating, and deliver voltage without excessive drop. Getting either wrong creates problems—from fire hazards with undersized cables to wasted capital with oversized ones.
Why This Calculation Matters
A cable that can safely carry 50A based on ampacity tables might still fail your installation if it's 100 meters long and drops 8% of the supply voltage. Conversely, a cable sized perfectly for voltage drop might run too hot in a conduit with other cables. Every installation requires checking both criteria, and the larger cable size governs. This dual requirement catches many engineers who focus only on current-carrying capacity.
The Fundamental Challenge
Cable sizing involves multiple interacting factors: ambient temperature, installation method, cable grouping, insulation type, conductor material, and circuit length. A 16mm² cable might carry 80A in free air but only 50A when bundled with other cables in a warm environment. Temperature correction factors, grouping factors, and installation method factors all compound, making the effective current rating significantly different from the base value in standard tables. This guide systematically addresses these derating factors.
What You'll Learn
This guide covers the complete cable sizing methodology per IEC 60364-5-52 standards. You'll master the ampacity-based sizing with correction factors (K₁, K₂, K₃), voltage drop verification for single-phase and three-phase circuits, and the process for selecting from standard conductor sizes per IEC 60228. Practical examples demonstrate the complete workflow from load calculation to final cable selection with code compliance verification.
Quick Answer: Cable Size Calculation Formula
Cable sizing requires two critical calculations: ampacity-based sizing and voltage drop verification.
Core Formulas
| Calculation Type | Formula | Application |
|---|---|---|
| Ampacity-Based Sizing | Determines minimum cable rating based on load and conditions | |
| Voltage Drop (Single-Phase) | Verifies potential drop for single-phase systems | |
| Electrical potential Drop (Three-Phase) | Verifies V value drop for three-phase systems |
Parameters:
- = Required conductor rating (A)
- = Design load current (A)
- = Temperature correction factor
- = Grouping correction factor
- = Installation method correction factor
- = Load current (A)
- = Electrical line length one way (m)
- = Resistance per km (Ω/km)
Voltage Drop Limits
IEC 60364-5-52 Maximum Allowable Electric tension Drop:
- Lighting circuits: 3% maximum
- Power circuits: 5% maximum
- Combined (from origin): 5% maximum total
Field Tip: When calculating cable derating for grouped circuits, apply ALL derating factors simultaneously to the base ampacity—not sequentially. A 35mm² copper cable rated at 119A (Method C), grouped with 3 other cables (×0.79) at 40°C ambient (×0.91), safely carries only 85.6A. I've seen installations fail inspection because designers applied factors one-by-one and got 96A instead. Always multiply: 119 × 0.79 × 0.91 = 85.6A per IEC 60364-5-52 Table B.52.17.
Standard Sizing Process
- Calculate design amperage () from load power
- Apply correction factors (, ) for installation conditions
- Select wiring from IEC 60228 standard sizes
- Verify volt level drop () is within limits
- Confirm protection coordination with overcurrent devices
Quick Example: Three-Phase Motor Circuit
Reference Values
| Parameter | Typical Range | Standard |
|---|---|---|
| Voltage Drop Limit (Lighting) | 3% maximum | IEC 60364-5-52 |
| Voltage Drop Limit (Power) | 5% maximum | IEC 60364-5-52 |
| Temperature Correction (K₁) | 0.71-1.00 | Based on ambient temperature |
| Grouping Correction (K₂) | 0.60-1.00 | Based on number of cables |
| Installation Method (K₃) | 0.70-1.00 | Based on installation type |
| Standard Cable Sizes | 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm² | IEC 60228 |
Key Standards
IEC 60364-5-52: Specifies cable sizing requirements including ampacity calculations, correction factors, and voltage drop limits. Requires verification of both current-carrying capacity and voltage drop for all installations.
1 Introduction to Cable Sizing
Electrical line sizing involves determining the minimum conductor cross-sectional area required to:
- Carry the load amperage safely without exceeding temperature limits (ampacity)
- Limit electric tension drop to acceptable levels (typically 3-5%)
- Withstand short-circuit currents for protection device operating times
- Account for installation conditions and environmental factors
Key Standards
- IEC 60364-5-52: Low-voltage electrical installations - Selection and erection of electrical equipment - Wiring systems
- IEC 60287: Electric cables - Calculation of current rating
- IEC 60228: Conductors of insulated cables
2 Ampacity-Based Sizing
2.1 Base Current-Carrying Capacity
The ampacity () is the maximum amp a wiring can carry continuously without exceeding its heat rating.
