Balance Vessel Calculator
Calculate balance vessel (header tank) size for open heating systems according to EN 12828 and TS 2164 standards
Balance vessels (expansion vessels) accommodate thermal expansion in closed-loop hydronic heating systems, preventing dangerous pressure spikes that would otherwise trigger relief valves or damage components. Water expands approximately 4% when heated from 10°C to 100°C—in a 500-liter system, this creates 20 liters of expansion volume requiring safe accommodation. The vessel provides a compressible gas cushion (air or nitrogen) separated from system water by a flexible diaphragm, absorbing expansion while maintaining system pressure within safe operating limits (typically 1.5-3 bar residential, 3-10 bar commercial).
Operating Principle: During heating, expanding water compresses the gas chamber, slightly increasing system pressure. During cooling, compressed gas expands, returning water to the system and decreasing pressure. This maintains pressure above the minimum threshold (preventing pump cavitation and maintaining air vent operation) while staying below maximum limits (preventing relief valve discharge). The diaphragm barrier prevents gas absorption into water, maintaining consistent pre-charge pressure throughout the vessel's 15-25 year service life.
Vessel Types and Construction: Modern diaphragm vessels feature synthetic rubber (EPDM for ≤70°C, butyl/nitrile for 70-120°C) separating water and gas chambers, rated for 200,000-300,000 cycles. Bladder vessels use replaceable bladders for extended service life. Older compression tanks without separators are largely obsolete in European applications per EN 12828 due to gas absorption issues requiring frequent recharging.
Sizing Methodology (EN 12828): Proper sizing requires four parameters: system volume (total water content in boilers, piping, radiators), temperature range (fill temperature to maximum operating temperature), static height (determines minimum pressure), and pressure range (minimum P₀ to maximum Pe). Expansion volume Ve = Vs × (ρcold/ρhot - 1) × SF, where SF = 1.3 residential, 1.5-2.0 commercial per EN 12828. Required vessel volume Vn = Ve / n, where acceptance factor n = (Pe - P₀) / Pe represents usable expansion capacity.
Pre-Charge and Installation: Factory pre-charge should equal 0.9 × P₀ (90% of minimum system pressure). Vessels install on the return line within 500mm upstream of the boiler inlet (coolest, most stable pressure location). EN 12828 requires isolation valve, pressure gauge, safety relief valve, fill/drain valve, and automatic air vent within 500mm radius. Large vessels (>100L) require structural support; seismic zones mandate bracing for vessels >200L per ASCE 7.
Special Considerations: Glycol antifreeze solutions increase expansion volume significantly—30% glycol requires 1.5× larger vessel, 50% glycol requires 1.8× larger vessel compared to water systems. Balance vessels can serve dual purposes: hydraulic separation (allowing primary/secondary circuits to operate independently) and thermal buffering (30L buffer per 100kW boiler power reduces short-cycling 50-70%). Annual inspection verifies pre-charge pressure, checks for diaphragm failure (water in gas chamber), and confirms proper system operation.
Standards Reference: EN 12828 (Design of Heating Systems in Buildings), ASCE 7 Chapter 13 (seismic requirements), ASHRAE Handbook HVAC Systems and Equipment.