Comparisons
electricalComparison

Copper vs Aluminum

Copper vs aluminum cable comparison: 61% conductivity difference, cost analysis, weight advantages, and reliability factors with sizing tables and NEC/IEC compliance guidelines for electrical installations.

Enginist Team
Published: November 23, 2025
Updated: December 3, 2025

Copper vs Aluminum Cable: Complete Engineering Comparison

Quick AnswerWhich is better: copper or aluminum cable?
Choose copper cables for space-constrained installations, branch circuits, and maximum reliability; choose aluminum for service entrances and feeders where cost and weight matter. Copper has 100% IACS conductivity vs aluminum's 61%—aluminum needs approximately 1.6 times larger cross-section for same ampacity. However, aluminum is 70% lighter and 40-60% cheaper per equivalent current capacity per NEC Table 310.16.

Quick Verdict

Choosing between copper and aluminum conductors is one of the most impactful decisions in electrical design—it affects cost, installation difficulty, long-term reliability, and code compliance. Neither material is universally "better"; the optimal choice depends on your specific application.

Bottom Line: Copper is the better choice for branch circuits under 100A and space-constrained installations due to its 64% higher conductivity and maintenance-free connections. However, aluminum becomes the clear winner for service entrances over 100A, long feeder runs, and budget-constrained projects where 40-60% material cost savings justify the additional termination care required.

For most residential and light commercial work, copper remains the standard. For large commercial, industrial, and utility applications, aluminum dominates due to compelling economics.

At-a-Glance Comparison Table

FeatureCopperAluminumWinner
Conductivity (IACS)100% (reference)61%Copper
Density8.9 g/cm³2.7 g/cm³ (70% lighter)Aluminum
Thermal Expansion16.5 μm/m·K23.1 μm/m·KCopper
Oxidation BehaviorConductive oxideInsulating oxideCopper
Material CostHigher (reference)40-60% cheaperAluminum
Conduit Size NeededSmaller~1.5× largerCopper
Installation EaseStandardRequires AL-rated terminationsCopper
Best ForBranch circuits, tight spacesFeeders >100A, long runs

Conductivity: The Fundamental Difference

Electrical conductivity determines how much current a conductor can safely carry for a given cross-sectional area. This is measured against the International Annealed Copper Standard (IACS), where pure annealed copper equals 100%.

Copper Conductivity

Copper's 100% IACS conductivity makes it the most efficient common conductor metal. For the same ampacity:

  • Smaller wire gauge required
  • Smaller conduit size
  • Less voltage drop per foot
  • Better heat dissipation per unit area

A 100A circuit at 75°C requires #3 AWG copper (0.0520 in² or 33.6 mm²).

Aluminum Conductivity

Aluminum's 61% IACS conductivity means larger conductors are needed. Per NEC Table 310.16, the same 100A at 75°C requires #1 AWG aluminum (0.0829 in² or 53.5 mm²).

The practical rule of thumb: increase aluminum by 2 AWG sizes to match copper ampacity. #6 Cu ≈ #4 Al, #4 Cu ≈ #2 Al, etc.

Verdict: Conductivity

Winner: Copper — 64% higher conductivity enables smaller conductors, smaller conduit, and reduced voltage drop. This advantage is most significant in space-constrained applications.

Weight: Aluminum's Major Advantage

Despite needing larger cross-sections, aluminum cables are significantly lighter than equivalent copper cables. This has major implications for installation labor and support structures.

The Physics

PropertyCopperAluminumRatio
Density8.9 g/cm³2.7 g/cm³Cu is 3.3× heavier
Relative area (same ampacity)1.0×1.6×Al is 1.6× larger
Net weight (same ampacity)1.0×0.5×Al is 50% lighter

Even with the upsizing required, an aluminum cable weighs roughly half what an equivalent copper cable weighs.

