Table of Contents
For many aspiring HVAC engineers, the psychrometric chart can seem like a complex and intimidating web of lines. However, it is one of the most powerful tools in the field, providing a complete graphical representation of the thermodynamic properties of moist air.
Mastering the psychrometric chart is essential for designing, analyzing, and troubleshooting HVAC systems. This guide will break down the chart into its core components and show you how to use it with confidence.
What is the Psychrometric Chart?
The psychrometric chart is a graphical representation of the properties of air at a constant pressure (usually sea-level atmospheric pressure). It allows engineers to quickly determine the properties of air and visualize the effects of heating, cooling, humidification, and dehumidification processes.
Example: At 25°C dry-bulb () and 50% RH (), you can read from the chart:
Calculate these instantly with our Psychrometric Calculator.
In essence, if you know any two properties of an air sample, you can determine all the others using the chart.
The Key Properties of Air on the Chart
| Property | Symbol | Units | Chart Location |
|---|---|---|---|
| Dry-Bulb Temperature | Tdb | °C or °F | Horizontal axis |
| Wet-Bulb Temperature | Twb | °C or °F | Diagonal lines (left-downward) |
| Relative Humidity | RH | % | Curved lines (0-100%) |
| Humidity Ratio | W | g/kg or lb/lb | Vertical axis (right side) |
| Enthalpy | h | kJ/kg or BTU/lb | Diagonal lines (parallel to Twb) |
| Specific Volume | v | m³/kg or ft³/lb | Nearly vertical lines |
| Dew Point | Tdp | °C or °F | Follow horizontal to saturation |
The chart maps out the following properties:
- Dry-Bulb Temperature: The temperature of the air as measured by a standard thermometer. This is shown on the horizontal axis.
- Wet-Bulb Temperature: The temperature measured by a thermometer with its bulb wrapped in a wet wick. This indicates the cooling effect of evaporation. Lines of constant wet-bulb temperature slope downwards from left to right. You can calculate wet-bulb with our Psychrometric Calculator.
- Relative Humidity (RH): The amount of moisture in the air as a percentage of the maximum amount it could hold at that temperature. These are the curved lines that sweep from the bottom left to the top right. The 100% RH line is the saturation curve on the far left.
- Humidity Ratio (or Absolute Humidity): The actual mass of water vapor per unit mass of dry air (e.g., in grams of water per kilogram of dry air). This is shown on the vertical axis.
- Enthalpy: The total heat content of the air (including both sensible and latent heat). Lines of constant enthalpy are nearly parallel to the wet-bulb temperature lines.
- Specific Volume: The volume of air per unit mass. These lines are steeper and less parallel than the enthalpy lines.
- Dew Point Temperature: The temperature at which the air would become saturated (100% RH) if cooled at a constant pressure. To find it, you move horizontally to the left from your point on the chart until you hit the saturation curve. Use our Dew Point Calculator for quick calculations.
Visualizing the Chart's Axes and Lines
The chart layout consists of: dry-bulb temperature on the horizontal axis, humidity ratio on the vertical axis, relative humidity curves sweeping diagonally, wet-bulb and enthalpy lines running nearly parallel to each other, and specific volume lines at steeper angles.
How to Read the Psychrometric Chart: A Simple Example
Let's find the properties of air at:
- Dry-Bulb Temperature: 25°C
- Relative Humidity: 50%
- Find the Dry-Bulb Temperature: Locate 25°C on the horizontal axis.
- Move Up: Move vertically up from the 25°C mark.
- Find the Relative Humidity Curve: Stop where your vertical line intersects the curved 50% RH line. This is your state point.
- Read the Other Properties: From this single point, you can now read all other properties:
- Humidity Ratio: Move horizontally to the right to read the value on the vertical axis.
- Wet-Bulb Temperature: Follow the diagonal line up and to the left to read the temperature on the saturation curve.
- Dew Point Temperature: Move horizontally to the left to read the temperature on the saturation curve.
