Comparisons
ventilationComparison

Supply vs Exhaust

Supply vs exhaust ventilation comparison: building pressure, air quality, energy efficiency, and application requirements. Complete guide with ASHRAE pressurization strategies and system selection.

Enginist Team
Published: November 25, 2025
Updated: December 1, 2025

Supply vs Exhaust Ventilation: Complete Airflow Strategy Comparison

Quick AnswerShould I use supply or exhaust ventilation?
Use supply ventilation to deliver filtered outdoor air and create positive building pressure that prevents infiltration—essential for offices, clean zones, and most commercial spaces. Use exhaust ventilation to remove contaminated air and create negative pressure that contains pollutants—essential for kitchens, bathrooms, labs, and isolation rooms. Most buildings need both: supply-dominant overall (105-110% of exhaust) for positive pressure, with dedicated exhaust from contaminated zones.

Quick Verdict

Supply and exhaust ventilation serve complementary purposes—neither is complete alone.

Bottom Line: Modern buildings require both supply and exhaust ventilation working together. Supply ventilation delivers clean, filtered outdoor air and creates positive pressure preventing uncontrolled infiltration. Exhaust ventilation removes contaminated air at the source and maintains negative pressure in spaces like kitchens, bathrooms, and laboratories. The key is proper balance: typically 5-10% more supply than exhaust to maintain slight positive building pressure while ensuring exhaust from all contaminated zones.

At-a-Glance Comparison Table

FeatureSupply VentilationExhaust VentilationWinner
Building PressurePositive (prevents infiltration)Negative (draws infiltration)Supply
Air FiltrationFilters outdoor airCannot filter makeup airSupply
Contaminant ControlDilution onlySource captureExhaust
Heat RecoveryPossible with HRV/ERVPossible with HRV/ERVTie
Humidity ControlCan dehumidify supplyCannot control infiltrationSupply
System CostHigher (conditioning)Lower (exhaust only)Exhaust
Best ForClean spaces, officesKitchens, labs, bathrooms

How Supply and Exhaust Ventilation Work

Understanding airflow direction and pressure effects is fundamental to system design.

Supply Ventilation

Supply ventilation uses fans to push outdoor air into the building:

Airflow path:

  1. Outdoor air drawn through intake
  2. Air filtered and conditioned (optional)
  3. Air distributed to occupied spaces
  4. Air exits through exhaust openings, envelope leaks, or relief dampers

Pressure effect:

  • Supply > Exhaust = Positive pressure
  • Air flows outward through envelope cracks
  • Prevents uncontrolled infiltration

Benefits:

  • Controls air entry point and quality
  • Enables filtration and conditioning
  • Prevents moisture infiltration (hot-humid climates)
  • Provides consistent outdoor air delivery

Exhaust Ventilation

Exhaust ventilation uses fans to remove air from the building:

Airflow path:

  1. Air removed from contaminated zones
  2. Makeup air enters through intakes or envelope leaks
  3. No direct control over makeup air quality
  4. Negative pressure maintained in exhausted zones

Pressure effect:

  • Exhaust > Supply = Negative pressure
  • Air flows inward through envelope cracks
  • Draws outdoor air through uncontrolled paths

Benefits:

  • Captures contaminants at source
  • Prevents contaminant spread to adjacent spaces
  • Simple, lower-cost systems
  • Essential for odor/fume control

Balanced Ventilation

Balanced systems provide equal supply and exhaust:

True balanced (HRV/ERV):

  • Separate supply and exhaust fans
  • Heat exchange between airstreams
  • Minimal pressure differential
  • Maximum energy recovery

Quasi-balanced (typical commercial):

  • Slight supply-dominant (105-110%)
  • Positive overall pressure
  • Local exhaust from contaminated zones
  • Practical approach for most buildings

Pressure Control: The Strategic Decision

Building pressurization strategy drives system design.

Positive Pressure Benefits

BenefitExplanationApplication
Infiltration preventionOutdoor air enters through controlled intakes, not cracksAll conditioned buildings
Moisture controlPrevents humid outdoor air from entering envelopeHot-humid climates
Dust controlReduces particle entry through envelopeClean environments, data centers
Consistent ventilationKnown supply rate vs uncertain infiltrationCode compliance
Energy efficiencyConditioned air not lost to stack effectHigh-rise buildings

Positive pressure targets:

  • Standard commercial: 0.02-0.05" WG (5-12 Pa)
  • Healthcare: 0.03-0.05" WG (7.5-12 Pa)
  • Clean rooms: 0.05-0.10" WG (12-25 Pa)

