Psychrometric Calculator

ASHRAE FundamentalsASHRAE 55
Psychrometric Analysis
Select analysis mode and enter air properties to calculate psychrometric state.

Select the type of psychrometric analysis

Select which two properties you know

°C

Air temperature (°C)

°C

Wet bulb temperature (°C)

m

Altitude above sea level (auto-calculates pressure). Examples: Denver 1,609m, Mexico City 2,240m

kPa

Total pressure (kPa). Auto-calculated from elevation, or enter manually

Frequently Asked Questions

Common questions about this calculator

Psychrometric properties describe moist air characteristics: dry-bulb temperature (sensible heat), wet-bulb temperature (evaporative cooling limit), dew point (condensation temperature), relative humidity (moisture saturation %), humidity ratio (water mass per kg dry air), and enthalpy (total heat content). These properties are interrelated—knowing any two determines all others.

Enthalpy (h) is the total heat content of moist air, measured in kJ/kg or BTU/lb. It combines sensible heat (temperature-related) and latent heat (moisture-related). Enthalpy is crucial for calculating cooling coil loads, heating requirements, and energy in air handling processes. Typical indoor air has enthalpy around 40-50 kJ/kg.

Dew point is the temperature at which air becomes 100% saturated and water vapor begins condensing. Calculate it from dry-bulb temperature and relative humidity, or read directly on a psychrometric chart by following a horizontal humidity ratio line to the saturation curve. Dew point determines condensation risk on cold surfaces.

Sensible Heat Ratio (SHR) is the fraction of total cooling load that is sensible heat, calculated as SHR = Sensible Load / Total Load. SHR typically ranges from 0.7-0.9 for comfort cooling. Higher SHR means more temperature reduction, lower SHR means more dehumidification. SHR determines the slope of the conditioning process line on a psychrometric chart.

When two airstreams mix, the resulting conditions lie on a straight line connecting both states, positioned by mass flow ratio. Use the formula: Mixed DB = (m₁×DB₁ + m₂×DB₂)/(m₁+m₂), and similarly for humidity ratio. This is essential for calculating return air mixing with outdoor air in air handling units.

Psychrometrics covers all air conditioning processes: sensible heating (horizontal line right), sensible cooling (horizontal line left), humidification (diagonal up), dehumidification (diagonal down), evaporative cooling (constant wet-bulb line), and combined heating/cooling with humidity control. Each process has a characteristic direction on the chart.
Loading visualizer...

Learn More

Psychrometrics is the science of moist air properties and their interactions, fundamental to all HVAC system design, analysis, and operation. Atmospheric air is a mixture of dry air and water vapor, with the water vapor content affecting thermal comfort, equipment performance, and energy consumption. The psychrometric chart graphically represents the thermodynamic properties of moist air, enabling engineers to visualize air conditioning processes such as heating, cooling, humidification, and dehumidification. Understanding psychrometric principles is essential for proper equipment selection, process control, and energy optimization.

Temperature Measurements: Dry-bulb temperature is measured by a standard thermometer, representing the sensible heat content of air. Wet-bulb temperature indicates the lowest temperature achievable through evaporative cooling, measured using a wetted wick exposed to moving air. The wet-bulb depression (difference between dry-bulb and wet-bulb) indicates the air's moisture-absorbing capacity. Dew point temperature is where water vapor begins to condense when air is cooled at constant pressure, directly indicating absolute moisture content. These temperature values define unique state points on the psychrometric chart.

Humidity Properties: Relative humidity expresses the ratio of actual water vapor pressure to saturation vapor pressure at the same temperature, typically 30-60% for human thermal comfort per ASHRAE Standard 55. Humidity ratio is the mass of water vapor per unit mass of dry air, remaining constant during sensible heating or cooling processes. Enthalpy represents total heat content per unit mass of dry air, including both sensible heat (temperature-related) and latent heat (moisture-related). These properties are critical for cooling load calculations and equipment sizing.

Psychrometric Processes: Sensible heating increases dry-bulb temperature while maintaining constant humidity ratio, moving horizontally right on the psychrometric chart. Sensible cooling reduces temperature at constant humidity ratio until reaching the dew point, where further cooling causes dehumidification. Humidification adds moisture, achievable through steam injection or evaporative cooling along constant wet-bulb lines. Dehumidification involves cooling air below its dew point temperature, condensing water vapor on cooling coil surfaces. The sensible heat ratio (SHR) defines the slope of the cooling process line, critical for matching equipment capacity to building load characteristics.