- Enthalpy: Read the value from the enthalpy scale, which is usually located outside the main chart area along the wet-bulb lines.
Common HVAC Processes on the Chart
The real power of the psychrometric chart is in visualizing HVAC processes.
- Sensible Heating (e.g., a furnace): A horizontal line moving from left to right. Dry-bulb and wet-bulb temperatures increase, but the humidity ratio remains constant.
- Sensible Cooling (e.g., cooling coils without dehumidification): A horizontal line moving from right to left. Dry-bulb and wet-bulb temperatures decrease, humidity ratio is constant.
- Humidification (e.g., adding steam): A vertical line moving up. The humidity ratio increases, with a slight increase in dry-bulb temperature.
- Dehumidification (e.g., using desiccants): A vertical line moving down. The humidity ratio decreases.
- Cooling and Dehumidification (e.g., a standard air conditioner): A line moving from right to left and downwards. This is the most common air conditioning process. The air is cooled below its dew point, causing moisture to condense out.
Process Line Directions Reference
| HVAC Process | Chart Direction | Temperature | Humidity Ratio | RH |
|---|---|---|---|---|
| Sensible Heating | Horizontal right | ↑ Increases | Constant | ↓ Decreases |
| Sensible Cooling | Horizontal left | ↓ Decreases | Constant | ↑ Increases |
| Humidification (steam) | Nearly vertical up | ↑ Slight increase | ↑ Increases | ↑ Increases |
| Adiabatic Humidification | Along wet-bulb line | ↓ Decreases | ↑ Increases | ↑ Increases |
| Dehumidification (desiccant) | Nearly vertical down | ↑ Increases | ↓ Decreases | ↓ Decreases |
| Cooling + Dehumidification | Diagonal down-left | ↓ Decreases | ↓ Decreases | Approaches 100% |
| Mixing Two Air Streams | Straight line between | Between states | Between states | Between states |
Calculating HVAC Process Energy
For any HVAC process, the energy required can be calculated using enthalpy change:
Where:
- = Heat transfer rate (kW)
- = Mass flow rate of dry air (kg/s)
- = Initial enthalpy (kJ/kg)
- = Final enthalpy (kJ/kg)
Sensible heat only:
Where kJ/(kg·K) for dry air.
Latent heat (moisture addition/removal):
Where kJ/kg (latent heat of vaporization at standard conditions).
Visualizing an Air Conditioning Process
In a typical air conditioning process, warm humid air (e.g., 30°C at 60% RH) passes through the air conditioner coil where it is cooled and dehumidified. The air exits as cool, dry air (e.g., 15°C at 90% RH) while moisture condenses out and drains away. On the psychrometric chart, this process appears as a line moving from the warm air point downward and to the left toward the cooler, drier state.
Why is This Important for HVAC Design?
The psychrometric chart is not just an academic exercise. It is used daily to:
- Calculate Cooling and Heating Loads: Determine how much energy must be added or removed to bring air to the desired condition.
- Design Air Conditioning Systems: Select cooling coils and size equipment to achieve the desired temperature and humidity.
- Analyze Indoor Air Quality: Ensure that ventilation and conditioning processes maintain a healthy and comfortable indoor environment.
- Troubleshoot System Performance: Diagnose issues like inadequate dehumidification or insufficient cooling by plotting the system's performance on the chart.
Worked Example: Cooling Load Calculation Using Psychrometrics
Let's calculate the cooling capacity required for an office air conditioning system using psychrometric principles.