Negative Pressure Benefits

BenefitExplanationApplication
Contaminant containmentPrevents spread to adjacent spacesLabs, isolation rooms
Odor controlCaptures odors before they spreadKitchens, bathrooms
Process exhaustMaintains capture at sourceIndustrial processes
Infection controlPrevents airborne pathogen spreadHealthcare isolation

Negative pressure targets:

  • Bathrooms: 0.01-0.03" WG relative to corridor
  • Kitchens: 0.03-0.05" WG relative to dining
  • Isolation rooms: 0.01-0.03" WG relative to corridor (minimum 3 Pa)
  • Laboratories: 0.03-0.10" WG relative to corridor

Pressure Cascade Strategy

Office Building with Kitchen: Pressure Strategy

Zone pressures (relative to outdoors):

ZoneTarget PressureStrategy
Offices+0.05" WGSupply-dominant, positive
Corridors+0.02" WGNeutral reference
Restrooms-0.02" WGExhaust-dominant, negative
Kitchen-0.05" WGStrong exhaust, negative
Lobby (entrance)+0.03" WGSlight positive

Airflow direction: Office → Corridor → Restroom/Kitchen → Exhaust

Supply/exhaust balance:

  • Total supply: 10,000 CFM
  • Office exhaust: 0 CFM (transfer to corridors)
  • Restroom exhaust: 500 CFM
  • Kitchen exhaust: 2,500 CFM
  • Building exhaust/relief: 6,500 CFM
  • Net positive: 500 CFM (5% positive)

Verdict: Pressure Control

Winner: Application-Dependent — Positive pressure is correct for clean zones and most building areas; negative pressure is correct for contaminated zones. The strategy is a design choice based on space use, not a universal recommendation.

Air Quality Control

Supply Ventilation Air Quality

Control over incoming air:

  • Filtration: MERV 8-16 typical, HEPA for critical
  • Conditioning: Heating, cooling, dehumidification
  • Consistent delivery: Known CFM regardless of weather
  • Distribution: Directed to occupied zones

Limitations:

  • Cannot capture contaminants at source
  • Dilution ventilation only for indoor pollutants
  • Requires makeup air path for local exhaust

Exhaust Ventilation Air Quality

Control over outgoing air:

  • Source capture: Removes contaminants where generated
  • Prevents spread: Negative pressure contains pollutants
  • Direct removal: Kitchen fumes, bathroom odors, lab vapors

Limitations:

  • No control over makeup air quality
  • Makeup enters through envelope (unfiltered)
  • Infiltration path unknown and variable

Combined Strategy Example

Commercial Kitchen Ventilation

Exhaust requirement (kitchen hood):

  • Hood exhaust: 5,000 CFM
  • Creates strong negative pressure

Supply/makeup requirement:

  • Makeup air unit: 5,500 CFM (110% of exhaust)
  • Provides: filtered, tempered outdoor air
  • Result: Kitchen slightly negative relative to dining, but not excessively so

Air quality outcomes:

  • Cooking fumes captured at hood (exhaust)
  • Filtered outdoor air provided (supply)
  • Kitchen negative prevents odor spread
  • Dining area maintains positive pressure

Without supply/makeup:

  • Kitchen goes strongly negative
  • Unfiltered air enters through doors
  • HVAC system unbalanced
  • Comfort complaints from drafts

Verdict: Air Quality

Winner: Combined — Supply controls what enters (filtration, conditioning); exhaust controls what leaves (source capture). Both are required for complete air quality control.

Energy Considerations

Supply Ventilation Energy

Energy components:

  • Fan power: Moving outdoor air into building
  • Conditioning: Heating/cooling outdoor air to supply temperature
  • Distribution: Duct pressure losses

Heat recovery opportunity:

  • With HRV/ERV: 70-85% of exhaust energy recovered
  • Reduces conditioning load significantly
  • Requires balanced airflow (supply ≈ exhaust)

Exhaust Ventilation Energy

Energy components:

  • Fan power: Moving exhaust air out
  • Lost conditioned air: Energy in exhausted air is wasted
  • Makeup air conditioning: If makeup is provided

Energy characteristics:

  • Lower fan energy than supply (simpler systems)
  • No heat recovery unless paired with supply
  • Makeup air through envelope = no conditioning control

Energy Comparison

ScenarioSupply EnergyExhaust EnergyNotes
Exhaust only0MediumMakeup uncontrolled, no recovery
Supply onlyHigh0Can filter/condition, no recovery
Balanced (no recovery)MediumMediumControlled, but no recovery
Balanced with HRVMediumMediumBest: 70-85% recovery

Verdict: Energy

Winner: Balanced with Recovery — Neither supply nor exhaust alone optimizes energy. Balanced systems with heat recovery (HRV/ERV) capture maximum benefit from both strategies.