Air Mixing and Economizer Control: Mixing processes combine two air streams, such as outdoor ventilation air with recirculated return air in air handling units. The mixed air condition lies on a straight line between the two inlet states, with position determined by mass flow ratio. Psychrometric analysis of mixing is essential for economizer control strategies, where varying the outdoor air fraction optimizes free cooling. Enthalpy comparison determines whether outdoor air conditions justify increased ventilation for cooling rather than mechanical refrigeration, enabling significant energy savings in temperate climates.

Advanced Applications: Industrial processes demand precise psychrometric control for product quality. Data centers maintain 40-50% RH to minimize corrosion while avoiding static discharge. Clean rooms for semiconductor fabrication specify temperature ±0.1°C and humidity ±1% RH. Desiccant dehumidification systems can achieve dew points below 0°C for specialized applications. Modern building automation systems continuously monitor psychrometric conditions, optimizing HVAC operation through demand-controlled ventilation and predictive controls that leverage weather forecasts and building thermal mass for energy efficiency.

Standards Reference: ASHRAE Standard 55 defines thermal comfort zones (30-60% RH, 20-26°C). ASHRAE Standard 62.1 specifies ventilation rates and indoor air quality requirements. ASHRAE Fundamentals Handbook provides psychrometric charts for various elevations and detailed calculation procedures for all air properties.

Office Space Thermal Comfort - Summer Design Conditions Analysis

Analyze psychrometric properties for office space to verify ASHRAE 55 thermal comfort compliance and size cooling system

1
Dry-Bulb Temperature: 24.0°C
2
Wet-Bulb Temperature: 17.1°C
3
Relative Humidity: 50.0%
4
Ventilation Rate: 10,000 m³/h (2.78 m³/s)
5
Atmospheric Pressure: 101.325 kPa

Result

Psychrometric State:
ASHRAE 55 Compliant

Calculated Properties

  • Dry-Bulb: 24.0°C
  • Wet-Bulb: 17.1°C (6.9K depression)
  • Relative Humidity: 50.0%
  • Dew Point: 12.9°C
  • Enthalpy: 47.8 kJ/kg dry air
  • Humidity Ratio: 0.00930 kg/kg (9.30 g/kg)
  • Specific Volume: 0.854 m³/kg
  • Vapor Pressure: 1.49 kPa (50% of 2.99 kPa saturation)

Compliance

  • Status: COMPLIANT with ASHRAE 55 thermal comfort zone
  • 24°C @ 50% RH falls within summer comfort boundary

Cooling System Requirements

  • Typical office SHR: 70% sensible / 30% latent
  • Leaving coil condition: 12°C supply, 95% RH (h = 33.0 kJ/kg, W = 0.00829 kg/kg)
  • Enthalpy difference: 47.8 - 33.0 = 14.8 kJ/kg

Calculations

  • Mass flow: 2.78 m³/s ÷ 0.854 m³/kg = 3.25 kg/s
  • Cooling capacity: 3.25 kg/s × 14.8 kJ/kg = 48.2 kW (13.7 tons)
  • Dehumidification: (0.00930 - 0.00829) × 3.25 = 0.00329 kg/s = 11.8 kg/hr condensate

Additional Notes

Per ASHRAE Fundamentals, psychrometric calculations determine air properties (temperature, humidity, enthalpy, dew point) for HVAC system design. Key relationships: Relative humidity decreases as dry-bulb temperature increases (constant moisture content). Cooling processes follow saturation curve. Use psychrometric chart or equations for accurate calculations. Critical for comfort (40-60% RH recommended), condensation prevention, and energy analysis.