Standard reference conditions:
- Ambient thermal value: 30°C for cables in air, 20°C for buried cables
- Single circuit
- Installation method reference (e.g., Method C - clipped direct on non-metallic surface)
2.2 Correction Factors
The actual electric current-carrying capacity must account for installation conditions:
Where:
- = Design load I value (A)
- = Degree correction factor
- = Grouping correction factor
- = Installation method correction factor
Temperature Correction ()
For PVC thermal resistance (70°C max):
| Ambient Temp | 25°C | 30°C | 35°C | 40°C | 45°C | 50°C |
|---|---|---|---|---|---|---|
| Factor | 1.03 | 1.00 | 0.94 | 0.87 | 0.79 | 0.71 |
For XLPE thermal protection (90°C max):
| Ambient Temp | 25°C | 30°C | 35°C | 40°C | 45°C | 50°C |
|---|---|---|---|---|---|---|
| Factor | 1.04 | 1.00 | 0.96 | 0.91 | 0.87 | 0.82 |
At 50°C ambient
PVC: -29% capacity
At 50°C ambient
XLPE: -18% capacity
XLPE advantage
+11% more capacity
Grouping Correction ()
Number of cables grouped together affects heat dissipation:
| Cables | Enclosed | On Wall | In Air | Underground |
|---|---|---|---|---|
| 1 | 1.00 | 1.00 | 1.00 | 1.00 |
| 2 | 0.80 | 0.85 | 0.88 | 0.90 |
| 3 | 0.70 | 0.79 | 0.82 | 0.85 |
| 4-6 | 0.65 | 0.73 | 0.77 | 0.80 |
| 7-9 | 0.60 | 0.68 | 0.73 | 0.75 |
| 10-20 | 0.50 | 0.62 | 0.68 | 0.70 |
Worst case (10+ enclosed)
-50% capacity!
Typical (3 cables on wall)
-21% capacity
Best case (single cable)
No derating
Installation Method Factor ()
| Method | Description | Factor |
|---|---|---|
| A1/A2 | Enclosed conduit in thermally insulated wall | 0.50 |
| B1/B2 | Enclosed conduit on wall/spaced from wall | 0.80 |
| C | Clipped direct (non-metallic surface) | 0.95 |
| D/E | In air on lead tray/ladder | 1.00 |
| D1 | Underground direct burial | 1.00 |
2.3 Standard Cable Sizes (IEC 60228)
Copper conductor cross-sections (mm2): 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630
Aluminum conductor cross-sections (mm2): 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630
2.4 Current-Carrying Capacity Tables
Copper PVC 70°C - Method C (Clipped Direct):
| Size (mm2) | Single Phase (A) | Three Phase (A) |
|---|---|---|
| 1.5 | 17.5 | 15.5 |
| 2.5 | 24 | 21 |
| 4 | 32 | 28 |
| 6 | 41 | 36 |
| 10 | 57 | 50 |
| 16 | 76 | 68 |
| 25 | 101 | 89 |
| 35 | 125 | 110 |
| 50 | 151 | 134 |
| 70 | 192 | 171 |
| 95 | 232 | 207 |
| 120 | 269 | 239 |
| 150 | 309 | 275 |
Copper XLPE 90°C - Method C (Clipped Direct):
| Size (mm2) | Single Phase (A) | Three Phase (A) |
|---|---|---|
| 1.5 | 23 | 20 |
| 2.5 | 31 | 27 |
| 4 | 42 | 37 |
| 6 | 54 | 47 |
| 10 | 75 | 66 |
| 16 | 100 | 89 |
| 25 | 133 | 117 |
| 35 | 164 | 145 |
| 50 | 198 | 175 |
| 70 | 253 | 224 |
| 95 | 306 | 271 |
| 120 | 354 | 314 |
| 150 | 407 | 361 |
Typical residential (2.5mm²)
PVC: 24A / XLPE: 31A
Industrial motor (35mm²)
PVC: 125A / XLPE: 164A
Heavy feeder (120mm²)
PVC: 269A / XLPE: 354A
3 Voltage Drop Calculations
3.1 Maximum Allowable Voltage Drop
Per IEC 60364-5-52:
- Lighting circuits: 3% maximum
- Other uses: 5% maximum
- Combined (from origin): 5% maximum total
3.2 Voltage Drop Formulas
Single-Phase (two-wire) Systems:
Three-Phase (three-wire or four-wire) Systems:
Note: This formula is already correctly wrapped in LaTeX math mode.