Application-Specific Recommendations

When to Use Supply-Dominant Ventilation

Use supply-dominant (positive pressure) for:

  • Office buildings and commercial spaces
  • Healthcare clean zones (patient rooms, ORs)
  • Clean rooms and controlled environments
  • Data centers and computer rooms
  • Retail spaces
  • Schools and educational facilities
  • Assembly spaces (theaters, conference rooms)
  • Buildings in hot-humid climates

Supply-dominant design:

  • Supply = 105-110% of total exhaust
  • Filtered, conditioned outdoor air
  • Positive building pressure (0.02-0.05" WG)
  • Local exhaust from bathrooms, janitor closets

When to Use Exhaust-Dominant Ventilation

Use exhaust-dominant (negative pressure) for:

  • Commercial kitchens
  • Bathrooms and restrooms
  • Laboratory fume hoods
  • Hospital isolation rooms
  • Industrial process areas
  • Paint booths and spray areas
  • Welding shops
  • Parking garages (CO control)
  • Any space generating contaminants

Exhaust-dominant design:

  • Exhaust sized for contaminant capture
  • Dedicated makeup air (supply) for balance
  • Negative pressure relative to adjacent zones
  • May be positive relative to outdoors if makeup exceeds exhaust

Balanced Ventilation Applications

Use balanced ventilation for:

  • Tight residential construction
  • Passive house / net-zero buildings
  • Any building wanting maximum heat recovery
  • Mixed-use buildings with multiple pressure requirements
  • Buildings in extreme climates (maximize recovery)

System Design Considerations

Supply System Components

ComponentFunctionDesign Consideration
Outdoor air intakeAir entry pointLocation away from exhaust, pollutants
FiltersParticle removalMERV 8-16, pressure drop
Heating/cooling coilTemperingSize for design conditions
Supply fanAir deliverySized for duct pressure + filter
DuctworkDistributionEqual friction or velocity reduction
DiffusersRoom distributionThrow, noise, draft risk

Exhaust System Components

ComponentFunctionDesign Consideration
Capture hoods/grillesContaminant collectionCapture velocity, hood design
DuctworkAir transportMaterial for contaminant, velocity
Exhaust fanAir removalSized for system pressure
Discharge locationAir releaseAway from intakes, property line
Makeup air sourceBalanceDedicated unit or transfer air

Pressure Control Strategies

Building pressure control:

  • Monitor: Pressure sensor at representative location
  • Control: Modulate supply VFD or relief damper
  • Target: 0.02-0.05" WG positive (adjustable)
  • Alarms: High/low pressure alerts

Zone pressure control:

  • Monitor: Pressure sensor in controlled zone
  • Control: Modulate supply or exhaust damper
  • Target: Per zone requirements
  • Interlock: Fail-safe with exhaust critical zones

Common Mistakes to Avoid

MistakeImpactPrevention
Exhaust without makeupExcessive negative pressure, drafts, door problemsSize supply/makeup to match exhaust
Over-pressurizing buildingDoors difficult to open, energy wasteTarget 0.02-0.05" WG only
Kitchen exhaust without makeupBack-drafting, smoke complaintsDedicated makeup air for kitchen
Lab exhaust without supplyNegative cascade, spread of contaminantsZone-by-zone pressure control
Ignoring stack effectPressure varies with heightConsider stack effect in high-rise
No pressure monitoringUnknown building conditionInstall building pressure sensor

Use these calculators for ventilation design:

Key Takeaways

  • Supply ventilation: Delivers controlled outdoor air, creates positive pressure, enables filtration
  • Exhaust ventilation: Removes contaminated air, creates negative pressure, captures pollutants
  • Both are needed: Supply for clean zones, exhaust for contaminated zones, balanced for overall building
  • Positive pressure standard: Most buildings target 5-10% supply-dominant for positive pressure
  • Heat recovery: Balanced systems enable 70-85% energy recovery from exhaust air

Further Reading

References & Standards

  • ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality
  • ASHRAE Handbook—HVAC Applications: Chapter 34, Kitchen Ventilation
  • ASHRAE Handbook—Fundamentals: Chapter 16, Ventilation and Infiltration
  • IMC (International Mechanical Code): Chapter 5, Exhaust Systems

Disclaimer: This comparison provides general technical guidance. Building ventilation design requires detailed analysis of occupancy, activities, and local codes. Always consult with qualified engineers and verify compliance with local requirements before finalizing ventilation strategies.

Frequently Asked Questions