Comparisons
electricalComparison

Star vs Delta

Star vs delta motor connection comparison: starting current, torque, voltage relationships, and application guidelines with IEC/NEC standards for motor wiring.

Enginist Team
Published: November 9, 2025
Updated: November 14, 2025

Star vs Delta Connection (Motors): Complete Engineering Comparison

Quick AnswerWhat is the difference between star and delta motor connection?
In star (Y) connection, each winding receives line voltage ÷ √3 (230V from 400V), producing 33% of delta starting current and torque. In delta (Δ), each winding receives full line voltage (400V), providing full torque but 6-8 times full-load starting current. Star-delta starting begins in star for low-current starting, then switches to delta for running—reducing inrush to 33% while achieving full running torque.

Quick Verdict

The choice between star and delta connection—or star-delta starting—depends on the motor application, starting torque requirements, and supply constraints. Understanding the electrical relationships enables proper motor application.

Bottom Line: Use direct-on-line (delta) starting for motors below 7.5 kW where the supply can handle starting current. Use star-delta starting for motors 7.5 kW+ with low starting torque requirements (fans, centrifugal pumps) where starting current must be limited. Use soft starters or VFDs for demanding applications requiring controlled acceleration or where transition current spikes are unacceptable.

Star-delta starting reduces starting current to 33% but also reduces torque to 33%. This fundamental trade-off limits its application to low-torque starts.

At-a-Glance Comparison Table

ParameterStar (Y)Delta (Δ)Relationship
Winding VoltageVL/3V_L / \sqrt{3}VLV_LStar = 58% of Delta
Winding CurrentILI_LIL/3I_L / \sqrt{3}Delta = 3\sqrt{3} × Star
Line CurrentIPhaseI_{Phase}3×IPhase\sqrt{3} \times I_{Phase}Delta = 3\sqrt{3} × Star
Starting Current33% of DOL100% (DOL)Star = 1/3 of Delta
Starting Torque33% of DOL100% (DOL)Star = 1/3 of Delta
Power33% of rated100% ratedStar = 1/3 of Delta
Best UseStarting phaseRunning phaseCombined in Y-Δ starting

Voltage Relationships

The fundamental difference between star and delta is how voltage divides across the motor windings.

Star Connection Voltage

In star connection, the three winding ends connect to a common neutral point:

Vwinding=Vline3=400V1.732=231VV_{winding} = \frac{V_{line}}{\sqrt{3}} = \frac{400V}{1.732} = 231V

Each winding sees only 58% of line voltage. This reduced voltage:

  • Limits magnetic flux in the motor
  • Reduces starting current proportionally
  • Reduces torque by the square of the voltage ratio

Physical arrangement:

  • U1, V1, W1 connected to line terminals
  • U2, V2, W2 connected together (star point)
  • Current path: Line → Winding → Neutral → Different winding → Different line

Delta Connection Voltage

In delta connection, windings connect end-to-end in a closed triangle:

Vwinding=Vline=400VV_{winding} = V_{line} = 400V

Each winding receives full line voltage. This provides:

  • Full magnetic flux and normal operation
  • Full starting torque capability
  • Higher starting current (6-8× FLA typical)

Physical arrangement:

  • U1-V2, V1-W2, W1-U2 connected
  • Line connections at U1-W2, V1-U2, W1-V2 junctions
  • Current path: Line → Winding → Adjacent line

Voltage Rating Requirements

For star-delta starting on a 400V supply:

  • Motor must be rated 400/690V (or 400V Δ / 690V Y)
  • This means: 400V per winding in delta, 690V per winding in star
  • When star-started at 400V supply: 400V÷3=231V400V \div \sqrt{3} = 231V per winding (acceptable)
  • When running in delta at 400V: 400V per winding (rated value)

A motor rated only 400V cannot use star-delta starting on a 400V supply—it would receive only 231V per winding in delta, producing inadequate torque.

Verdict: Voltage

Key Understanding: The 3\sqrt{3} relationship is fundamental. Star reduces winding voltage to 58% of line, affecting all other parameters proportionally or by the square.

Current Relationships

Current behavior differs significantly between star and delta connections, directly affecting starting current limitations.

Star Connection Current

In star, line current equals phase (winding) current:

Iline=IphaseI_{line} = I_{phase}

During starting:

  • Winding voltage is reduced to 58%
  • Winding impedance remains the same
  • Starting current reduces proportionally to voltage
  • Line current = Phase current = VL/3Zwinding\frac{V_L / \sqrt{3}}{Z_{winding}}

Compared to delta starting: Istart(star)=Istart(delta)3I_{start(star)} = \frac{I_{start(delta)}}{3}

Star starting current is one-third of delta starting current.