Practical Impact

  • Easier cable pulling: Long horizontal runs and vertical risers are significantly easier with aluminum
  • Reduced support requirements: Lighter cable trays and fewer supports
  • Overhead lines: Aluminum dominates utility transmission due to weight advantage
  • Handling safety: Less installer fatigue, fewer strain injuries

Verdict: Weight

Winner: Aluminum — Even with larger sizing, aluminum cables are 50% lighter than copper equivalents. This reduces installation labor, support costs, and improves safety for long pulls.

Cost Analysis: Where Aluminum Shines

Cost is often the deciding factor, especially for large feeders and services where the difference is substantial.

Material Cost Comparison

Size (Copper)Copper $/ftEquivalent Al SizeAluminum $/ftSavings
#4 AWG$1.50-2.00#2 AWG$0.80-1.2040-47%
#1 AWG$3.00-4.001/0 AWG$1.50-2.0050%
4/0 AWG$8.00-12.00250 kcmil$4.00-6.0050%
250 kcmil$12.00-16.00350 kcmil$6.00-8.0050%
500 kcmil$24.00-32.00750 kcmil$12.00-16.0050%

Total Cost of Ownership Example

200A Service Entrance: Copper vs Aluminum Over 25 Years

Given:

  • 200A residential service, 150 ft from meter to panel
  • Three-phase 120/240V
  • Parallel runs in PVC conduit

Copper Option (4/0 AWG Cu):

  • Cable (4/0 Cu THHN × 3 + #4 ground): 150 ft × $35/ft = $5,250
  • Conduit (2" PVC): 150 ft × $3.50/ft = $525
  • Terminations: Standard, included
  • Material Total: $5,775

Aluminum Option (250 kcmil Al):

  • Cable (250 Al THHN × 3 + #4 Cu ground): 150 ft × $20/ft = $3,000
  • Conduit (2.5" PVC for larger Al): 150 ft × $4.50/ft = $675
  • Anti-oxidant compound: $25
  • AL-CU rated lugs (if needed): $50
  • Material Total: $3,750

Result: Aluminum saves $2,025 (35%) on this 200A service despite requiring larger conduit. For larger services (400A+), savings approach 50%.

Verdict: Cost

Winner: Aluminum — Material cost savings of 40-60% for equivalent ampacity. Even with larger conduit and termination accessories, net savings of 30-50% are typical for feeders over 100A.

Reliability and Connections: Copper's Strength

This is where copper's advantages become critical. The long-term behavior of terminations and connections differs significantly between the materials.

Oxidation Behavior

When exposed to air:

  • Copper oxide (Cu₂O) remains electrically conductive
  • Aluminum oxide (Al₂O₃) is an electrical insulator

This means copper connections maintain good contact even without maintenance. Aluminum connections develop insulating oxide layers that increase resistance, causing heat buildup.

Thermal Expansion

PropertyCopperAluminumImpact
Coefficient of expansion16.5 μm/m·K23.1 μm/m·KAl expands 40% more

Aluminum's higher thermal expansion causes connections to loosen over heating/cooling cycles—a phenomenon called "cold flow" or "creep." This is why aluminum requires:

  • Higher-torque terminations
  • More frequent inspection
  • Spring-loaded or compression connectors in some cases

Galvanic Corrosion

When dissimilar metals contact in the presence of moisture, galvanic corrosion occurs. Copper and aluminum have significantly different electrochemical potentials:

  • Copper: +0.34V (cathode, protected)
  • Aluminum: -1.66V (anode, corrodes)

Direct copper-aluminum connections will corrode the aluminum over time. Always use bimetallic (AL-CU rated) connectors when transitioning between materials.

Verdict: Reliability

Winner: Copper — Conductive oxide, lower thermal expansion, and no special termination requirements make copper connections inherently more reliable. Aluminum can match this reliability but requires proper anti-oxidant, torque specifications, and AL-rated terminations.