Cooling Coil Sizing - Sensible and Latent Load Calculation

Size cooling coil for commercial air handler with both sensible and latent cooling requirements

1
Inlet Dry-Bulb Temperature: 25.0°C
2
Inlet Wet-Bulb Temperature: 19.5°C
3
Inlet Relative Humidity: 60%
4
Outlet Dry-Bulb Temperature: 13.0°C
5
Outlet Wet-Bulb Temperature: 12.1°C
6
Outlet Relative Humidity: 90%
7
Mass Flow Rate: 12.0 kg/s
8
Atmospheric Pressure: 101.325 kPa

Result

Total Cooling Capacity:
254.4 kW (72 tons)

Inlet State

  • 25.0°C DB, 19.5°C WB, 60% RH
  • Dew Point: 16.7°C
  • Enthalpy: 55.5 kJ/kg
  • Humidity Ratio: 0.01190 kg/kg

Outlet State

  • 13.0°C DB, 12.1°C WB, 90% RH
  • Dew Point: 11.4°C
  • Enthalpy: 34.3 kJ/kg
  • Humidity Ratio: 0.00839 kg/kg

Heat Removal

  • Total (enthalpy): 12.0 kg/s × (55.5-34.3) kJ/kg = 254.4 kW (72.3 tons)
  • Sensible: 12.0 kg/s × 1.006 × (25-13)K = 144.9 kW (41.2 tons)
  • Latent: Total - Sensible = 254.4 - 144.9 = 109.5 kW (31.1 tons)
  • Sensible Heat Ratio: 144.9 ÷ 254.4 = 0.57 (57% sensible, 43% latent)

Moisture Removal

  • Rate: 12.0 × (0.01190-0.00839) = 0.042 kg/s = 152 kg/hr
  • Condensate drain: 2" minimum per IPC (40 GPH)
  • P-trap 100mm depth for -250 Pa coil pressure

Coil Selection

  • 8-row chilled water coil
  • Water: 7°C EWT, 11°C LWT, 38 GPM
  • Face velocity: 2.5 m/s (typical 2.0-3.0 m/s)

Status

  • SHR 0.57 indicates high latent load (typical office 0.70-0.75)
  • Verify high occupancy or outdoor air is expected

Additional Notes

Commercial HVAC systems per ASHRAE 62.1 require psychrometric analysis for: ventilation air mixing, cooling coil design, humidification/dehumidification sizing, and energy recovery calculations. Mixed air conditions: Weighted average of outdoor and return air based on flow rates. Cooling coil outlet: Sized for leaving air temperature and required dehumidification (apparatus dew point method). Monitor dew point to prevent condensation in ducts.

Economizer Mixed Air Analysis - Free Cooling Optimization

Analyze mixed air conditions for economizer operation to optimize free cooling and reduce mechanical cooling energy consumption

1
Stream 1 Dry-Bulb Temperature: 15.0°C
2
Stream 1 Wet-Bulb Temperature: 10.8°C
3
Stream 1 Relative Humidity: 60%
4
Stream 1 Mass Flow Rate: 9.6 kg/s
5
Stream 2 Dry-Bulb Temperature: 26.0°C
6
Stream 2 Wet-Bulb Temperature: 17.9°C
7
Stream 2 Mass Flow Rate: 2.4 kg/s
8
Atmospheric Pressure: 101.325 kPa

Result

Mixed Air Conditions:
17.2°C DB, 57% RH

Stream 1 (Outdoor Air)

  • 15.0°C DB, 10.8°C WB, 60% RH
  • Dew Point: 7.3°C
  • Enthalpy: 31.1 kJ/kg
  • Humidity Ratio: 0.00635 kg/kg

Stream 2 (Return Air)

  • 26.0°C DB, 17.9°C WB, 45% RH
  • Dew Point: 13.2°C
  • Enthalpy: 50.2 kJ/kg
  • Humidity Ratio: 0.00943 kg/kg

Mixed Air Conditions (80% OA)

  • 17.2°C DB, 12.4°C WB, 57% RH
  • Dew Point: 8.7°C
  • Enthalpy: 34.9 kJ/kg
  • Humidity Ratio: 0.00696 kg/kg
  • Total mass flow: 12.0 kg/s

Economizer Savings Analysis

Cooling the mixed air to a 13°C / 90% RH supply setpoint (h = 34.3 kJ/kg) at 12 kg/s:
| Condition | Mixed Air | Cooling Load | |

Additional Notes

Industrial process environments require precise psychrometric control per application requirements. Clean rooms: Maintain ±2°F temperature, ±5% RH. Data centers: 18-27°C, 40-60% RH per ASHRAE TC 9.9. Drying processes: Calculate moisture removal rate, size dehumidification equipment. High-temperature processes: Account for air density changes affecting fan performance. Install sensors: dry-bulb, wet-bulb (or RH), and dew point for complete monitoring.