Delta Connection Current

In delta, line current is 3\sqrt{3} times phase current:

Iline=3×IphaseI_{line} = \sqrt{3} \times I_{phase}

During starting:

  • Full line voltage across each winding
  • Each winding draws full starting current
  • Line current = 3×\sqrt{3} \times winding current due to the triangle connection

Typical values:

  • Full-load current (FLA): Nameplate value
  • Starting current (DOL): 6-8× FLA typically
  • Starting current (star): 2-2.7× FLA (= DOL ÷ 3)

Current Comparison Example

30 kW Motor Starting Current Comparison

Given:

  • Motor: 30 kW, 400V, 55A FLA
  • DOL starting current: 7× FLA = 385A

Delta (DOL) Starting:

  • Line current: 385A for 3-5 seconds
  • Voltage dip: Significant on weak supplies
  • Protection: Must not trip on 385A

Star Starting:

  • Line current: 385A ÷ 3 = 128A
  • Voltage dip: Much reduced
  • Protection: Easily accommodated

Transition to Delta:

  • Motor reaches ~90% speed in star
  • Brief open-transition period
  • Reconnects in delta at 100-150A
  • Some transition spike possible

Verdict: Current

Winner: Star for starting current — 33% starting current is star's main advantage. However, this comes with 33% starting torque, limiting applications to low-torque starts.

Torque Relationships

Motor torque is proportional to the square of applied voltage—this is critical for understanding star-delta limitations.

Torque-Voltage Relationship

TV2T \propto V^2

In star connection: Tstar=(13)2×Tdelta=13×TdeltaT_{star} = \left(\frac{1}{\sqrt{3}}\right)^2 \times T_{delta} = \frac{1}{3} \times T_{delta}

Star starting torque is one-third of delta starting torque.

Starting Torque Comparison

Motor Start TypeStarting TorqueStarting Current
Direct-on-line (Delta)100% (1.5-2.5× FLT typical)100% (6-8× FLA)
Star-delta33% (0.5-0.8× FLT)33% (2-2.7× FLA)
Soft starter (50% V)25%50%
VFD (150% current)150%+ (adjustable)100-150%

Application Limitations

Star-delta starting is only suitable when:

  • Load torque at start is less than 33% of motor starting torque
  • Motor can accelerate to near-rated speed before switching to delta
  • Transition torque dip doesn't cause deceleration

Suitable loads:

  • Centrifugal fans (torque ∝ speed²)
  • Centrifugal pumps (torque ∝ speed²)
  • Unloaded conveyors
  • Generators starting unloaded

Unsuitable loads:

  • Loaded conveyors
  • Positive displacement pumps
  • Crushers, mills, grinders
  • Compressors with load
  • High-inertia flywheels

Verdict: Torque

Winner: Delta for torque — Full voltage provides full torque. Star-delta is a compromise accepting reduced torque for reduced current. Choose based on application torque requirements.

Star-Delta Starting Sequence

Understanding the complete starting sequence helps with proper application and troubleshooting.

Starting Sequence Phases

Phase 1: Star Starting (t = 0 to t₁)

  1. Main contactor closes (connects motor to supply)
  2. Star contactor closes (creates neutral point)
  3. Motor starts with 33% current and 33% torque
  4. Motor accelerates toward rated speed
  5. Timer counts down (typically 3-10 seconds)

Phase 2: Transition (t = t₁)

  1. Timer expires
  2. Star contactor opens (motor disconnected briefly)
  3. Brief coast-down period (open transition)
  4. Delta contactor closes
  5. Motor reconnects at full voltage

Phase 3: Delta Running (t > t₁)

  1. Motor operates at full voltage
  2. Normal running current (FLA at rated load)
  3. Full torque available

Transition Current Spike

The open-transition period creates a current spike:

  • Motor is briefly disconnected (50-100ms typical)
  • Motor back-EMF decays during coast
  • Reconnection in delta at voltage phase may not match motor phase
  • Current spike can approach DOL starting current momentarily

Closed-transition starting uses a fourth contactor with resistors to maintain connection during transition, reducing the spike. This adds cost but provides smoother transition.