Application-Specific Recommendations

When to Choose Copper

Use copper when:

  • Branch circuits under 100A: Cost savings from aluminum are minimal, and smaller conduit saves money
  • Space is constrained: Panel interiors, junction boxes, tight conduit runs
  • Wet or corrosive environments: Copper's oxidation behavior is superior
  • Critical infrastructure: Data centers, hospitals, fire alarm circuits—where reliability is paramount
  • Residential branch wiring: Per NEC 334.104, most NM cable is copper
  • Terminations aren't AL-rated: Many older devices accept only copper

Typical Copper Applications:

  • Residential branch circuits (15A-50A)
  • Commercial receptacle and lighting circuits
  • Motor branch circuits under 100A
  • Fire alarm and life safety systems
  • Data and communication wiring

When to Choose Aluminum

Use aluminum when:

  • Service entrances over 100A: Cost savings are substantial
  • Long feeder runs (>50 feet): Weight savings ease installation
  • Large electrical rooms: Conduit space is available
  • Budget is constrained: 30-50% net savings on large feeders
  • Qualified installers available: Proper termination techniques are critical
  • Overhead or utility connections: Weight is critical

Typical Aluminum Applications:

  • Service entrance conductors (200A+)
  • Building feeders to distribution panels
  • Paralleled conductors in large installations
  • Underground utility feeders
  • Temporary/construction power

Installation Considerations

Copper Installation

Copper installation follows standard practices:

  • Strip insulation per connector requirements
  • Insert fully into termination
  • Torque to manufacturer specification
  • No special compounds required (though anti-oxidant doesn't hurt)

Aluminum Installation

Aluminum requires additional care:

  1. Wire brushing: Remove oxide layer immediately before termination
  2. Anti-oxidant compound: Apply to cleaned conductor before inserting (e.g., Noalox, Penetrox)
  3. AL-rated terminations: Verify all lugs, breakers, and devices are marked "AL" or "AL-CU"
  4. Proper torque: Follow manufacturer specifications exactly—overtorque damages soft aluminum, undertorque allows loosening
  5. Re-torque: Some specifications require re-torquing after thermal cycling

Standards and Code Compliance

StandardCopper RequirementsAluminum Requirements
NEC 310.106Standard conductorsMust be AA-8000 series alloy
NEC 110.1460°C or 75°C ratedSame + AL-rated terminations
NEC Table 310.16Base ampacity tableSame table, different columns
UL 486A-486BStandard connectorsAL-rated connectors required
IEC 60228Class 1 or 2 conductorsSame classes apply

Common Mistakes to Avoid

MistakeImpactPrevention
Direct Cu-Al contactGalvanic corrosion, failureUse AL-CU rated bimetallic lugs
Skipping anti-oxidantOxide buildup, overheatingAlways apply to cleaned aluminum
Wrong torqueLoose (fire) or damaged conductorUse calibrated torque tool
Copper-only devices with AlConnection failure, fire riskVerify AL or AL-CU rating
Undersizing for voltage dropExcessive lossesAccount for Al's lower conductivity in long runs
Using old Al alloysCreep, connection looseningSpecify AA-8000 series per NEC

Use these calculators to size and compare copper and aluminum for your specific application:

Key Takeaways

  • Conductivity difference: Copper is 100% IACS, aluminum is 61%—aluminum requires ~1.6× larger cross-section for equivalent ampacity
  • Weight advantage: Aluminum is 70% lighter by volume; even with upsizing, aluminum cables weigh 50% less than copper equivalents
  • When to choose Copper: Branch circuits under 100A, space-constrained installations, critical infrastructure, wet/corrosive environments
  • When to choose Aluminum: Service entrances over 100A, long feeders, weight-sensitive applications, budget-constrained projects with qualified installers
  • Most applications: Copper for residential and light commercial branch circuits; aluminum for large services and feeders

Further Reading

References & Standards

  • NEC (NFPA 70): National Electrical Code, Articles 110, 310, and 334
  • UL 486A-486B: Wire Connectors and Soldering Lugs for Use With Copper and/or Aluminum Conductors
  • ASTM B193: Standard Test Method for Resistivity of Electrical Conductor Materials
  • IEC 60228: Conductors of Insulated Cables

Disclaimer: This comparison provides general technical guidance based on NEC and international standards. Actual performance depends on specific installation conditions, local code amendments, and material specifications. Always consult with licensed electricians and verify compliance with local codes before making final decisions.

Frequently Asked Questions