Problem Statement
An office has the following conditions:
- Outside air: 35°C dry-bulb, 50% RH (summer design day)
- Required indoor conditions: 24°C dry-bulb, 50% RH
- Supply air temperature: 14°C (leaving cooling coil)
- Airflow rate: 1,500 L/s
- Outdoor air fraction: 20%
Step 1: Determine Air Properties from the Chart
Outside air (Point 1): 35°C DB, 50% RH
- = 72 kJ/kg (from chart or calculator)
- = 18 g/kg
Room air (Point 2): 24°C DB, 50% RH
- = 48 kJ/kg
- = 9.3 g/kg
Supply air (Point 3): 14°C DB, ~90% RH (after coil)
- = 36 kJ/kg
- = 8.8 g/kg
Step 2: Calculate Mixed Air Conditions
With 20% outdoor air and 80% return air:
Step 3: Calculate Cooling Coil Load
Mass flow rate:
Total cooling load (mixed air to supply air):
Step 4: Separate Sensible and Latent Loads
Sensible cooling:
Latent cooling (dehumidification):
Summary
| Parameter | Value | Notes |
|---|---|---|
| Total cooling load | 30.2 kW | Mixed air to supply |
| Sensible heat ratio | 0.72 | 21.7 / 30.2 |
| Latent load | 9.9 kW | Dehumidification |
| Required tonnage | 8.6 RT | 30.2 ÷ 3.517 |
Worked Example 2: Winter Humidification Load
Let's calculate the humidification requirement for a building in winter using psychrometric principles.
Problem Statement
An office building requires humidification during winter:
- Indoor conditions: 22°C dry-bulb, 40% RH (target)
- Outdoor air: -5°C dry-bulb, 80% RH
- Ventilation rate: 2,000 L/s outdoor air
- Question: How much steam is needed for humidification?
Step 1: Determine Air Properties
Outdoor air (Point 1): -5°C DB, 80% RH
- = 2.0 g/kg (from chart or calculator)
- Very dry in absolute terms despite high RH
Indoor target (Point 2): 22°C DB, 40% RH
- = 6.5 g/kg
- Moisture content must increase significantly
Step 2: Calculate Moisture Addition Required
Step 3: Calculate Mass Flow Rate of Dry Air
Step 4: Calculate Steam Requirement
Step 5: Calculate Energy for Steam Generation
If using electric humidifier (latent heat of vaporization):
Summary
| Parameter | Value | Notes |
|---|---|---|
| Moisture deficit | 4.5 g/kg | Outdoor vs. indoor |
| Steam requirement | 38.9 kg/hr | For 2,000 L/s outdoor air |
| Electric load | 27 kW | If using electric steam |
| Operating cost | ~3.50 USD/hr | At 0.13 USD/kWh |
Common Psychrometric Mistakes and How to Avoid Them
Even experienced HVAC engineers make errors when working with psychrometric charts. Here are the most common mistakes and their solutions:
Mistake 1: Using Sea-Level Charts at Altitude
Problem: Standard psychrometric charts are constructed for 101.325 kPa (sea level). At Denver (1,609m), atmospheric pressure is ~83 kPa.
Impact: Air density is 18% lower, changing all humidity-related calculations.
Fix: Use altitude-corrected charts or apply correction factor:
Mistake 2: Confusing Wet-Bulb and Dew Point
Problem: Both involve saturation, but they're fundamentally different.
| Property | Definition | Found By |
|---|---|---|
| Wet-bulb | Temperature if air were adiabatically saturated | Follow wet-bulb line to saturation |
| Dew point | Temperature where moisture condenses | Move horizontally left to saturation |
Key Insight: Dew point depends only on moisture content; wet-bulb depends on both temperature and moisture.
Mistake 3: Incorrect Process Line Direction
Problem: Drawing cooling lines in the wrong direction.
Rule: Cooling and dehumidification always moves toward the saturation curve (down and left). If your process line moves away from saturation during cooling, something is wrong.
Mistake 4: Ignoring the Bypass Factor
Problem: Assuming all air contacts the coil surface during cooling.
Reality: Real cooling coils have bypass factors of 5-15%. Some air passes without contacting the cold surface.
Corrected calculation:
Where = bypass factor (typically 0.05-0.15).
