Amps to VA Converter
Calculate apparent power in volt-amperes from current in amperes and voltage in volts. Supports single-phase and three-phase systems.
Converting amperes to volt-amperes (VA) establishes the fundamental relationship between current flow and apparent power in AC electrical systems. This conversion is essential for transformer selection, circuit breaker sizing, conductor ampacity determination, and electrical service design. Unlike DC circuits with straightforward power calculations, AC systems require understanding voltage-current relationships and power factor effects. Equipment ratings in VA or kVA reflect total current-handling requirements regardless of whether loads are resistive, inductive, or capacitive.
Apparent Power and Equipment Rating Fundamentals: Volt-amperes represent the product of RMS voltage and RMS current without considering phase relationships: S = V × I for single-phase, S = √3 × V × I for three-phase systems. Transformers, generators, UPS systems, and distribution panels are rated in VA because windings must carry full current regardless of power factor. A 24 kVA transformer delivering 100A at 240V experiences the same thermal stress at 0.80 PF (19.2 kW) as unity PF (24 kW). Per IEEE 100, this distinction between apparent and real power drives equipment specification practices.
Single-Phase and Three-Phase Voltage Relationships: Single-phase 120V circuits produce 120 VA per ampere; 240V circuits yield 240 VA per ampere. Three-phase systems use the √3 multiplier (1.732) accounting for geometric phase relationships in balanced systems. Common voltages include 208V, 480V, and 600V for commercial/industrial applications. At 480V three-phase, 100A represents 83.1 kVA. Understanding these voltage-current-VA relationships ensures correct system design and code compliance for residential through industrial installations.
Protective Device and Conductor Sizing: Per NEC 210.20(A), circuit breakers must be rated at 125% of continuous loads (operating 3+ hours). A 16A continuous load at 120V (1,920 VA) requires a 20A breaker minimum. Conductors must similarly handle 125% of continuous current per NEC Table 310.16, ensuring both protection and conductors operate within thermal limits. Voltage drop per NEC 210.19(A) may require larger conductors than ampacity alone indicates, particularly for long runs or motor loads requiring tight voltage regulation.
Transformer and Panel Loading Analysis: Converting measured current to VA determines loading percentages against equipment ratings. A 40A circuit at 240V provides 9,600 VA capacity; 32A operation represents 80% loading with 20% margin remaining. Balanced three-phase loads allow phase-by-phase evaluation; unbalanced systems require individual phase analysis. IEEE 1100 limits sustained current imbalance to 10% to prevent excessive heating in motors and transformers, which reduces equipment life and efficiency through thermal degradation.
Motor Applications and Generator Sizing: Motor full-load current from NEC Table 430.250 converts to VA for sizing starters, disconnects, and branch circuits. A 25 HP motor at 480V draws 34A, representing 28.2 kVA. Starting currents reach 5-7× FLC, creating transient VA demands for generator and UPS sizing. Per NFPA 110 and IEEE 446, emergency generators require 125% margin above calculated load for transient conditions. Utility billing often includes power factor charges; facilities drawing 800A at 480V (664 kVA) with 560 kW consumption operate at 0.84 PF, potentially triggering penalties below 0.90 thresholds.
Standards Reference: NEC Articles 210, 220, 310, 408, and 430 govern conductor sizing, demand factors, panel ratings, and motor calculations. IEEE C57.91 establishes transformer loading and thermal management guidelines. IEEE 1100 provides power quality and current imbalance limits. IEC 60364-5-52 specifies international conductor ampacity standards. NFPA 110 and IEEE 446 cover emergency generator sizing with appropriate safety margins.
Related Calculators
You might also need these calculators
Referenced Standards & Guidelines
Calculations comply with the following authoritative sources
IEC 60364 - Low-voltage Electrical Installations
IEC 60364 (2017)
International standard for electrical installation design, protection against electric shock, and overcurrent protection.
NEC (National Electrical Code) - NFPA 70
NFPA 70 (2023)
US electrical installation code covering wiring, protection, and equipment standards for safe electrical systems.
IEEE Standards Association
IEEE
Institute of Electrical and Electronics Engineers standards for electrical and electronic systems.
All formulas and calculations are based on peer-reviewed standards and official engineering guidelines
Usage Examples
Real-world scenarios showing how to use this calculator effectively