Timer Setting Guidelines

Load TypeTypical TimerNotes
Fans (light)3-5 secondsQuick acceleration
Fans (heavy)5-8 secondsHigher inertia
Pumps (centrifugal)5-10 secondsDepends on head
Compressors (unloaded)8-15 secondsHigh inertia

Setting too short: Motor hasn't reached speed → high transition current Setting too long: Motor runs inefficiently in star → overheating risk

Motor Starting Method Comparison

Direct-On-Line (DOL)

Advantages:

  • Simplest and cheapest
  • Full starting torque
  • No transition issues
  • Suitable for small motors

Disadvantages:

  • High starting current (6-8× FLA)
  • Voltage dip on supply
  • Mechanical stress on coupling

Best for: Motors under 7.5 kW, strong supplies

Star-Delta

Advantages:

  • Reduces starting current to 33%
  • Lower cost than soft starter/VFD
  • No power electronics to fail
  • Established technology

Disadvantages:

  • Starting torque reduced to 33%
  • Open-transition current spike
  • Requires six-terminal motor
  • Not suitable for high-torque starts

Best for: 7.5-200 kW motors with low-torque starts

Soft Starter

Advantages:

  • Adjustable current limit (typically 300-500%)
  • Smooth acceleration ramp
  • No transition spike
  • Works with three-terminal motors

Disadvantages:

  • Higher cost than star-delta
  • Power electronics can fail
  • Limited torque at reduced voltage
  • Heat dissipation requirements

Best for: Variable starting requirements, smooth acceleration needed

Variable Frequency Drive (VFD)

Advantages:

  • Full torque from zero speed
  • Current limited to 100-150% FLA
  • Speed control during operation
  • Energy savings for variable loads

Disadvantages:

  • Highest cost
  • Harmonics may require filtering
  • Motor insulation requirements
  • Complexity

Best for: Demanding starts, speed control needed, energy optimization

Common Mistakes to Avoid

MistakeImpactPrevention
Wrong motor voltage ratingMotor damaged or won't startVerify 400/690V rating for 400V Y-Δ
Star-delta on high-torque loadMotor stalls, overheatsCalculate starting torque requirement
Timer too shortHigh transition currentSet for 80-95% speed attainment
Timer too longOverheating in starMonitor star-phase duration
Wrong terminal connectionsMotor doesn't start or reversesFollow IEC terminal marking standard
Simultaneous star-delta closureShort circuitVerify interlocks working

Use these calculators to analyze motor starting:

Key Takeaways

  1. The √3 Rule Governs Everything: In star connection, winding voltage = line voltage ÷ √3 (58%). Since torque is proportional to voltage squared, star provides exactly 1/3 of delta's torque and current—not approximately, but mathematically exact. This 33% figure is non-negotiable physics.

  2. Motor Rating Must Match Your Starting Method: For 400V star-delta starting, your motor MUST be rated 400/690V (not 400V or 230/400V). The lower number is delta (running), the higher is star. Wrong rating = motor damage or inadequate torque.

  3. Star-Delta Only Works for Light Starts: If your load needs more than 33% of motor's locked-rotor torque to begin moving, star-delta will fail. Centrifugal fans and pumps (torque ∝ speed²) are ideal. Conveyors, crushers, and positive displacement pumps are not.

  4. The Transition Spike Is Real: Open-transition switching creates a momentary current spike that can approach DOL levels. Budget for closed-transition starters (4th contactor with resistors) if this spike is problematic for your supply or protection coordination.

  5. Timer Setting Is Critical: Too short = motor hasn't reached speed, causing high transition current. Too long = motor runs inefficiently in star, risking overheating. Target 80-95% of rated speed before transition. Typical range: 3-15 seconds depending on load inertia.

  6. Economics Favor VFDs for New Installations: Star-delta saves money upfront but provides zero speed control, creates transition stress, and offers no energy savings. For motors running variable loads, VFD payback is often under 2 years through energy savings alone.

  7. Six Terminals Required: Star-delta starting is physically impossible with three-terminal motors. Verify your motor has U1, U2, V1, V2, W1, W2 terminals accessible before specifying this starting method.

Further Reading

References & Standards

  • IEC 60034-1: Rotating electrical machines—Rating and performance
  • IEC 60947-4-1: Contactors and motor-starters
  • NEC Article 430: Motors, Motor Circuits, and Controllers
  • IEEE 141 (Red Book): Motor starting analysis

Disclaimer: This comparison provides general technical guidance based on international standards. Actual motor behavior depends on specific design and load characteristics. Always consult motor manufacturer data and licensed engineers for critical applications.

Frequently Asked Questions