Quick Reference: Typical Air Conditions
| Location/Condition | Dry-Bulb | RH | Humidity Ratio | Enthalpy |
|---|---|---|---|---|
| Summer outdoor (hot/humid) | 35°C | 60% | 21 g/kg | 89 kJ/kg |
| Summer outdoor (hot/dry) | 38°C | 20% | 8 g/kg | 59 kJ/kg |
| Winter outdoor (cold) | 0°C | 50% | 2 g/kg | 5 kJ/kg |
| Indoor comfort (summer) | 24°C | 50% | 9 g/kg | 48 kJ/kg |
| Indoor comfort (winter) | 22°C | 40% | 6.5 g/kg | 39 kJ/kg |
| AHU supply air | 13-15°C | 90-95% | 8-9 g/kg | 34-38 kJ/kg |
Quick Diagnostic: Using Psychrometrics to Troubleshoot HVAC Problems
When a system isn't performing as expected, psychrometric analysis can quickly identify the issue:
| Complaint | Measure | Chart Analysis | Likely Cause |
|---|---|---|---|
| "Too humid" | High indoor RH despite AC running | Supply air RH > 95% | Coil oversized (SHR too high) |
| "Too dry" (winter) | Low indoor RH despite humidifier | Supply humidity ratio unchanged | Humidifier undersized or not running |
| "Cold drafts" | Low supply air temp | Supply DB < 12°C | Excessive outside air or failed economizer |
| "Stuffy" | High CO₂, normal temp/RH | Process lines show minimal outdoor air | Inadequate ventilation |
| "AC runs but doesn't cool" | High return air enthalpy | Compare to design enthalpy | Internal loads exceed design |
Quick Property Lookup
For common HVAC scenarios, use these approximations:
Dry-bulb 24°C, 50% RH (comfort baseline):
- Wet-bulb: 17°C
- Dew point: 13°C
- Humidity ratio: 9.3 g/kg
- Enthalpy: 48 kJ/kg
- Specific volume: 0.855 m³/kg
Supply air at 13°C, 95% RH (typical AHU discharge):
- Wet-bulb: 12.5°C
- Dew point: 12°C
- Humidity ratio: 8.9 g/kg
- Enthalpy: 36 kJ/kg
Industry Standards Reference
The psychrometric properties and calculations in this guide follow ASHRAE 55 (Thermal Environmental Conditions for Human Occupancy) and ASHRAE Fundamentals Handbook Chapter 1 (Psychrometrics). Air conditioning design parameters should comply with ASHRAE 62.1 (Ventilation for Acceptable Indoor Air Quality). These references contain detailed property tables and formulas used in professional HVAC calculations worldwide.
Psychrometric Design Checklist
Use this checklist for every HVAC design involving psychrometrics:
Pre-Design:
- Confirm design outdoor conditions (ASHRAE weather data)
- Establish indoor comfort criteria (ASHRAE 55)
- Identify sensible and latent loads separately
- Determine required fresh air quantity (ASHRAE 62.1)
Coil Selection:
- Calculate mixed air conditions (outdoor + return)
- Verify coil leaving conditions meet humidity target
- Check sensible heat ratio matches equipment capability
- Confirm coil can handle peak latent load
Verification:
- Plot all air states on psychrometric chart
- Verify process lines are physically reasonable
- Check that no state exceeds 95% RH (except coil leaving)
- Calculate total cooling/heating load from enthalpy change
Field Application: Quick Coil Selection Check
When selecting a cooling coil, use this quick check to verify your design:
Step 1: Calculate Sensible Heat Ratio (SHR)
Typical values:
- Office buildings: 0.75-0.85
- Retail spaces: 0.70-0.80
- Gymnasiums: 0.50-0.65 (high latent)
Step 2: Draw Process Line
Starting from room conditions (24°C, 50% RH), draw a line toward the saturation curve. The slope represents your SHR.
Step 3: Verify Coil Leaving Conditions
The intersection with the 90-95% RH curve gives your apparatus dew point.
Conclusion
The psychrometric chart is a foundational tool for any HVAC professional.
Understanding its layout unlocks a powerful method for analyzing HVAC systems. Digital calculators provide quick answers. But visualizing processes on the chart provides deeper understanding—invaluable in the field.