Watt to VA Calculator

Convert real power (watts) to apparent power (VA) using VA = W / PF. Use this calculator to size UPS systems, transformers, and generators based on equipment wattage ratings. Accounts for power factor to ensure adequate capacity for reactive loads like motors and computers. Outputs kVA rating for equipment specification.

IEC 60364Power FactorApparent Power
Calculator Input
Enter real power and power factor to calculate apparent power
W

Real power in watts (0.1 - 10,000,000 W)

Power factor (0.1 - 1.0, typical: 0.8-0.95)

Engineering Theory & Fundamentals
Understanding the engineering principles and standards behind this calculator

Converting watts (W) to volt-amperes (VA) is fundamental to understanding the relationship between real power and apparent power in AC electrical systems. This conversion is critical for properly sizing transformers, generators, UPS systems, inverters. Other electrical equipment that must handle both the real power consumed by loads and the reactive power that oscillates within the system. The distinction between watts and volt-amperes represents a core principle in AC power engineering that directly affects equipment selection, system efficiency, utility billing. Electrical infrastructure design.

Real power, measured in watts, represents the actual electrical power consumed by loads to perform useful work—converting electrical energy into mechanical motion, heat, light. Other desired outputs. Real power is what utilities bill for energy consumption, integrated over time as watt-hours (Wh) or kilowatt-hours (kWh). In purely resistive loads such as electric heaters or incandescent lighting, voltage and current waveforms are perfectly in-phase, meaning all electrical power contributes to useful work. For these resistive loads, watts and volt-amperes are numerically equal since power factor equals unity (PF = 1.0).

Apparent power, measured in volt-amperes, represents the total electrical power flowing through AC circuits, combining both real power that performs work and reactive power that oscillates between source and load without performing net work. Apparent power equals the product of RMS voltage and RMS current (S = V × I), regardless of the phase relationship between these waveforms. Electrical equipment including transformers, generators, and UPS systems must be rated in VA because windings, conductors, and switching devices must safely carry the total current, which depends on apparent power rather than real power alone.

The relationship between watts and volt-amperes is governed by power factor (PF), which equals the cosine of the phase angle between voltage and current waveforms. Power factor ranges from 0 to 1 (or 0% to 100%), with unity power factor (PF = 1.0) indicating voltage and current in perfect phase alignment. For loads with power factor less than unity, more VA capacity is required to deliver a given amount of watts. The fundamental conversion relationship is: VA = W / PF. A 1,000-watt load operating at 0.80 power factor requires 1,250 VA capacity (1,000W ÷ 0.80 = 1,250 VA).

Inductive loads such as motors, transformers, ballasts, and solenoids cause current to lag voltage, creating lagging power factor. These devices require magnetic fields for operation, storing energy in those fields during portions of each AC cycle and returning the energy to the source during other portions. This cyclic energy exchange, measured as reactive power in volt-amperes reactive (VAR), performs no net useful work but increases the current that electrical systems must deliver. Typical inductive load power factors range from 0.50 to 0.90, depending on load type and operating conditions.

Capacitive loads, while less common than inductive loads in typical installations, cause current to lead voltage, creating leading power factor. Capacitors store energy in electric fields and can be strategically applied for power factor correction, offsetting inductive reactive power by supplying reactive power locally at the load. Modern electronic loads with switched-mode power supplies often include active power factor correction (PFC) circuits, achieving power factors of 0.95 to 0.99 and minimizing the disparity between watts consumed and VA drawn from the supply.

The power triangle provides geometric visualization of the relationships between real power (W), reactive power (VAR), and apparent power (VA). Real power forms the horizontal leg, reactive power forms the vertical leg, and apparent power forms the hypotenuse of a right triangle. The angle between the real power and apparent power vectors equals the power factor angle θ, where cos(θ) = PF. This geometric relationship yields both the basic formula VA = W / PF and the Pythagorean relationship VA = √(W² + VAR²).

Low power factor creates significant economic and technical challenges in electrical systems. Utilities commonly impose power factor penalties on commercial and industrial customers operating below specified thresholds (typically 0.85 to 0.90 power factor). These penalties manifest as demand charges based on VA or kVA rather than kW, or as explicit surcharges for poor power factor. A facility consuming 100 kW at 0.70 power factor draws 143 VA from the utility, while the same 100 kW at 0.95 power factor draws only 105 VA—a 36% reduction in utility infrastructure burden that utilities reward through favorable rate structures.

From a technical perspective, low power factor increases current magnitude for any given real power delivery, necessitating larger conductors, transformers, switchgear, and protection devices. Higher current also increases I²R resistive losses throughout distribution systems, reducing efficiency and wasting energy as heat. Consider a distribution feeder delivering 50 kW at 0.70 power factor versus 0.95 power factor: the lower power factor requires 34% higher current, resulting in 81% higher resistive losses (since losses scale with current squared). These losses represent wasted energy and reduced system capacity.

Power factor correction involves installing capacitor banks to supply reactive power locally, reducing reactive current drawn from upstream sources. Improving power factor from 0.75 to 0.95 for a 100 kW load reduces VA demand from 133 VA to 105 VA, decreasing current by 21% and resistive losses by 37%. Automatic power factor correction systems use controllers to switch capacitor banks in steps, maintaining target power factor across varying load conditions. However, capacitor installation requires harmonic analysis, as capacitors can create resonance with system inductance, particularly in facilities with variable frequency drives or other harmonic-producing nonlinear loads.

Transformer sizing critically depends on watt-to-VA conversion. Per IEEE C57.12.00 and IEC 60076, transformers are rated in VA (or kVA) because transformer windings must carry total current regardless of load power factor. A transformer supplying 10,000 watts at 0.80 power factor must be rated for at least 12,500 VA (10,000W ÷ 0.80 = 12,500 VA). Undersizing transformers based on watts without considering power factor leads to overheating, accelerated aging, and potential failure. Best practice includes 20-25% capacity margin above calculated VA to accommodate load growth, harmonic heating, and transient overloads.

Generator sizing follows similar principles. Emergency and standby generators must supply both real and reactive power, with excitation systems controlling voltage and reactive power output. Per NFPA 110 and IEEE 446, generators should be sized based on total VA requirements with margins for motor starting (which can require 5-7 times running VA temporarily), altitude derating (approximately 3.5% per 1,000 feet above sea level), temperature derating, and sustained operation at less-than-unity power factor. Modern generator automatic voltage regulators maintain stable voltage across varying power factors, but fundamental VA ratings limit maximum deliverable current.

UPS systems illustrate practical watt-to-VA conversion considerations. Older UPS designs operated at 0.80 power factor output, meaning a 10,000 VA UPS delivered only 8,000 watts maximum. Modern IT loads with power factor correction typically operate at 0.95-0.99 power factor, creating mismatch with 0.80 PF-rated UPS systems. Contemporary UPS designs specify 0.90 or higher output power factor, with many unity power factor (1.0 PF) models now standard. When sizing UPS for data centers, engineers must evaluate both real power requirements (watts) of server loads and ensure adequate VA capacity for any reactive loads in the protected equipment group.

Learn More

Dive deeper with our comprehensive guide

Mathematical Formulas
Engineering equations with detailed explanations and unit references
15 formulas

Usage Examples

Real-world scenarios showing how to use this calculator effectively