Where:
- = Potential drop (V)
- = Load amperage (A)
- = Wire length one way (m)
- = Resistance per km (Ω/km)
- = Reactance per km (Ω/km)
- = Load factor
- = Reactive factor
Percentage electrical potential drop:
3.3 Cable Resistance Values (at 70°C)
Copper conductors (Ω/km):
| Size (mm2) | R (Ω/km) | X (Ω/km) |
|---|---|---|
| 1.5 | 13.30 | 0.145 |
| 2.5 | 8.21 | 0.135 |
| 4 | 5.09 | 0.125 |
| 6 | 3.39 | 0.120 |
| 10 | 2.00 | 0.110 |
| 16 | 1.24 | 0.105 |
| 25 | 0.795 | 0.100 |
| 35 | 0.565 | 0.095 |
| 50 | 0.393 | 0.090 |
| 70 | 0.277 | 0.085 |
| 95 | 0.206 | 0.082 |
| 120 | 0.161 | 0.080 |
| 150 | 0.129 | 0.078 |
Aluminum conductors (Ω/km):
| Size (mm2) | R (Ω/km) | X (Ω/km) |
|---|---|---|
| 16 | 2.03 | 0.105 |
| 25 | 1.30 | 0.100 |
| 35 | 0.927 | 0.095 |
| 50 | 0.641 | 0.090 |
| 70 | 0.453 | 0.085 |
| 95 | 0.337 | 0.082 |
| 120 | 0.265 | 0.080 |
| 150 | 0.211 | 0.078 |
3.4 Simplified Voltage Drop (for )
For typical capacity factor 0.8 and short conductor runs where X·sin is negligible:
Single-phase:
Three-phase:
4 Practical Cable Sizing Procedure
Step 1: Determine Design Current ()
From connected load energy:
Single-phase:
Three-phase:
Note: The formulas above are already correctly wrapped in LaTeX math mode.
Step 2: Apply Correction Factors
Measure required base electrical flow rating:
Step 3: Select Cable from Tables
Choose the smallest standard electrical line size with amp rating
Step 4: Verify Voltage Drop
Assess V value drop for selected wiring. If allowable limit, select next larger lead size.
Step 5: Check Short-Circuit Rating
Verify wire can withstand fault electric current for protection device operating time (beyond this guide's scope).
5 Worked Examples
Example 1: Three-Phase Motor Circuit
Given:
- Machine electrical power: 15 kW
- Electric tension: 400V, three-phase
- Wattage factor: 0.85
- Conductor length: 40m
- Installation: Clipped direct on wall (Method C)
- Ambient heat level: 35°C
- 2 cables grouped together
- Heat barrier: XLPE 90°C
- Material: Copper
Step 1: Design I value
Step 2: Correction factors
- (35°C for XLPE): 0.96
- (2 cables on wall): 0.85
- (Method C): 0.95
Required rating:
Step 3: Select electrical line
From tables, 6mm2 XLPE has 47A rating (three-phase) > 32.9A ✔
Step 4: Check volt level drop
For 6mm2 copper: R = 3.39 /km
1.3% < 5% allowable ✔
Result: Use 6mm2 copper XLPE wiring
Example 2: Single-Phase Lighting Circuit
Given:
- Load: 3.5 kW
- Potential: 230V, single-phase
- Load factor: 1.0 (resistive)
- Lead length: 25m
- Installation: In conduit on wall (Method B)
- Ambient temp: 30°C
- Single circuit
- Isolation: PVC 70°C
- Material: Copper
Step 1: Design amperage
Step 2: Correction factors
- (30°C for PVC): 1.00
- (single circuit): 1.00
- (Method B): 0.80
Required rating:
Step 3: Select wire
From tables, 2.5mm2 PVC has 24A rating (single-phase) > 19.0A ✔
Step 4: Check electrical potential drop (lighting: 3% max)
For 2.5mm2 copper: R = 8.21 Ω/km
2.7% < 3% allowable ✔
Result: Use 2.5mm2 copper PVC conductor
6 Common Design Considerations
6.1 Oversizing Benefits
Consider upsizing electrical line when:
- Future load expansion is likely (+20-30%)
- Very long wiring runs (over 100m)
- Critical circuits requiring high reliability
- Energy savings from reduced I2R losses justify cost
6.2 Aluminum vs Copper
Aluminum advantages:
- Lower material cost
- Lighter weight (important for long runs)
- Suitable for larger sizes (greater than 35mm2)
Copper advantages:
- Higher conductivity ( aluminum)
- Better mechanical strength
- Easier termination
- Preferred for smaller sizes (less than 35mm2)
Choose Copper when:
- • Size < 35mm²
- • Complex routing/bending
- • Easy termination needed
Choose Aluminum when:
- • Size > 35mm²
- • Long runs (weight matters)
- • Cost is primary concern
6.3 Insulation Selection
PVC (70°C):
- Lower cost
- Suitable for most general applications
- Max continuous thermal reading: 70°C
- Short-circuit heat: 160°C
XLPE (90°C):
- Higher continuous thermal value rating
- Better thermal and electrical properties
- Longer service life
- 20-30% higher ampacity than PVC
- Short-circuit degree: 250°C
- Preferred for industrial applications
6.4 Parallel Cables
For very high currents, multiple cables in parallel may be more economical than single large lead:
Requirements:
- Same length, cross-section, material, construction
- Equal load sharing
- Derating factor for grouping applies
- Terminations must ensure equal electrical flow distribution
7 Safety and Compliance
7.1 Protection Coordination
Wire must be protected by overcurrent device (MCB/MCCB/Fuse):
Where:
- = Nominal amp of protective device
- = Electric current-carrying capacity of conductor
- = Capacity correction factor
7.2 Fault Protection
Electrical line must withstand short-circuit I value () for fault clearing time ():
Where:
- = Minimum cross-sectional area (mm2)
- = Short-circuit amperage (A)
- = Fault clearing time (s)
- = Material/thermal resistance constant (115 for Cu/PVC, 143 for Cu/XLPE)
7.3 Environmental Considerations
Account for:
- Ambient heat level: Derating above 30°C
- Burial depth: Thermal resistance increases with depth
- Soil thermal resistivity: 2.5 K·m/W standard, derate if higher
- Solar radiation: Add 15-20°C for cables in direct sun
- Chemical exposure: Select appropriate thermal protection/sheath
8 Common Mistakes to Avoid
- Ignoring correction factors - Always apply ,
- Using nominal V value for electric tension drop - Use actual system volt level
- Forgetting wiring length is one-way - Total circuit length = 2x lead length
- Neglecting future loads - Size for expected growth
- Wrong capacity factor assumption - Verify actual load characteristics
- Not considering installation method - Significant impact on ampacity
- Mixing conductor materials - Don't mix copper and aluminum
- Inadequate short-circuit protection - Always verify fault withstand
9 Quick Reference Tables
Typical Conductor Temperatures
| Heat barrier Type | Max Continuous (°C) | Short-Circuit (°C) |
|---|---|---|
| PVC | 70 | 160 |
| XLPE | 90 | 250 |
| EPR | 90 | 250 |
Standard Voltage Levels (IEC 60038)
| System | Nominal Potential | Tolerance |
|---|---|---|
| LV Single-phase | 230V | ±10% |
| LV Three-phase | 400V | ±10% |
| MV (Europe) | 10kV, 20kV | ±10% |
Cable Selection Flowchart Summary
- Determine design electrical flow ()
- Determine correction factors (, )
- Compute required rating ()
- Select wire from tables ()
- Verify electrical potential drop ( limit)
- Check protection coordination
- Verify short-circuit withstand (if applicable)
Real-World Case Studies
Case Study 1: Data Center UPS Feeder Upgrade
Case Study 2: Solar Farm DC Cable Fire
Case Study 3: Industrial Motor Voltage Drop Failure
Quick Reference Card
Cable Selection Decision Matrix
| Scenario | Primary Concern | Typical Solution |
|---|---|---|
| Long runs (>50m) | Voltage drop | Increase cable size 1-2 steps |
| Hot environments (>40°C) | Temperature derating | Use XLPE instead of PVC |
| Multiple cables grouped | Grouping factor | Increase spacing or cable size |
| Motor circuits | Starting voltage drop | Size for 6× FLA starting current |
| Critical loads | Redundancy | Parallel cables with 20% margin |
Derating Factor Quick Reference
| Condition | Typical Factor | Impact |
|---|---|---|
| 35°C ambient (PVC) | 0.94 | -6% capacity |
| 40°C ambient (PVC) | 0.87 | -13% capacity |
| 45°C ambient (XLPE) | 0.87 | -13% capacity |
| 3 cables grouped | 0.79 | -21% capacity |
| 6 cables grouped | 0.73 | -27% capacity |
| Enclosed conduit | 0.80 | -20% capacity |
| Direct burial | 1.00 | No reduction |
Design Checklist
Before Finalizing Any Cable Selection:
- Calculated design current including all connected loads?
- Applied ALL three derating factors (, , )?
- Used operating temperature resistance (not 20°C values)?
- Verified voltage drop for both running AND starting conditions?
- Selected from IEC 60228 standard sizes (not custom)?
- Checked protection device coordination ()?
- Considered future load growth (20-30% margin)?
- Documented all assumptions for code review?
10 Conclusion
Proper cable sizing requires careful consideration of multiple factors including design current, correction factors for installation conditions, voltage drop limits, and short-circuit ratings. By following the systematic approach outlined in this guide and applying IEC 60364-5-52 standards, engineers can select cables that ensure electrical safety, system reliability, and energy efficiency. Always verify calculations with manufacturer data and local electrical codes, and consult licensed electrical engineers for complex installations.
Export as PDF — Generate professional reports for documentation, client presentations, or permit submissions.
Key Takeaways
- Cable sizing requires two critical verifications: ampacity-based sizing using correction factors (K₁, K₂, K₃) and voltage drop verification to ensure compliance with 3-5% limits
- Apply correction factors for ambient temperature (K₁), cable grouping (K₂), and installation method (K₃) to determine actual current-carrying capacity
- Voltage drop limits: 3% maximum for lighting circuits and 5% maximum for power circuits per IEC 60364-5-52
- Always select the smallest standard cable size (per IEC 60228) that meets both ampacity and voltage drop requirements
- Verify short-circuit ratings to ensure cables can withstand fault currents for protection device operating times
- Consider economic optimization balancing initial cost against energy losses over the cable's lifetime
Related Guides
- Voltage Drop Guide - Detailed voltage drop calculations and verification methods
- Power Factor Guide - Understanding power factor and its impact on cable sizing
- Transformer Sizing Guide - Proper transformer selection for cable installations
- Cable Sizing Calculator - Interactive calculator with automatic correction factors
References & Standards
This guide follows established engineering principles and standards. For detailed requirements, always consult the current adopted edition in your jurisdiction.
Primary Standards
IEC 60364-5-52 Low-voltage electrical installations - Part 5-52: Selection and erection of electrical equipment - Wiring systems. Specifies cable sizing requirements, correction factors, and voltage drop limits.
IEC 60287 Electric cables - Calculation of the current rating. Provides methods for calculating current-carrying capacity under various installation conditions.
IEC 60228 Conductors of insulated cables. Defines standard conductor sizes and resistance values.
Supporting Standards & Guidelines
National Electrical Code (NEC) Comprehensive electrical safety standards for the United States. Article 310 specifies conductor ampacity requirements.
IEEE Standards Institute of Electrical and Electronics Engineers technical standards for electrical installations.
IEC 60050 - International Electrotechnical Vocabulary International standards for electrical terminology and definitions.
NEMA Publications National Electrical Manufacturers Association standards for electrical equipment.
Further Reading
- Electrical Installation Guide - Schneider Electric - Comprehensive guide to electrical installation best practices
Note: Standards and codes are regularly updated. Always verify you're using the current adopted edition applicable to your project's location. Consult with local authorities having jurisdiction (AHJ) for specific requirements.
Disclaimer: This guide provides general technical information based on international electrical standards. Always verify calculations with applicable local electrical codes (NEC, IEC, BS 7671, etc.) and consult licensed electrical engineers or electricians for actual installations. Electrical work should only be performed by qualified professionals. Component ratings and specifications may vary by manufacturer.